Plan Review Details - Permit 21060265
Plan Review Stops For Permit 21060265 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2021-07-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2021-07-12 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2021-07-12 |
Time |
15:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-06-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2021-06-30 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2021-06-30 |
Time |
10:31 |
Sent To |
|
|
Notes |
2021-06-30 11:03:12 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | SERVICES/ BUILDING DIVISION | | 2020 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 21060265 | | ADD: 1701 S. FLAGLER DR. # 1208 | | CONT: MARK OF EXCELLENCE CONSTRUCTION / CGC1505007 | | TEL: 561-746-0001 | | E-MAIL: [email protected] | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: | | ACTION: DENIED | | 1) 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED / | | DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES | | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, | | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE | | LICENSED IN AND PLANS DRAWN. | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT | | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE | | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. | | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET | | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR | | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME | | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN | | AND PLANS DRAWN. | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET. | | | | 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | REVIEW CYCLE. | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | 19 | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | 561-718-9724. | | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ | | RETIRED. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-07-20 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-07-20 |
Time |
19:12 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-07-20 |
Time |
18:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-06-12 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-06-12 |
Time |
23:24 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-06-12 |
Time |
22:59 |
Sent To |
|
|
Notes |
2021-06-12 23:24:39 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY | | THE ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT | | ANY ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE | | THAT ON PLAN. FS 471.003(2)(H); 471.025; WPB FBC | | 107.2.1, 107.3.5 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2021-06-25 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2021-06-25 |
Time |
|
Rev Time |
0.00 |
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-07-20 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-07-20 |
Time |
19:13 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-07-09 |
Time |
13:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2021-06-30 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
cdecoeur |
Date |
2021-06-03 |
Time |
14:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-07-15 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-07-15 |
Time |
09:33 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-07-15 |
Time |
09:33 |
Sent To |
|
|
Notes |
2021-07-15 09:34:12 | 07/15/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-06-15 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2021-06-15 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2021-06-15 |
Time |
16:16 |
Sent To |
|
|
Notes |
2021-06-15 16:16:39 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1 | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | MANUAL REVISED 2017 | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH | | EDITION | | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION | | FAC= FLORIDA ADMINISTRATIVE CODE | | FS = FLORIDA STATUTES | | | | | | 1ST REVIEW | | | | PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED | | WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE | | NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER | | PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE | | BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO | | ISSUANCE OF A PERMIT. | | | | PLUMBING COMMENTS: DENIED | | | | PER WPB FBC 104.1, A PLUMBING SUB-PERMIT APPLICATION | | SHALL BE SUBMITTED FOR THIS PROJECT BY A LICENSED | | PLUMBING CONTRACTOR. | | | | 1.AS THE PLANS ARE NOT SIGNED AND SEALED BY A | | PROFESSIONAL ENGINEER OR ARCHITECT, A SEPARATE PLUMBING | | PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR | | THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION | | NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR | | LICENSED IN THE PLUMBING TRADE. | | | | A.PER WPB FBC 107.2.1, PROVIDE A KITCHEN FLOOR PLAN | | NAMED PLUMBING PLAN: PROVIDE THE FOLLOWING: | | 1) INDICATE ACTUAL PLUMBING SCOPE OF WORK I.E. REPLACE | | EXISTING SINK WITH NEW, MAKE PLUMBING CONNECTIONS TO | | SINK, DISHWASHER AND REFRIGERATOR ICE MAKER. | | 2 )PROVIDE NOTE, "ALL WORK TO COMPLY WITH FLORIDA | | PLUMBING CODE 2020 7TH EDITION." | | 3) PROVIDE NOTE, "PROVIDE WATER HAMMER ARRESTORS PER | | FLORIDA PLUMBING CODE 604.9" | | 4) PROVIDE NOTE, "CONNECT DISHWASHER WASTE DIRECTLY TO | | A WYE BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN | | SINK, DIRECTLY TO THE DISHWASHER CONNECTION OF A FOOD | | WASTE DISPOSER, OR THROUGH AN AIR BREAK TO A STANDPIPE. | | THE WASTE LINE OF A RESIDENTIAL DISHWASHER SHALL RISE | | AND BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK | | RIM OR COUNTER TOP PER FLORIDA PLUMBING CODE 604.9" | | | | | | END OF COMMENTS. | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | MOBILE 561-246-0882 | | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND | | THURSDAYS | | | | 21060265 1701 S FLAGLER DR # 1208 |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
N |
Date |
2021-07-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2021-07-22 |
Time |
06:40 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2021-07-22 |
Time |
06:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-07-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2021-07-12 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2021-07-12 |
Time |
15:45 |
Sent To |
|
|
Notes |
2021-07-12 16:04:29 | SIGNATURE FOR BUILDING REVIEW PASSED, BUT THERE STILL | | IS NO PLANS FOR PLUMBING REVIEW AND PLUMBING CONTRACTOR | | SIGNATURE FOR THOSE PAGES. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-06-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2021-06-30 |
Time |
11:01 |
Rev Time |
|
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2021-06-30 11:04:11 | SIGNATURE | | 1ST REVIEW | | DATE: | | ACTION: DENIED | | 1) 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED / | | DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES | | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, | | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE | | LICENSED IN AND PLANS DRAWN. | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT | | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE | | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. | | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET | | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR | | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME | | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN | | AND PLANS DRAWN. | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET. | | | | 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | REVIEW CYCLE. | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | 19 | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | 561-718-9724. | | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ | | RETIRED. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
|