Plan Review Stops For Permit 21051507 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2021-12-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-12-07 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-12-07 |
Time |
09:15 |
Sent To |
|
|
Notes |
2021-12-07 09:16:54 | BUILDING PROVISO | | FBC-R311.3 REQUIRES A LANDING AT THE EXTERIOR OF THE | | ENTRY PORCH DOOR. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-08-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-08-20 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-08-20 |
Time |
15:23 |
Sent To |
|
|
Notes |
2021-08-20 14:17:15 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO, CFM | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING (PREVIOUS COMMENTS WERE NOT | | ADDRESSED.) | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | 1) THE HEIGHT ABOVE GRADE AT THE NEW STEPS IS NOT | | SPECIFIED ON THE PLANS. IF ANY PORTION OF THE STEPS ARE | | MORE THAN 30" ABOVE GRADE, GUARDS COMPLYING WITH | | FBC-R312 WILL BE REQUIRED. | | | | 2) SUBMIT ENERGY CODE COMPLIANCE DOCUMENTS FOR THE | | PROPOSED ADDITION. FBC ENERGY CONSERVATION CHAPTER 4 | | | | 3) SPECIFY THE UNDER FLOOR INSULATION. FBC ENERGY | | CONSERVATION CHAPTER 4 | | | | 4) SHOW HOW THE ADDITION WILL COMPLY WITH FBC-R 408.1 | | VENTILATION. THE UNDER-FLOOR SPACE BETWEEN THE BOTTOM | | OF THE FLOOR JOISTS AND THE EARTH UNDER ANY BUILDING | | (EXCEPT SPACE OCCUPIED BY A BASEMENT) SHALL HAVE | | VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR | | EXTERIOR WALLS. THE MINIMUM NET AREA OF VENTILATION | | OPENINGS SHALL BE NOT LESS THAN 1 SQUARE FOOT (0.0929 | | M2) FOR EACH 150 SQUARE FEET (14 M2) OF UNDER-FLOOR | | SPACE AREA, UNLESS THE GROUND SURFACE IS COVERED BY A | | CLASS 1 VAPOR RETARDER MATERIAL. WHERE A CLASS 1 VAPOR | | RETARDER MATERIAL IS USED, THE MINIMUM NET AREA OF | | VENTILATION OPENINGS SHALL BE NOT LESS THAN 1 SQUARE | | FOOT (0.0929 M2) FOR EACH 1,500 SQUARE FEET (140 M2) OF | | UNDER-FLOOR SPACE AREA. ONE SUCH VENTILATING OPENING | | SHALL BE WITHIN 3 FEET (914 MM) OF EACH CORNER OF THE | | BUILDING. | | | | 5) SHOW HOW THE ADDITION WILL COMPLY WITH R408.4 | | ACCESS. ACCESS SHALL BE PROVIDED TO ALL UNDER-FLOOR | | SPACES. ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A | | MINIMUM OF 18 INCHES BY 24 INCHES (457 MM BY 610 MM). | | OPENINGS THROUGH A PERIMETER WALL SHALL BE NOT LESS | | THAN 16 INCHES BY 24 INCHES (407 MM BY 610 MM). WHERE | | ANY PORTION OF THE THROUGH-WALL ACCESS IS BELOW GRADE, | | AN AREAWAY NOT LESS THAN 16 INCHES BY 24 INCHES (407 MM | | BY 610 MM) SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY | | SHALL BE BELOW THE THRESHOLD OF THE ACCESS OPENING. | | THROUGH WALL ACCESS OPENINGS SHALL NOT BE LOCATED UNDER | | A DOOR TO THE RESIDENCE. | | | | 6) SUBMIT COMPLETE PRODUCT APPROVALS FOR THE ROOFING | | MATERIALS AND THE JAMES HARDIE PANEL WALL SIDING THAT | | HAVE BEEN APPROVED IN WRITING BY THE DESIGNER OF | | RECORD. (THE DOCUMENT SUBMITTED FOR THE SIDING IS NOT A | | PRODUCT APPROVAL.) FBC AMEND. 107.3.4 - PROVIDE TWO | | SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE | | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE | | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN | | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE | | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING | | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES | | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WALL | | PANELS, WINDOW (GLASS TYPES), STRUCTURAL MULLIONS AND | | EXTERIOR DOOR TYPES. THESE ITEMS CAN BE DEFERRED IF | | REQUESTED, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND | | APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE | | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR | | ELECTRONICALLY SUBMITTED DOCUMENTS. | | | | 7) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-07-06 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-07-06 |
Time |
11:11 |
Sent To |
|
|
Notes |
2021-07-06 15:26:28 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO, CFM | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | 1) THE HEIGHT ABOVE GRADE AT THE NEW STEPS IS NOT | | SPECIFIED ON THE PLANS. IF ANY PORTION OF THE STEPS ARE | | MORE THAN 30" ABOVE GRADE, GUARDS COMPLYING WITH | | FBC-R312 WILL BE REQUIRED. | | | | 2) SUBMIT ENERGY CODE COMPLIANCE DOCUMENTS FOR THE | | PROPOSED ADDITION. FBC ENERGY CONSERVATION CHAPTER 4 | | | | 3) SPECIFY THE UNDER FLOOR INSULATION. FBC ENERGY | | CONSERVATION CHAPTER 4 | | | | 4) SHOW HOW THE ADDITION WILL COMPLY WITH FBC-R 408.1 | | VENTILATION. THE UNDER-FLOOR SPACE BETWEEN THE BOTTOM | | OF THE FLOOR JOISTS AND THE EARTH UNDER ANY BUILDING | | (EXCEPT SPACE OCCUPIED BY A BASEMENT) SHALL HAVE | | VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR | | EXTERIOR WALLS. THE MINIMUM NET AREA OF VENTILATION | | OPENINGS SHALL BE NOT LESS THAN 1 SQUARE FOOT (0.0929 | | M2) FOR EACH 150 SQUARE FEET (14 M2) OF UNDER-FLOOR | | SPACE AREA, UNLESS THE GROUND SURFACE IS COVERED BY A | | CLASS 1 VAPOR RETARDER MATERIAL. WHERE A CLASS 1 VAPOR | | RETARDER MATERIAL IS USED, THE MINIMUM NET AREA OF | | VENTILATION OPENINGS SHALL BE NOT LESS THAN 1 SQUARE | | FOOT (0.0929 M2) FOR EACH 1,500 SQUARE FEET (140 M2) OF | | UNDER-FLOOR SPACE AREA. ONE SUCH VENTILATING OPENING | | SHALL BE WITHIN 3 FEET (914 MM) OF EACH CORNER OF THE | | BUILDING. | | | | 5) SHOW HOW THE ADDITION WILL COMPLY WITH R408.4 | | ACCESS. ACCESS SHALL BE PROVIDED TO ALL UNDER-FLOOR | | SPACES. ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A | | MINIMUM OF 18 INCHES BY 24 INCHES (457 MM BY 610 MM). | | OPENINGS THROUGH A PERIMETER WALL SHALL BE NOT LESS | | THAN 16 INCHES BY 24 INCHES (407 MM BY 610 MM). WHERE | | ANY PORTION OF THE THROUGH-WALL ACCESS IS BELOW GRADE, | | AN AREAWAY NOT LESS THAN 16 INCHES BY 24 INCHES (407 MM | | BY 610 MM) SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY | | SHALL BE BELOW THE THRESHOLD OF THE ACCESS OPENING. | | THROUGH WALL ACCESS OPENINGS SHALL NOT BE LOCATED UNDER | | A DOOR TO THE RESIDENCE. | | | | 6) SUBMIT COMPLETE PRODUCT APPROVALS FOR THE ROOFING | | MATERIALS AND THE JAMES HARDIE PANEL WALL SIDING THAT | | HAVE BEEN APPROVED IN WRITING BY THE DESIGNER OF | | RECORD. (THE DOCUMENT SUBMITTED FOR THE SIDING IS NOT A | | PRODUCT APPROVAL.) FBC AMEND. 107.3.4 - PROVIDE TWO | | SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE | | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE | | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN | | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE | | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING | | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES | | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WALL | | PANELS, WINDOW (GLASS TYPES), STRUCTURAL MULLIONS AND | | EXTERIOR DOOR TYPES. THESE ITEMS CAN BE DEFERRED IF | | REQUESTED, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND | | APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE | | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR | | ELECTRONICALLY SUBMITTED DOCUMENTS. | | | | 7) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-12-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-12-07 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-12-07 |
Time |
09:54 |
Sent To |
|
|
Notes |
2021-12-07 09:54:04 | VOICE DATA AND TV JLEAHY |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-06-15 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-06-15 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-06-14 |
Time |
17:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
Rev No |
1 |
Status |
P |
Date |
2021-06-15 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-06-15 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-06-15 |
Time |
09:56 |
Sent To |
|
|
Notes |
2021-06-15 09:57:04 | VOICE DATA AND TV JLEAHY |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2021-06-15 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-06-15 |
Time |
12:55 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-06-15 |
Time |
12:55 |
Sent To |
|
|
Notes |
2021-06-15 12:56:03 | GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN | | THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN | | PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS | | WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE | | RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT | | REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | | A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR | | FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC | | SEC. 105.1. | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2021-11-09 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2021-11-09 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2021-11-09 |
Time |
15:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2021-07-14 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2021-07-14 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2021-07-14 |
Time |
08:22 |
Sent To |
|
|
Notes |
2021-07-14 08:22:37 | APPROVED WITH CONDITION THAT FRONT WINDOWS ARE REVISED | | PER BOARD APPROVAL, |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2022-02-04 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2022-02-04 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-12-15 |
Time |
10:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-12-07 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-12-07 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-11-02 |
Time |
13:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-08-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-08-20 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-07-29 |
Time |
15:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-07-14 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-07-14 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-06-04 |
Time |
10:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2022-02-16 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2022-02-16 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-11-06 |
Time |
16:54 |
Sent To |
|
|
Notes |
2022-02-15 14:32:21 | RECEIPT MU-2021-053552 - $1945.04 PAID | | | 2021-11-06 16:55:02 | 11/6/21 EMAILED IMPACT FEES FOR REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-07-06 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-07-06 |
Time |
11:12 |
Sent To |
|
|
Notes |
2021-07-06 11:14:46 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2021-12-08 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-12-08 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-12-08 |
Time |
12:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2021-11-05 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-11-03 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-11-03 |
Time |
16:25 |
Sent To |
|
|
Notes |
2021-11-03 16:28:19 | PLEASE RESPOMD TO THE PREVIOUS REVIEW COMMENTS BELOW; | | | | PLEASE ALSO PROVIDE THE ENERGY CALCULATIONS AND THE | | MECHANICAL EQUIPMENT SIZING CALCULATIONS BECAUSE THIS | | IS A REMODEL AND ADDITION. FBC EC R403.7 | | | | 2ND REVIEW FBC-2020 MECHANICAL | | PERMIT-21051507 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 2) PLEASE SHOW THE RETURN AIR PATH FROM BEDROOMS 1 AND | | 2 TO THE AHU. FBC RES M1602.3 | | | | 3) PLEASE SHOW THE CONDENSING UNIT TIE DOWN. FBC RES | | M1307.2 | | | | 4) IS THE HOOD VENTED TO THE EXTERIOR? FBC RES M1503 | | | | 5) PLEASE SHOW THE DRYER DUCT AND TERMINATION LOCATION. | | FBC RES M1502.3 | | | | 6) PLEASE SHOW THE CONDENSATION PIPING AND TERMINATION | | LOCATION. FBC RES M1411.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2021-08-04 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-08-04 |
Time |
08:05 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-08-04 |
Time |
08:05 |
Sent To |
|
|
Notes |
2021-08-04 08:05:44 | 2ND REVIEW FBC-2020 MECHANICAL | | PERMIT-21051507 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) IS THIS A LIKE FOR LIKE CHANGE OUT? IF SO PLEASE | | PROVIDE THE LIKE FOR LIKE CHANGE OUT FORM SHOWING THE | | OUT UNIT INFORMATION. IF NOT PLEASE PROVIDE THE | | MECHANICAL EQUIPMENT SIZING CALCULATIONS SIGNED BY THE | | MECHANICAL CONTRACTOR OR A LICENSED ENGINEER CAN | | DIGITALLY SIGN THE DOCUMENTS. FBC 107.2.1 | | | | 2) PLEASE SHOW THE RETURN AIR PATH FROM BEDROOMS 1 AND | | 2 TO THE AHU. FBC RES M1602.3 | | | | 3) PLEASE SHOW THE CONDENSING UNIT TIE DOWN. FBC RES | | M1307.2 | | | | 4) IS THE HOOD VENTED TO THE EXTERIOR? FBC RES M1503 | | | | 5) PLEASE SHOW THE DRYER DUCT AND TERMINATION LOCATION. | | FBC RES M1502.3 | | | | 6) PLEASE SHOW THE CONDENSATION PIPING AND TERMINATION | | LOCATION. FBC RES M1411.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2021-06-14 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-06-14 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-06-14 |
Time |
10:54 |
Sent To |
|
|
Notes |
2021-06-14 11:11:58 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21051507 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE A DETAILED SCOPE OF WORK FOR THE | | MECHANICAL SYSTEM. FBC 107.2.1 | | | | 2) THERE ARE NO MECHANICAL PLANS FOR THIS PROJECT. | | PLEASE PROVIDE A DETAILED MECHANICAL DRAWING SHOWING | | THE SCOPE OF WORK. FBC 107.2.1 | | | | 3) IF THEE IS GOING TO BE A NEW MECHANICAL SYSTEM | | INSTALLED PLEASE PRESENT THE ENERGY CALCULATIONS. FBC | | EC R402.1 | | | | 4) IF THERE IS GOING TO BE A NEW MECHANICAL SYSTEM | | INSTALLED PLEASE PRESENT THE MECHANICAL EQUIPMENT | | SIZING CALCULATIONS. FBC EC R403.7 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-11-03 |
