Plan Review Stops For Permit 21050894 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2021-05-19 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-05-19 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-05-19 |
Time |
11:09 |
Sent To |
|
|
Notes |
2021-05-19 11:10:23 | LOT 74434403180000201 SPLIT FROM 74434403170000300 | | UPDATED PARCEL. ADDRESS OK FOR NEW SINGLE FAMILY HOME |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2021-10-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-10-23 |
Time |
06:25 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-10-22 |
Time |
15:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2021-08-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-08-18 |
Time |
09:52 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-08-18 |
Time |
06:44 |
Sent To |
|
|
Notes |
2021-08-18 09:57:26 | PLAN REVIEW BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 3RD REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | NOTIVE: PROVISO ON PLAN PAG. SP-001: GENERATOR SHALL BE | | BY SEPERATE PERMIT. | | | | 1. PROVIDE THE ICC-ES REPORT FOR THE PROPOSED SPRAY | | FOAM INSULATION. PROVIDE THE CITY INSPECTOR A COPY AT | | TIME OF INSPECTION. | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 2. PROVIDE SITE DRAINAGE PLAN. | | FBC R401.3 SITE DRAINAGE | | PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH | | FBC R401.3 DRAINAGE. | | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | DOES NOT CREATE A HAZARD. | | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM | | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 | | INCHES WITHIN THE FIRST 10 FEET. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-07-12 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-07-12 |
Time |
17:15 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-07-12 |
Time |
16:45 |
Sent To |
|
|
Notes |
2021-07-12 17:17:00 | PLAN REVIEW BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 2ND REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | NOTICE: COMMNENTS FROM 1ST REVIEW HAVE NOT BEEN | | ADDRESSED. SEE BELOW. | | | | 1. REF. PAGE S0.3. , COMPONENTS AND CLADDING - DESIGN | | IS BASED ON ASCE 7-10. THIS DOCUMENT HAS EXPIRED. | | PLEASE USE THE 2020 FBC RES AND ASCE 7-16 FOR YOUR | | DESIGN. | | REF: PAGE A-001. GENERAL NOTES: OCCUPANCY GROUP STAES | | THIS IS AN ALTERATION LEVEL 3. THIS IS A NEW SFR. | | PLEASE CORRECT. | | | | PROVIDE PROJECT DESIGN PARAMETERS: | | | | 2020 FBC RESIDENTIAL; ASCE 7-16; 2017 NEC | | CLASSIFICATION OF WORK: NEW SFR | | CONSTRUCTION TYPE: VB | | OCCUPANCY: R3 | | EXPOSURE CLASSIFICATION: (C OR D) | | RISK CATEGORY: II | | MEAN ROOF HEIGHT: ( ) 2 STORY | | | | 2. PROVIDE ROOF SHEATHING FASTENER SCHEDULE BASED ON | | DESIGN WIND LOADS FOR ZONES 1, 2 AND 3. | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | 3. PROVIDE A SITE DRAINAGE PLAN. | | SITE PLAN/DRAINAGE PLAN/SURVEY | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED BOUNDARY LINE SURVEY. | | | | 4.REF: SOILS REPORT: THE SOILS REPORT SUBMITTED FOR | | REVIEW IS FOR A ONE STORY STRUCTURE. THIS PROJECT IS A | | 2 STORY STRUCTURE. THE SOILS REPORT ALSO STATES THAT | | ADDITIONAL BORINGS ARE REQUIRED FOR THE REAR OF THE | | PROPERTY DUE TO LACK OF ACCESS. SUBMIT A CORRECTED | | SOILS REPORT. | | 1803.2 INVESTIGATIONS REQUIRED. | | GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN | | ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5. | | | | 5. PROVIDE AN ENERGY SUBMITTAL. | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | 6. PRODUCT APPROVALS SUBMITTED FOR REVIEW FOR THE | | WINDOWS AND DOORS INCLUDE PAGE 1 ONLY. SUBMIT A | | COMPLETE SET OF PRODUCT APPROVALS INCLUDING THE | | INSTALLATION INSTRUCTIONS. | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | 7. PROVIDE A WINDOW AND DOOR SCHEDULE. PROVIDE THE | | DESIGN PRESSURES AND ROUGH OPENINGS OF EACH WINDOW AND | | DOOR. IDENTIFY THE OPENINGS ON THE PLANS. | | | | 1. LOCATION REFERENCE TO OPENING NUMBER ON PLAN. | | 2. WINDOW/DOOR TYPE | | 3. ROUGH OPENING WXH (AREA SF) | | 4. DESIGN PRESSURE OF OPENING (TABLE R301.1.(2) OR ASCE | | 7-16 | | 5. NOA OR FL NUMBER | | 6. MAX DESIGN PRESSURE FROM NOA OR FL | | 7. IDENTIFY EGRESS OPENINGS | | | | 7. PROVIDE SECTIONAL VIEW OF EXTERIOR WALL/FOUNDATION | | AND ROOF. INCLUDE PROPOSED CONNECTORS AND CEILING AND | | WALL INSULATION R-VALUE | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-06-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-06-19 |
