2021-06-29 17:14:43 | 1ST REVIEW FBC-2020 BUILDING |
| PERMIT- 21060446 |
| 6/29/2021 |
| |
| CODES IN EFFECT: |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE A BASIC FLOOR PLAN DRAWING AND A |
| SCOPE OF WORK FOR THE FLOOR TILE REPLACEMENT. INDICATE |
| THE ALL AREAS TO BE REPLACED AND LIST THE TYPE OF FLOR |
| TILE AND UNDERLAYMENT TO BE INSTALLED- SECTION 107.2.1 |
| WPB. PRODUCT DATA SHEETS FOR TWO TYPES OF UNDERLAYMENT |
| HAVE BEEN SUBMITTED. PLEASE CHOOSE ONE OR THE OTHER AND |
| SUBMIT THE APPLICABLE TEST REPORTS FOR AIRBORNE AND |
| STRUCTURE BORNE SOUND TRANSMISSION BASED ON THE TYPE OF |
| FLOORING TO BE INSTALLED AND THICKNESS OF THE SLAB. |
| |
| 1207.2 AIRBORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN |
| TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE |
| SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND |
| FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY |
| ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND |
| TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST |
| PROCEDURES SET FORTH IN ASTM E90. PENETRATIONS OR |
| OPENINGS IN CONSTRUCTION ASSEMBLIES FOR PIPING; |
| ELECTRICAL DEVICES; RECESSED CABINETS; BATHTUBS; |
| SOFFITS; OR HEATING, VENTILATING OR EXHAUST DUCTS SHALL |
| BE SEALED, LINED, INSULATED OR OTHERWISE TREATED TO |
| MAINTAIN THE REQUIRED RATINGS. THIS REQUIREMENT SHALL |
| NOT APPLY TO ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL |
| BE TIGHT FITTING TO THE FRAME AND SILL. |
| |
| 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS AND |
| SLEEPING UNITS OR BETWEEN A DWELLING UNIT OR SLEEPING |
| UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE |
| SHALL HAVE AN IMPACT INSULATION CLASS RATING OF NOT |
| LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, WHEN |
| TESTED IN ACCORDANCE WITH ASTM E492. ALTERNATIVELY, THE |
| IMPACT INSULATION CLASS OF FLOOR/CEILING ASSEMBLIES |
| SHALL BE ESTABLISHED BY ENGINEERING ANALYSIS BASED ON A |
| COMPARISON OF FLOOR/CEILING ASSEMBLIES HAVING IMPACT |
| INSULATION CLASS RATINGS AS DETERMINED BY THE TEST |
| PROCEDURES SET FORTH IN ASTM E492. |
| |
| 2) PROVIDE A FLOORING UNDERLAYMENT FLAME SPREAD TEST |
| DATA REPORT TO VERIFY THE MATERIAL HAS A FLAME SPREAD |
| INDEX OF NOT MORE THAN 200 WHEN TESTED IN ACCORDANCE |
| WITH ASTM E 84 OR UL 723- SEE SECTIONS 603.1 ITEM 2- |
| EXCEPTION 2, AND SECTION 803.1.1 FBC B |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |