| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL16709-R8 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-4 TO |
| INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| BOTTOM OF THE COVER PAGE. PRINT PAGES 1-4 ONLY. |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R8 SELECTED SYSTEM NO W-4; EXPOSURE |
| (B); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H < 15); |
| ULTIMATE WIND SPEED 170 (MPH) IS NOT CORRECT. THE |
| CORRECT EXPOSURE CATEGORY FOR THE LISTED ADDRESS IS |
| EXPOSURE C. PLEASE SELECT THE CORRECT OPTIONS; CONSIDER |
| USING FL16709-R8 SYSTEM NO. W-4; EXPOSURE C; ENCLOSED; |
| ZONE 1 PRIME #1 (AS-LISTED), ZONE 1 #2, ZONE 2 #4, & |
| ZONE 3 #6; H < 15; 170 (MPH). ALL APPLICABLE DETAILS |
| AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| SITE-SPECIFIC ENGINEERING. |
| |