Time |
08:16 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-06-19 |
Time |
06:07 |
Sent To |
|
|
Notes |
2021-06-19 09:11:38 | PLAN REVIEW BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. REF. PAGE S0.3. , COMPONENTS AND CLADDING - DESIGN | | IS BASED ON ASCE 7-10. THIS DOCUMENT HAS EXPIRED. | | PLEASE USE THE 2020 FBC RES AND ASCE 7-16 FOR YOUR | | DESIGN. | | REF: PAGE A-001. GENERAL NOTES: OCCUPANCY GROUP STAES | | THIS IS AN ALTERATION LEVEL 3. THIS IS A NEW SFR. | | PLEASE CORRECT. | | | | PROVIDE PROJECT DESIGN PARAMETERS: | | | | 2020 FBC RESIDENTIAL; ASCE 7-16; 2017 NEC | | CLASSIFICATION OF WORK: NEW SFR | | CONSTRUCTION TYPE: VB | | OCCUPANCY: R3 | | EXPOSURE CLASSIFICATION: (C OR D) | | RISK CATEGORY: II | | MEAN ROOF HEIGHT: ( ) 2 STORY | | | | 2. PROVIDE ROOF SHEATHING FASTENER SCHEDULE BASED ON | | DESIGN WIND LOADS FOR ZONES 1, 2 AND 3. | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | 3. PROVIDE A SITE DRAINAGE PLAN. | | SITE PLAN/DRAINAGE PLAN/SURVEY | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED BOUNDARY LINE SURVEY. | | | | 4.REF: SOILS REPORT: THE SOILS REPORT SUBMITTED FOR | | REVIEW IS FOR A ONE STORY STRUCTURE. THIS PROJECT IS A | | 2 STORY STRUCTURE. THE SOILS REPORT ALSO STATES THAT | | ADDITIONAL BORINGS ARE REQUIRED FOR THE REAR OF THE | | PROPERTY DUE TO LACK OF ACCESS. SUBMIT A CORRECTED | | SOILS REPORT. | | 1803.2 INVESTIGATIONS REQUIRED. | | GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN | | ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5. | | | | 5. PROVIDE AN ENERGY SUBMITTAL. | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | 6. PRODUCT APPROVALS SUBMITTED FOR REVIEW FOR THE | | WINDOWS AND DOORS INCLUDE PAGE 1 ONLY. SUBMIT A | | COMPLETE SET OF PRODUCT APPROVALS INCLUDING THE | | INSTALLATION INSTRUCTIONS. | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | 7. PROVIDE A WINDOW AND DOOR SCHEDULE. PROVIDE THE | | DESIGN PRESSURES AND ROUGH OPENINGS OF EACH WINDOW AND | | DOOR. IDENTIFY THE OPENINGS ON THE PLANS. | | | | 1. LOCATION REFERENCE TO OPENING NUMBER ON PLAN. | | 2. WINDOW/DOOR TYPE | | 3. ROUGH OPENING WXH (AREA SF) | | 4. DESIGN PRESSURE OF OPENING (TABLE R301.1.(2) OR ASCE | | 7-16 | | 5. NOA OR FL NUMBER | | 6. MAX DESIGN PRESSURE FROM NOA OR FL | | 7. IDENTIFY EGRESS OPENINGS | | | | 7. PROVIDE SECTIONAL VIEW OF EXTERIOR WALL/FOUNDATION | | AND ROOF. INCLUDE PROPOSED CONNECTORS AND CEILING AND | | WALL INSULATION R-VALUE | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-05-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-05-21 |
Time |
08:08 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-05-21 |
Time |
06:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2021-08-25 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-08-25 |
Time |
09:44 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-08-25 |
Time |
09:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2021-07-01 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-07-01 |
Time |
17:05 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-07-01 |
Time |
17:05 |
Sent To |
|
|
Notes |