|
|
Cont ID |
|
Sent By |
abelisle |
Date |
2021-11-03 |
Time |
19:53 |
Rev Time |
0.00 |
Received By |
abelisle |
Date |
2021-11-03 |
Time |
19:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2021-06-15 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-06-15 |
Time |
12:54 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-06-15 |
Time |
12:08 |
Sent To |
|
|
Notes |
2021-06-15 12:55:10 | 06/15/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
P |
Date |
2021-12-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-12-07 |
Time |
08:13 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-12-07 |
Time |
08:13 |
Sent To |
|
|
Notes |
2021-12-07 08:18:27 | UNDERLAYMENT- OWENS CORNING, FL11602 - R13 | | ASPHALT SHINGLES- OWENS CORNING, FL10674 - R16 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2021-08-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-08-20 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-08-20 |
Time |
13:33 |
Sent To |
|
|
Notes |
2021-08-20 13:34:00 | NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ROOFING | | MATERIALS AT THE NEW ADDITION. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-07-06 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-07-06 |
Time |
11:12 |
Sent To |
|
|
Notes |
2021-07-06 14:27:59 | NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ROOFING | | MATERIALS AT THE NEW ADDITION. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2021-11-10 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2021-11-10 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2021-11-10 |
Time |
10:36 |
Sent To |
|
|
Notes |
2021-11-10 10:37:08 | MIISING SHEETS WERE APPROVED WITH ORIGINAL PAPER | | SUBMITTAL. | | ANY ADDITIONAL SHEETS WILL NEED TO BE REVIEWED FORM | | THIRD REVIEW COMMENTS. | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2021-11-02 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2021-11-02 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2021-11-02 |
Time |
14:48 |
Sent To |
|
|
Notes |
2021-11-02 15:08:48 | SIGNATURE REVIEW FBC- 2020 | | PERMIT- 21051507 | | 11/2/2021 | | | | CODES IN EFFECT: | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE PAPER SET OF PLANS SUBMITTED TO VERIFY | | SIGNATURES AND SEALS ARE MISSING PLAN SHEETS D1, D2, | | A-3, & S4.- FL STATUTE 481.221 AND SECTION 61G1-16.002 | | FLORIDA ADMINISTRATIVE CODE. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
N |
Date |
2021-07-30 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-07-30 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-07-30 |
Time |
15:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2021-06-17 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-06-17 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-06-17 |
Time |
10:12 |
Sent To |
|
|
Notes |
2021-06-17 10:13:38 | ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO | | STORAGE.ME |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2022-02-03 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2022-02-03 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2022-02-03 |
Time |
10:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2021-12-06 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2021-12-06 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2021-12-06 |
Time |
16:32 |
Sent To |
|
|
Notes |
2021-12-06 16:32:20 | PROPRERTY NEEDS A LANDSCAPE PERMIT BEFORE ZONING CAN BE | | PASSED OR A CONDITIONAL LANDSCAPE APPROVAL FORM. | | | | PLEASE REACH OUT FOR MORE INFORMATION. | | | | ANNE HAMILTON | | HISTORIC PRESERVATION PLANNER | | 561.822.1428 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-11-10 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2021-11-10 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2021-11-10 |
Time |
14:04 |
Sent To |
|
|
Notes |
2021-11-10 14:05:56 | PROPRERTY NEEDS A LANDSCAPE PERMIT BEFORE ZONING CAN BE | | PASSED. | | | | PLEASE REACH OUT FOR CLARIFICATION: | | | | ANNE HAMILTON | | HISTORIC PRESERVATION PLANNER | | 561.822.1428 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2021-07-14 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2021-07-14 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2021-07-14 |
Time |
08:22 |
Sent To |
|
|
Notes |
|
|