Plan Review Details - Permit 21060357
Plan Review Stops For Permit 21060357
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-16 Cont ID  
Sent By rmcdouga Date 2021-07-16 Time 08:23 Rev Time 0.00
Received By rmcdouga Date 2021-07-16 Time 08:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-07 Cont ID  
Sent By rmcdouga Date 2021-07-07 Time 13:03 Rev Time 0.00
Received By rmcdouga Date 2021-07-07 Time 13:03 Sent To  
Notes
2021-07-07 13:07:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO, CFM
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DETAILS WITH GENERATOR TO PAD
 ANCHORING DETAILS AND WIND DESIGN DATA. IF A
 PREFABRICATED GENERATOR PAD IS TO BE USED SUBMIT SITE
 SPECIFIC ENGINEERING FOR THE PAD THAT HAS BEEN
 PREPARED, SIGNED AND SEALED BY A FLORIDA LICENSED
 DESIGN PROFESSIONAL. FBC 107.2.1, FS 471 & 481
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-07-01 Cont ID  
Sent By jleahy Date 2021-07-01 Time 10:24 Rev Time 0.00
Received By jleahy Date 2021-07-01 Time 10:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-30 Cont ID  
Sent By jleahy Date 2021-06-30 Time 10:32 Rev Time 0.00
Received By jleahy Date 2021-06-30 Time 10:25 Sent To  
Notes
2021-06-30 10:44:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FEEDER NOT SUPPLYING ENTIRE LOAD PLEASE CHANGE TO 3/0.
  
 FOR A FEEDER RATED 100 THROUGH 400 AMPERES, THE FEEDER
 CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A
 ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS SUPPLYING
 THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING
 UNIT IN A TWO-FAMILY OR MULTIFAMILY DWELLING, SHALL BE
 PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT
 OF THE FEEDER RATING.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-07-06 Cont ID  
Sent By lcrespo Date 2021-07-06 Time 08:50 Rev Time 0.00
Received By lcrespo Date 2021-07-06 Time 08:50 Sent To  
Notes
2021-07-06 08:50:5007/07/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-16 Cont ID  
Sent By rmcdouga Date 2021-07-16 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2021-07-08 Time 13:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-07 Cont ID  
Sent By rmcdouga Date 2021-07-07 Time 13:10 Rev Time 0.00
Received By rmcdouga Date 2021-06-29 Time 11:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-07-06 Cont ID  
Sent By lcrespo Date 2021-07-06 Time 08:50 Rev Time 0.00
Received By lcrespo Date 2021-07-06 Time 08:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-07-16 Cont ID  
Sent By rmcdouga Date 2021-07-16 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2021-07-16 Time 08:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-07 Cont ID  
Sent By rmcdouga Date 2021-07-07 Time 13:08 Rev Time 0.00
Received By rmcdouga Date 2021-07-07 Time 13:07 Sent To  
Notes
2021-07-07 13:10:17PREFABRICATED GENERATOR PAD DETAILS ARE REQUIRED TO BE
 SIGNED AND SEALED. ELECTRONICALLY SUBMITTED DRAWINGS
 ARE REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO
 BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF
 THE SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 &
 61G15
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-07-06 Cont ID  
Sent By awooten Date 2021-07-06 Time   Rev Time  
Received By awooten Date 2021-07-06 Time   Sent To  
Notes
***NONE***