Plan Review Details - Permit 21060222
Plan Review Stops For Permit 21060222
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By cthroop Date 2021-08-10 Time 08:15 Rev Time 0.00
Received By cthroop Date 2021-08-10 Time 07:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-14 Cont ID  
Sent By cthroop Date 2021-07-14 Time 08:09 Rev Time 0.00
Received By cthroop Date 2021-07-13 Time 05:39 Sent To  
Notes
2021-07-14 08:16:58PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DEMO PLAN SHOWS REMOVAL OF COLUMNS AT KITCHEN
 TERRACE. PROVIDE DETAIL OF NEW COLUMNS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. DEMO PLAN SHOWS REMOVAL OF EXISTING EXTERIOR WALL.
 PROVIDE IN-FILL DETAIL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE ROUGH OPENING AND DESIGN PRESSURE FOR NEW
 EXTERIOR DOORS.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2021-07-13 Cont ID  
Sent By cthroop Date 2021-07-13 Time 17:14 Rev Time 0.00
Received By cthroop Date 2021-07-13 Time 07:16 Sent To  
Notes
2021-07-13 17:14:42SEE STAND ALONE ELECTRICAL PERMIT 21070260. CT

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-08-10 Cont ID  
Sent By cthroop Date 2021-08-10 Time 08:17 Rev Time 0.00
Received By cthroop Date 2021-08-10 Time 08:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-07-14 Cont ID  
Sent By cthroop Date 2021-07-14 Time 06:41 Rev Time 0.00
Received By cthroop Date 2021-07-13 Time 07:50 Sent To  
Notes
2021-07-14 06:45:42PROVISO ON PLAN PAGE A-1: SEPERATE GAS PERMIT REQUIRED.
 CT
  
 SEPARATE GAS PERMIT
  
 PLAN REVIEW / FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 PROVIDE THE FOLLOWING INFORMATION:
  
  
 1.SUBMIT A GAS PLAN. SHOW THE LOCATION OF ALL PROPOSED
 GAS APPLIANCES. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
 SHOW THE DISTANCE FROM THE GAS METER TO THE MOST REMOTE
 REGULATOR ON THE SYSTEM.
 (LONGEST RUN)
  
 3. SUBMIT APPLICABLE GAS TABLES. G2413.3 (402.3)SIZING
 AND G2413.4 (402.4)SIZING TABLES AND EQUATIONS.
  
 4. SUBMIT MANUFACTURERS SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR
 2020 FBC FUEL GAS RES. SEC. G2408.1.
  
 5. SUBMIT LOW PRESSURE GAS REGULATOR SPECIFICATIONS.
 2020 FBC FUEL GAS SEC.305.1 OR 2020 FBC FUEL GAS RES.
 SEC. G2408.1.
  
 NOTICE: REGULATORS SHALL HAVE A UNION INSTALLED WITHIN
 1 FOOT OF EITHER SIDE OF THE REGULATOR FBC FG 410.2
  
 NOTICE: REGULATORS SHALL BE LOCATED PER 409.1.3.
  
 7. SUBMIT COMBUSTION AIR CALCULATIONS, IF REQUIRED, FOR
 THE PROPOSED GAS APPLIANCES. WHERE IS COMBUSTION AIR
 PROVIDED BY THE BUILDINGS MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR. 2017 FGC SEC.304.9.3 OR 2017 FBC R
 G2407.9.3. COMBINED COMBUSTION AIR AND VENTILATION AIR
 SYSTEM.
  
 8. SUBMIT A SITE PLAN IDENTIFYING THE LOCATION OF THE
 PROPOSED GAS METER OR UNDERGROUND TANK.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-10 Cont ID  
Sent By cthroop Date 2021-08-10 Time 08:22 Rev Time 0.00
Received By cthroop Date 2021-08-06 Time 07:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-14 Cont ID  
Sent By cthroop Date 2021-07-14 Time 08:17 Rev Time 0.00
Received By cthroop Date 2021-06-28 Time 14:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-08-10 Cont ID  
Sent By cthroop Date 2021-08-10 Time 08:21 Rev Time 0.00
Received By cthroop Date 2021-08-10 Time 08:21 Sent To  
Notes
2021-08-10 08:22:13SEE PLUMBING PERMIT 21051157.

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-14 Cont ID  
Sent By cthroop Date 2021-07-14 Time 08:02 Rev Time 0.00
Received By cthroop Date 2021-07-13 Time 07:16 Sent To  
Notes
2021-07-14 08:08:52PLAN REVIEW PLUMBING FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A PLUMBING PLAN. WATER HEATER REMOVED ON
 DEMO PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
 2. PROVIDE SOURCE OF HOT WATER.
 PLEASE PROVIDE THE SOURCE OF HOT WATER PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 P2804.1RELIEF VALVES REQUIRED. SECTION P2801.1 FBC RES.
 APPLIANCES AND EQUIPMENT USED FOR HEATING WATER OR
 STORING HOT WATER SHALL BE PROTECTED BY ONE OF THE
 FOLLOWING:
 1. 1.A SEPARATE PRESSURE-RELIEF VALVE AND A SEPARATE
 TEMPERATURE-RELIEF VALVE.
 2. 2.A COMBINATION PRESSURE-AND-TEMPERATURE RELIEF
 VALVE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-06 Cont ID  
Sent By ccole Date 2021-08-06 Time 10:12 Rev Time 0.00
Received By ccole Date 2021-08-06 Time 10:11 Sent To  
Notes
2021-08-06 10:12:49REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED
 AND PLANS ROUTED TO STORAGE/CLC

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-14 Cont ID  
Sent By cthroop Date 2021-07-14 Time 08:08 Rev Time 0.00
Received By cthroop Date 2021-07-13 Time 05:39 Sent To  
Notes
***NONE***