Plan Review Details - Permit 21061009
Plan Review Stops For Permit 21061009
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-07-23 Cont ID  
Sent By cpuell Date 2021-07-23 Time 09:41 Rev Time 0.00
Received By cpuell Date 2021-07-23 Time 09:41 Sent To  
Notes
2021-07-23 09:42:55PARCEL MERGED OFFICIALLY UNIT 28F PCN AND ADDRESS
 MERGED THE NEW OFFICIAL ADDRESS FOR THE MERGED UNIT AND
 PCN IS 529 S FLAGLER DR # 28E

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By cpuell Date 2021-06-16 Time 12:30 Rev Time 0.00
Received By cpuell Date 2021-06-16 Time 12:30 Sent To  
Notes
2021-06-16 12:31:39HAS A UNITY OF TITLE BEEN APPLIED FOR, IF NOT CONTACT
 VINCE NOEL [email protected]. HAVE YOU GIVEN THE UNITY OF
 TITLE TO THE COUNTY PROPERTY APPRAISER AND HAVE THEY
 GIVEN YOU A SINGLE PROPERTY CONTROL NUMBER FOR THE
 SINGLE UNIT? ONCE THESE STEPS HAVE HAPPENED, PLEASE
 CONTACT [email protected] TO BE ASSIGNED AN ADDRESS FOR
 THE SINGLE UNIT, PLEASE LET KNOW IF YOU HAVE A
 PREFERENCE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-08-03 Cont ID  
Sent By jwitmer Date 2021-08-03 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2021-08-03 Time 10:58 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-07-14 Cont ID  
Sent By jwitmer Date 2021-07-14 Time 16:17 Rev Time 0.00
Received By jwitmer Date 2021-07-14 Time 14:45 Sent To  
Notes
2021-07-14 16:16:56TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-03 Cont ID  
Sent By jwitmer Date 2021-08-03 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2021-08-03 Time 10:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-14 Cont ID  
Sent By jwitmer Date 2021-07-14 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2021-07-14 Time 14:45 Sent To  
Notes
2021-07-14 16:19:23WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21061009
 ADD: 529 S. FLAGLER DR. # 28E & 28F
 CONT: BATTEN CONSTRUCTION INC.
 TEL: 561-820-0027
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 14TH
 ACTION: DENIED
 1) IT APPEARS A UNITY OF TITLE MAY HAVE BEEN UPLOADED.
 THE TOP 1/3 TO ? OF THE DOCUMENT DOES NOT SHOW.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT
 FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 A UNITY OF TITLE IS REQUIRED. SUBMIT APPLICATION TO THE
 ENGINEERING DEPARTMENT:
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 2) SUBMITTED DOCUMENTS, SALES BROCHURES FOR PROFLEX MSC
 90, PLEASE SEE TEST ARE REQUIRED FOR THIS PRODUCT,
 TESTING FOR USE WITH A 6 INCH CONCRETE SLAB. TO DATE
 PROFLEX MSC 90 WE HAVE NOT SEEN ANY TESTING REPORTS FOR
 THIS PRODUCT FOR USE WITH EITHER TILE OR MARBLE.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) SHEET A-002 THIS IS THE PROPOSED FLOOR PLAN, NO
 EXISTING PLAN PROVIDED. 2020 EXISTING BUILDING CODE.
 801.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 THROUGHOUT THE FLOOR PLAN THERE ARE QUITE A FEW DOORS
 THAT ARE NOT 3 FEET WIDE OR EVEN 2FEET 10 INCHES TO
 MAKE A 32-INCH CLEAR DOOR OPENING FOR SWING DOORWAYS.
 2020 FBC-B 1010.1.1 SIZE OF DOORS.
  