2021-07-01 17:06:50 | 05/26/21 2ND GAS REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. ON SHEET P0.1, UNDER PLUMBING SHEET INDEX, IT HAS A | | P2.2 SECOND FLOOR PLUMBING PLAN - DOMESTIC WATER & | | NATURAL GAS. NO SUCH PAGE WAS FOUND. PLEASE PROVIDE OR | | REMOVE FROM INDEX PER THE WPB AMENDMENTS TO THE FBC | | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2. ON SHEET P3.1; | | A. PLEASE SHOW THE LOCATION OF THE TANK-LESS WATER | | HEATER AND THE LOCATION AND DISTANCE OF ANY OPERABLE | | DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE | | LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE | | MANUFACTURER'S INSTALLATION INSTRUCTIONS PER THE WPB | | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | | | B. PLEASE PROVIDE MANUFACTURER'S SPECIFICATION | | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO | | VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. | | | | C. PLEASE LIST THE BTU LOAD OF EACH APPLIANCE IN LEGEND | | TYPE AND THE TOTAL BTU LOAD ON THE SYSTEM PER THE WPB | | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | | | D. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, GAS | | METER TO THE MOST REMOTE OUTLET IN THE BUILDING AND | | SYSTEM PER THE 2020 FBC RES. SEC. G2413.4.1. | | | | E. PLEASE SUBMIT CALCULATIONS FOR COMBUSTION AIR PER | | THE 2020 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES | | DRYERS AND RANGE). IF PROVIDED BY SUPPLIED BY A LOUVER, | | PLEASE SHOW LOCATION. | | | | F. PLEASE PROVIDE THE SIZING TABLE USED IN THE DESIGN | | FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF | | PLANS LISTING THE SIZING TABLES FROM GAS CODES OR | | ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM PER | | THE 2020 FBC RES. SEC. G2413.3. | | | | G. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR | | THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. | | | | H. GAS P. E. SHOWN UNDER-SLAB IN A SLEEVE AND PIPING | | INSTALLED UNDERGROUND BENEATH BUILDINGS IS PROHIBITED | | PER THE 2020 FBC SEC. G2415.14 PIPING UNDERGROUND | | BENEATH BUILDINGS. THE AJH DOES NOT ALLOW THIS UNLESS | | IT IS APPROVED FOR AN ISLAND. | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-05-26 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-05-26 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-05-26 |
Time |
10:34 |
Sent To |
|
|
Notes |
2021-05-26 12:29:42 | 05/26/21 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. ON SHEET P0.1, UNDER PLUMBING SHEET INDEX, IT HAS A | | P2.2 SECOND FLOOR PLUMBING PLAN - DOMESTIC WATER & | | NATURAL GAS. NO SUCH PAGE WAS FOUND. PLEASE PROVIDE OR | | REMOVE FROM INDEX PER THE WPB AMENDMENTS TO THE FBC | | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2. ON SHEET P3.1; | | A. PLEASE SHOW THE LOCATION OF THE TANK-LESS WATER | | HEATER AND THE LOCATION AND DISTANCE OF ANY OPERABLE | | DOORS OR WINDOWS IN RELATION TO THE WATER HEATER. THE | | LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE | | MANUFACTURER'S INSTALLATION INSTRUCTIONS PER THE WPB | | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | | | B. PLEASE PROVIDE MANUFACTURER'S SPECIFICATION | | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO | | VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. | | | | C. PLEASE LIST THE BTU LOAD OF EACH APPLIANCE IN LEGEND | | TYPE AND THE TOTAL BTU LOAD ON THE SYSTEM PER THE WPB | | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | | | D. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, GAS | | METER TO THE MOST REMOTE OUTLET IN THE BUILDING AND | | SYSTEM PER THE 2020 FBC RES. SEC. G2413.4.1. | | | | E. PLEASE SUBMIT CALCULATIONS FOR COMBUSTION AIR PER | | THE 2020 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES | | DRYERS AND RANGE). IF PROVIDED BY SUPPLIED BY A LOUVER, | | PLEASE SHOW LOCATION. | | | | F. PLEASE PROVIDE THE SIZING TABLE USED IN THE DESIGN | | FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF | | PLANS LISTING THE SIZING TABLES FROM GAS CODES OR | | ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM PER | | THE 2020 FBC RES. SEC. G2413.3. | | | | G. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR | | THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. | | | | H. GAS P. E. SHOWN UNDER-SLAB IN A SLEEVE AND PIPING | | INSTALLED UNDERGROUND BENEATH BUILDINGS IS PROHIBITED | | PER THE 2020 FBC SEC. G2415.14 PIPING UNDERGROUND | | BENEATH BUILDINGS. THE AJH DOES NOT ALLOW THIS UNLESS | | IT IS APPROVED FOR AN ISLAND. | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2021-10-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-10-23 |
Time |
07:47 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-10-18 |
Time |
13:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-09-01 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-09-01 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-08-16 |
Time |
10:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-07-21 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-07-21 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-06-28 |
Time |
09:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-06-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-06-19 |
Time |
09:11 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-05-19 |
Time |
12:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2021-11-05 |
|
|
Cont ID |
|
Sent By |
ccarvaja |
Date |
2021-11-05 |
Time |
17:33 |
Rev Time |
0.00 |
Received By |
ccarvaja |
Date |
2021-10-23 |
Time |
07:47 |
Sent To |
|
|
Notes |
2021-11-05 17:34:41 | 11/05/21 MU-2021-051836-0000 $459.33 PAID - EMAILED PBC | | IMPACT OFFICE -STAMP.CC | 2021-10-23 07:47:49 | 10/23/21 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2021-06-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-06-19 |
Time |
07:38 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-06-19 |
Time |
07:38 |
Sent To |
|
|
Notes |
2021-06-19 07:39:08 | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT | | LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO | | THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF. | | THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ | | B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE | | RECEIPT TO PROJECT DOX OR EMAIL IT TO | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2021-08-20 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-08-20 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-08-20 |
Time |
17:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2021-06-29 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-06-29 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-06-29 |
Time |
07:31 |
Sent To |
|
|
Notes |
2021-06-29 07:35:11 | PLEASE PROVIDE THE INFORMATION REQUESTED BELOW IN THE | | 1ST CYCLE MECHANICAL PLAN REVIEW. | | | | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21050894 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. FBC EC R403.7 | | | | 2) PLEASE PROVIDE ENERGY CALCULATIONS. FBC EC | | 101.5.1.1.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2021-05-21 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-05-21 |
Time |
06:46 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-05-21 |
Time |
06:10 |
Sent To |
|
|
Notes |
2021-05-21 06:47:08 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21050894 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. FBC EC R403.7 | | | | 2) PLEASE PROVIDE ENERGY CALCULATIONS. FBC EC | | 101.5.1.1.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-08-25 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-08-25 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-08-25 |
Time |
09:50 |
Sent To |
|
|
Notes |
2021-08-25 09:50:36 | 08/25/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2021-05-25 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-05-25 |
Time |
12:33 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-05-25 |
Time |
11:44 |
Sent To |
|
|
Notes |
2021-05-25 12:33:34 | 05/25/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
4 |
Status |
P |
Date |
2021-10-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-10-23 |
Time |
06:25 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-10-22 |
Time |
15:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
F |
Date |
2021-08-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-08-18 |
Time |
09:24 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-08-18 |
Time |
06:45 |
Sent To |
|
|
Notes |
