Plan Review Stops For Permit 21060357 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2021-07-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-07-16 |
Time |
08:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-07-16 |
Time |
08:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-07-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-07-07 |
Time |
13:03 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-07-07 |
Time |
13:03 |
Sent To |
|
|
Notes |
2021-07-07 13:07:52 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO, CFM | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT GENERATOR PAD DETAILS WITH GENERATOR TO PAD | | ANCHORING DETAILS AND WIND DESIGN DATA. IF A | | PREFABRICATED GENERATOR PAD IS TO BE USED SUBMIT SITE | | SPECIFIC ENGINEERING FOR THE PAD THAT HAS BEEN | | PREPARED, SIGNED AND SEALED BY A FLORIDA LICENSED | | DESIGN PROFESSIONAL. FBC 107.2.1, FS 471 & 481 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-07-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-07-01 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-07-01 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-06-30 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-06-30 |
Time |
10:32 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-06-30 |
Time |
10:25 |
Sent To |
|
|
Notes |
2021-06-30 10:44:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | FEEDER NOT SUPPLYING ENTIRE LOAD PLEASE CHANGE TO 3/0. | | | | FOR A FEEDER RATED 100 THROUGH 400 AMPERES, THE FEEDER | | CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A | | ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS SUPPLYING | | THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING | | UNIT IN A TWO-FAMILY OR MULTIFAMILY DWELLING, SHALL BE | | PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT | | OF THE FEEDER RATING. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-07-06 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-07-06 |
Time |
08:50 |
Sent To |
|
|
Notes |
2021-07-06 08:50:50 | 07/07/21 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-07-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-07-16 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-07-08 |
Time |
13:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-07-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-07-07 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-06-29 |
Time |
11:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-07-06 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-07-06 |
Time |
08:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-07-16 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-07-16 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-07-16 |
Time |
08:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-07-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-07-07 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-07-07 |
Time |
13:07 |
Sent To |
|
|
Notes |
2021-07-07 13:10:17 | PREFABRICATED GENERATOR PAD DETAILS ARE REQUIRED TO BE | | SIGNED AND SEALED. ELECTRONICALLY SUBMITTED DRAWINGS | | ARE REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S | | DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO | | SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. | | AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN | | SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S | | ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO | | BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF | | THE SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 & | | 61G15 | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2021-07-06 |
Time |
|
Rev Time |
|
Received By |
awooten |
Date |
2021-07-06 |
Time |
|
Sent To |
|
|
Notes |
|
|