 4) SHEET A-002 THIS IS THE PROPOSED FLOOR PLAN, NO
 EXISTING PLAN PROVIDED. THE FLOOR PLAN SHOWS ALL NEW
 PLUMBING FIXTURES, WITHOUT THE EXISTING LAYOUT THE
 PLANS EXAMINER CANNOT TELL IF TUB LOCATIONS ARE MOVED,
 OR IF THEY HAVE BEEN CONVERTED INTO SHOWERS. PLEASE
 SHOW COMPLIANCE FOR THE FOLLOWING CODE SECTIONS:
  
 4A) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4B) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE
 FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 4C) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 4D) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 5) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-07-28 Cont ID  
Sent By jleahy Date 2021-07-28 Time 16:54 Rev Time 0.00
Received By jleahy Date 2021-07-28 Time 16:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-07-01 Cont ID  
Sent By jleahy Date 2021-07-01 Time 18:16 Rev Time 0.00
Received By jleahy Date 2021-07-01 Time 17:40 Sent To  
Notes
2021-07-01 18:15:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER AND PANEL SCHEDULE DON'T MATCH 215.5
  
 PANEL "A" STATES 200A MAIN IN ONE PLACE AND 150A IN
 ANOTHER, IF IT IS 200A 1/0 CONDUCTORS ARE NOT LARGE
 ENOUGH TO FEED A 200A BREAKER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-07-23 Cont ID  
Sent By pleduc Date 2021-07-23 Time   Rev Time 0.00
Received By pleduc Date 2021-07-23 Time 11:06 Sent To  
Notes
2021-07-23 11:32:14FIRE PROVISO COMMENTS
  
 UPDATE THE FIRE CODE EDTIONS TO THE CURRENT 7TH ED. OF
 THE FFPC
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 THE EXISTING FIRE ALARM AND/OR FIRE SPRINKLER SYSTEMS
 SHALL BE MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 ENSURE COMPLIANCE TO AVOID FAILED FIRE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-24 Cont ID  
Sent By pleduc Date 2021-06-24 Time   Rev Time 0.00
Received By pleduc Date 2021-06-24 Time 15:36 Sent To  
Notes
2021-06-24 15:37:40FIRE PROVISO COMMENTS
  
 UPDATE THE FIRE CODE EDTIONS TO THE CURRENT 7TH ED. OF
 THE FFPC
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 THE EXISTING FIRE ALARM AND/OR FIRE SPRINKLER SYSTEMS
 SHALL BE MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 ENSURE COMPLIANCE TO AVOID FAILED FIRE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-03 Cont ID  
Sent By jwitmer Date 2021-08-03 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2021-07-22 Time 16:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-07-14 Time 16:21 Rev Time 0.00
Received By cdecoeur Date 2021-06-23 Time 05:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-07-14 Cont ID  
Sent By jwitmer Date 2021-07-14 Time 16:17 Rev Time 0.00
Received By jwitmer Date 2021-07-14 Time 14:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 09:43 Rev Time 0.00
Received By medwards Date 2021-08-02 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-02 Cont ID  
Sent By medwards Date 2021-07-02 Time 11:03 Rev Time 0.00
Received By medwards Date 2021-07-02 Time 11:03 Sent To  
Notes
2021-07-02 11:04:33PLEASE PROVIDE A MECHANICAL DRAWING THAT HAS THE DUCTS
 AND DUCT SIZES. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-07-06 Cont ID  
Sent By lcrespo Date 2021-07-06 Time 18:09 Rev Time 0.00
Received By lcrespo Date 2021-07-06 Time 18:09 Sent To  
Notes
2021-07-06 18:10:0007/06/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-06-22 Cont ID  
Sent By rgathrig Date 2021-06-22 Time 17:56 Rev Time 0.00
Received By rgathrig Date 2021-06-22 Time 17:56 Sent To  
Notes
2021-06-22 17:57:13PRIVATE PROVIDER INSPECTIONS ONLY APPROVED
  
 RICHARD GATHRIGHT
 561 805 6679

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 09:43 Rev Time 0.00
Received By medwards Date 2021-08-02 Time 09:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-02 Cont ID  
Sent By medwards Date 2021-07-02 Time 11:08 Rev Time 0.00
Received By medwards Date 2021-07-02 Time 11:08 Sent To  
Notes
2021-07-02 11:09:57PLEASE PROVIDE DIGITALLY SIGNED DRAWINGS FROM JAVAD
 AHMAD P.E. AS THE DRAWINGS SUBMITTED WITH HIS NAME
 APPEAR TO NOT HAVE THE REQUIRED DIGITAL SIGNATURE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  