2021-05-25 11:02:28 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R8 HAS NOT BEEN APPROVED YET. PLEASE |
| PROVIDE A COMPLETE SET OF APPROVED 2020 CODE VERSION |
| PRODUCT APPROVALS/NOA?S FOR THE PROPOSED FLAT/LOW ROOF |
| SYSTEM USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. (FL16709-R7) |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R8 SELECTED OPTION FOR SYSTEM NO W-1; |
| EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); |
| ULTIMATE WIND SPEED (180). ZONE 3 IS MARKED ?N/A? WHICH |
| INDICATES SYSTEM CANNOT BE USED WITHIN THE PRESSURE |
| ZONE. THE CORRECT SYSTEM FOR THE LISTED ADDRESS IS NO |
| W-3. PLEASE SELECT THE CORRECT OPTIONS FOR FL16709-R7. |
| 3. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL11288-R19 HAS NOT BEEN APPROVED YET. PLEASE |
| PROVIDE A COMPLETE SET OF APPROVED 2020 CODE VERSION |
| PRODUCT APPROVALS/NOA?S FOR THE PROPOSED ROOF |
| UNDERLAYMENT SYSTEM USED. INCLUDE COVER PAGE, |
| EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR |
| SYSTEM USED. (FL11288-R18) |
| 4. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE METAL TO BE USED. |
| |