Plan Review Details - Permit 21051366
Plan Review Stops For Permit 21051366
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2021-08-31 Cont ID  
Sent By jwitmer Date 2021-08-31 Time 07:59 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-08-23 Cont ID  
Sent By jwitmer Date 2021-08-23 Time 16:59 Rev Time 0.00
Received By jwitmer Date 2021-08-23 Time 16:31 Sent To  
Notes
2021-08-23 16:59:03TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-08-11 Cont ID  
Sent By pvalenti Date 2021-08-11 Time 08:25 Rev Time 0.00
Received By pvalenti Date 2021-08-11 Time 07:35 Sent To  
Notes
2021-08-11 08:28:04****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By jwitmer Date 2021-06-29 Time 09:49 Rev Time 0.00
Received By jwitmer Date 2021-06-29 Time 09:42 Sent To  
Notes
2021-06-29 09:48:32TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-09-15 Cont ID  
Sent By jwitmer Date 2021-09-15 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2021-09-15 Time 07:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-09-14 Cont ID  
Sent By jwitmer Date 2021-09-14 Time 16:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-14 18:50:49PER APPLICANT, APPLICATION WAS SUBMITTED UNDER
 INCORRECT ADDRESS. THE PLANS MATCH THE ADDRESS IN OUR
 SYSTEM. TO RESOLVE, IN ADDITION TO THE NEW PERMIT
 APPLICATION, REVISE DRAWINGS AND RESUBMIT TO SUPERSEDE
 THE PREVIOUSLY REVIEWED PLANS.
  
 [email protected]
 561-805-6724

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-08-23 Cont ID  
Sent By jwitmer Date 2021-08-23 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2021-08-23 Time 16:31 Sent To  
Notes
2021-08-23 16:57:57WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21051366
 ADD: 720 S. SAPODILLA AVE. # 302
 CONT: PALM BEACH CONSTRUCTION & ASSOCAIATES
 TEL: 561-441-7493
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. AUGUST 23, 2021
 ACTION: DENIED
  
 1) 3RD ROUND OF COMMENTS. SHEET A100 BY ARCHITECT
 WILSON ORLANDO HERRERA. DRAWING # 1 FLOOR PLAN BY THE
 COURTYARDS IN CITY PLACE, WITH 2 AREAS CIRCLED AREAS OF
 WORK, NO AUTHORSHIP OF PLAN. WITH THERE BEING A
 DESIGNER OF RECORD AND SCOPE ON HIS PLAN, THE
 CONTRACTOR AND ARCHITECT NEED TO GET TOGETHER ON WHAT
 WORK IS TO BE COMPLETED UNDER THIS PERMIT. ARCHITECT
 DOES NOT INCLUDE ANY WORK IN THE KITCHEN UNDER HIS
 SCOPE OF WORK. DISCREPANCY IN AREAS O WORK, DESIGNER OF
 RECORD MAY NEED TO MODIFY THE PLAN IF THE KITCHEN FLOOR
 REPLACEMENT IS TO BE A PART OF THIS PROJECT. 107.2.1.2
 DISCREPANCY IN PLANS 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 1ST ROUND COMMENTS. THE SUBMITTED PLANS DO NOT INDICATE
 WHO THE AUTHOR IS. CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) COMPLIED.
  
 3) NO ACTION NEEDED. SHEET A-100 PROFLEX SUPER SIM 90.
 W. P. B. BUILDING DEPARTMENT HAS
 ALL (3) REQUIRED TEST ON FILE AT CITY HALL
 ON (F) DRIVE FLOOR UNDERLAYMENTS FOR:
  
 PROFLEX SUPER SIM 90 /TILE OR MARBLE
 IIC = 50 DB / 6 INCH SLAB P. T. / NO DROPPED CEILING /
 ASTM E-492
 STC = 52 DB / 6 INCH SLAB P. T./ NO DROPPED / CEILING
 ASTM E-90
 FLAME= 0 ASTM-E84
 SMOKE= 0 ASTM E-84
 J. WITMER BUILD PLAN REVIEW 8/23/2021
  
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-11 Cont ID  
Sent By pvalenti Date 2021-08-11 Time 09:12 Rev Time 0.00
Received By pvalenti Date 2021-08-11 Time 07:35 Sent To  
Notes
2021-08-11 09:13:38****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 1) PLEASE CLARIFY WHO THE AUTHOR OF THE SUBMITTED PLANS
 IS.
  
 IF THE SUBMITTED PLANS WERE MEANT TO BE DESIGNED BY A
 CONTRACTOR THEN THE IMAGES OF A DESIGN PROFESSIONAL?S
 SIGNATURE/SEAL & TITLE BLOCK CAN NOT APPEAR ON
 SUBMITTALS AND CONTRACTOR?S SIGNATURE MUST BE ON
 SUBMITTALS AS PER FBC B 107.3.4.3 & WPB AMENDMENTS
 107.2.1.
  
 IF THE SUBMITTED PLANS ARE DESIGNED BY A DESIGN
 PROFESSIONAL (ENGINEER OR ARCHITECT)
 ORIGINAL/VERIFIABLE SIGNATURES/SEALS ARE REQUIRED AS
 PER NOTE BELOW.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD/EMAIL A DIGITALLY SIGNED (THIRD PARTY VERIFIED)
 PLAN OR YOU CAN MAIL/HAND DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 401 CLEMATIS STREET
 P.O. BOX 3147
 WEST PALM BEACH, FL 33402
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES/BUILDING DEPT.
 561 805 6673
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By jwitmer Date 2021-06-29 Time 10:13 Rev Time 0.00
Received By jwitmer Date 2021-06-29 Time 09:42 Sent To  
Notes
2021-06-29 10:07:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21051366
 ADD: 720 S. SAPODILLA AVE. # 302
 CONT: PALM BEACH CONSTRUCTION & ASSOCAIATES
 TEL: 561-441-7493
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 29TH / 2021
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS DO NOT INDICATE WHO THE AUTHOR
 IS. CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) DRAWING # 1 INDICATES THE REMODELING OF THE
 BATHROOM, PLEASE INDICATE THE FAIR HOUSING GUIDELINE
 TYPE A OR B ON THE PLAN. FAIR HOUSING GUIDELINES. FAIR
 HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS. FOR
 PURPOSES OF THIS SECTION, A COVERED MULTIFAMILY
 DWELLING SHALL BE DEEMED TO BE DESIGNED AND CONSTRUCTED
 FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13, 1991, IF
 THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST BUILDING
 PERMIT OR RENEWAL THEREOF FOR THE COVERED MULTIFAMILY
 DWELLINGS IS ISSUED BY A STATE, COUNTY OR LOCAL
 GOVERNMENT ON OR BEFORE JANUARY 13, 1990.
 FAIR HOUSING LETTER AS AN ALTERNATE METHOD. SEE
 PROPOSED LETTER LAYOUT BELOW:
 PROJECT ADDRESS: ______________________________________
 _____________________
 PERMIT NUMBER: ________________________
 THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE
 PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS
 OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER
 AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF
 SALE IF SO REQUESTED BY THE BUYER.
  
 SIGNATURE OF DESIGNER: ______________________________
 PRINTED NAME OF DESIGNER: ___________________________
  
 SIGNATURE OF OWNER: ________________________________
 PRINTED NAME OF OWNER: _____________________________
 NOTARY FOR OWNER?S SIGNATURE:
 STATE OF FLORIDA, COUNTY OF PALM BEACH
 THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME
 THIS _____ DAY OF ________, 20__ BY
 ___________________________ WHO IS PERSONALLY KNOWN TO
 ME OR WHO HAS PRODUCED: ___________________________ AS
 IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH.
 NOTARY SIGNATURE ___________________________________
 NOTARY PRINTED NAME ________________________________
  
 3) THE FLOOR PLAN LABELED DRAWING # 02 INDICATES THE
 INSTALLATION OF PROFLEX 90. PLEASE BE SPECIFIC AS TO
 WHICH TYPE OF PROFLEX 90 IS TO BE INSTALLED. PROVIDE
 FLOOR FINISH MATERIAL, TILE, MARBLE, WOOD VENEERS OR
 VINYL FLOORING. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
 PROFLEX 90 MSC MEGA SOUND CONTROL WE HAVE NO TESTING
 REPORTS ON THIS PRODUCT.
 PROFLEX SUPER SIM 90 WE HAVE ALL THE TEST REPORTS
 REQUIRED FOR THIS PRODUCT IF TILE OF MARBLE IS BEING
 INSTALLED.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2021-06-14 Cont ID  
Sent By jleahy Date 2021-06-14 Time 16:48 Rev Time 0.00
Received By jleahy Date 2021-06-14 Time 16:46 Sent To  
Notes
2021-06-14 16:48:53NO ELECTRIC SHOWN ON PLANS JLEAHY
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-03 Cont ID  
Sent By pleduc Date 2021-06-03 Time   Rev Time 0.00
Received By pleduc Date 2021-06-03 Time 13:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-09-14 Cont ID  
Sent By jwitmer Date 2021-09-14 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2021-09-13 Time 07:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-25 Cont ID  
Sent By lcrespo Date 2021-08-25 Time 13:33 Rev Time 0.00
Received By lcrespo Date 2021-08-17 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-11 Cont ID  
Sent By pvalenti Date 2021-08-11 Time 09:20 Rev Time 0.00
Received By pvalenti Date 2021-07-30 Time 09:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-06-29 Time 10:13 Rev Time 0.00
Received By cdecoeur Date 2021-05-28 Time 10:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-08-25 Cont ID  
Sent By lcrespo Date 2021-08-25 Time 13:33 Rev Time 0.00
Received By lcrespo Date 2021-08-25 Time 13:29 Sent To  
Notes
2021-08-25 13:33:5008/25/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 10:44 Rev Time 0.00
Received By lcrespo Date 2021-08-10 Time 10:44 Sent To  
Notes
2021-08-10 10:45:0208/10/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-14 Cont ID  
Sent By lcrespo Date 2021-06-14 Time 09:22 Rev Time 0.00
Received By lcrespo Date 2021-06-11 Time 16:50 Sent To  
Notes
2021-06-14 09:23:2206/14/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS BUILDING WAS ORIGINALLY BUILT AND DESIGNED
 UNDER THE FAIR HOUSING ACT GUIDELINES AND THE LEVEL OF
 ACCESSIBILITY CANNOT BE DECREASED. THE PLANNED
 ALTERATIONS TO THE MASTER BATH ARE BEING ALTERED AND
 MAY NOT COMPLY WITH THE REQUIREMENTS OF THE FAIR
 HOUSING ACT GUIDELINES. PLEASE INDICATE ON PLANS WHICH
 DESIGN SPECIFICATION ( ?A? OR ?B? OF THE ACT) WAS USED
 IN THE ORIGINAL DESIGN OF THESE UNITS. TELL US WHICH
 USABLE BATHROOM IN THE DWELLING UNITS, THE ALTERATION
 THAT IS PROPOSED IN THE BATHROOM SHALL ALSO BE IN
 COMPLIANCE WITH THE FAIR HOUSING ACT.
  
 2. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 PROVIDES AN OPTION FOR THE CHANGING OF AN FHA
 COMPLIANCE STRUCTURE. THE OWNER AND DESIGNER OF RECORD
 ACKNOWLEDGE THAT THE PROPOSED BATHROOM DESIGN DOES NOT
 MEET THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES. THE OWNER AGREES TO REVERT THE UNIT BACK TO
 COMPLIANCE AT THE TIME OF SALE IF SO, REQUESTED BY THE
 BUYER. THIS WILL BE IN A LETTER TYPE FORMAT SIGNED AND
 NOTARIZED BY THE OWNER. WE PROVIDE A SAMPLE LETTER AND
 IT MUST BE SUBMITTED TO THE BUILDING DEPARTMENT OF THE
 CITY OF WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN
 EMAIL TO [email protected] AND I WILL SEND A COPY OF THE
 FAIR HOUSING AFFIDAVIT.
  
 3. IF SPECIFICATION A BATHROOMS IS CALLED OUT THE TOP
 FIXTURE RIM IS A MAXIMUM OF 34 INCHES AFF, WITH THE
 APRON AT LEAST 27 INCHES AFF.
  
 4. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-09-14 Cont ID  
Sent By jwitmer Date 2021-09-14 Time 16:11 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-08-23 Cont ID  
Sent By jwitmer Date 2021-08-23 Time 17:00 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-08-23 16:59:543RD ROUND OF COMMENTS. SHEET A100 BY ARCHITECT WILSON
 ORLANDO HERRERA. DRAWING # 1 FLOOR PLAN BY THE
 COURTYARDS IN CITY PLACE, WITH 2 AREAS CIRCLED AREAS OF
 WORK, NO AUTHORSHIP OF PLAN. WITH THERE BEING A
 DESIGNER OF RECORD AND SCOPE ON HIS PLAN, THE
 CONTRACTOR AND ARCHITECT NEED TO GET TOGETHER ON WHAT
 WORK IS TO BE COMPLETED UNDER THIS PERMIT. ARCHITECT
 DOES NOT INCLUDE ANY WORK IN THE KITCHEN UNDER HIS
 SCOPE OF WORK. DISCREPANCY IN AREAS O WORK, DESIGNER OF
 RECORD MAY NEED TO MODIFY THE PLAN IF THE KITCHEN FLOOR
 REPLACEMENT IS TO BE A PART OF THIS PROJECT. 107.2.1.2
 DISCREPANCY IN PLANS 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-11 Cont ID  
Sent By pvalenti Date 2021-08-11 Time 08:29 Rev Time 0.00
Received By pvalenti Date 2021-08-11 Time 07:35 Sent To  
Notes
2021-08-11 08:58:02SIGNATURE REVIEW DENIED:
  
 IF THE SUBMITTED PLANS WERE MEANT TO BE DESIGNED BY A
 CONTRACTOR THEN THE IMAGES OF A DESIGN PROFESSIONAL'S
 SIGNATURE/SEAL & TITLE BLOCK CAN NOT APPEAR ON
 SUBMITTAL AND CONTRACTOR'S SIGNATURE MUST BE ON
 SUBMITTALS AS PER FBC B 107.3.4.3 & WPB AMENDMENTS
 107.2.1.
  
 IF THE SUBMITTED PLANS ARE DESIGNED BY A DESIGN
 PROFESSIONAL (ENGINEER OR ARCHITECT)
 ORIGINAL/VERIFIABLE SIGNATURES/SEALS ARE REQUIRED AS
 PER NOTE BELOW.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD/EMAIL A DIGITALLY SIGNED (THIRD PARTY VERIFIED)
 PLAN OR YOU CAN MAIL/HAND DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 401 CLEMATIS STREET
 P.O. BOX 3147
 WEST PALM BEACH, FL 33402
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES/BUILDING DEPT.
 561 805 6673
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-06-29 Cont ID  
Sent By jwitmer Date 2021-06-29 Time 09:48 Rev Time 0.00
Received By jwitmer Date 2021-06-29 Time 09:42 Sent To  
Notes
***NONE***