2021-08-18 09:44:16 | PLAN REVIEW ROOFING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 3RD REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ROOFING PERMIT REQUIRED. | | PERMITS - 105.1 REQUIRED. | | | | 2. DESIGNER SHALL SELECT METHOD OF INSTALLATION FOR | | ROOF TILE (SEE NOA NO. 18-0509.17) (MECHANICAL, | | ADHESIVE OR MORTAT SET) | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | 3. ROOFING UNDERLAYMENT - IF AN UNDERLAYMENT SYSTEM IS | | USED OTHER THAN PER ASTM D225, PROVIDE FLORIDA APPROVED | | PRODUCT APPROVAL | | (REF: RAS 118,119 AND 120). | | | | R905.1.1.2UNDERLAYMENT FOR CONCRETE AND CLAY TILE. | | UNDERLAYMENT FOR CONCRETE AND CLAY TILE SHALL COMPLY | | WITH SECTION 905.3. | | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2021-07-12 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-07-12 |
Time |
17:14 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-07-12 |
Time |
16:45 |
Sent To |
|
|
Notes |
2021-07-12 17:15:17 | PLAN REVIEW ROOFING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 2ND REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | NOTICE: COMMENTS FROM 1ST REVIEW HAVE NOT BEEN | | ADDRESSED. SEE BELOW. | | | | 1. ROOFING PERMIT REQUIRED. | | PERMITS - 105.1 REQUIRED. | | | | 2. NOA SUBMITTED FOR ROOFING INCLUDES PAGE 1 ONLY. | | PROVIDE COMPLETE SET OF PRODUCT APPROVALS | | | | 3. PROVIDE PRODUCT APPROVALS FOR UNDERLAYMENT. | | | | R905.1.1UNDERLAYMENT. | | UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL | | CONFORM TO THE APPLICABLE STANDARDS LISTED IN THIS | | CHAPTER. UNDERLAYMENT MATERIALS REQUIRED TO COMPLY WITH | | ASTM D226, D1970, D4869 AND D6757 SHALL BEAR A LABEL | | INDICATING COMPLIANCE TO THE STANDARD DESIGNATION AND, | | IF APPLICABLE, TYPE CLASSIFICATION INDICATED. | | UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL BE | | APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION | | R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE. | | | | R905.1.1.2UNDERLAYMENT FOR CONCRETE AND CLAY TILE. | | UNDERLAYMENT FOR CONCRETE AND CLAY TILE SHALL COMPLY | | WITH SECTION 905.3.3. | | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-06-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-06-19 |
Time |
07:53 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-06-19 |
Time |
06:07 |
Sent To |
|
|
Notes |
2021-06-19 08:03:58 | PLAN REVIEW ROOFING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. ROOFING PERMIT REQUIRED. | | PERMITS - 105.1 REQUIRED. | | | | 2. NOA SUBMITTED FOR ROOFING INCLUDES PAGE 1 ONLY. | | PROVIDE COMPLETE SET OF PRODUCT APPROVALS | | | | 3. PROVIDE PRODUCT APPROVALS FOR UNDERLAYMENT. | | | | R905.1.1UNDERLAYMENT. | | UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL | | CONFORM TO THE APPLICABLE STANDARDS LISTED IN THIS | | CHAPTER. UNDERLAYMENT MATERIALS REQUIRED TO COMPLY WITH | | ASTM D226, D1970, D4869 AND D6757 SHALL BEAR A LABEL | | INDICATING COMPLIANCE TO THE STANDARD DESIGNATION AND, | | IF APPLICABLE, TYPE CLASSIFICATION INDICATED. | | UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL BE | | APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION | | R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE. | | | | R905.1.1.2UNDERLAYMENT FOR CONCRETE AND CLAY TILE. | | UNDERLAYMENT FOR CONCRETE AND CLAY TILE SHALL COMPLY | | WITH SECTION 905.3.3. | | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-10-23 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-10-23 |
Time |
06:25 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-10-22 |
Time |
15:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-08-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-08-18 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-08-18 |
Time |
06:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2021-06-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-06-19 |
Time |
07:52 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-06-19 |
Time |
06:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2021-09-01 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2021-09-01 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2021-09-01 |
Time |
11:43 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-07-20 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2021-07-20 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2021-07-20 |
Time |
12:35 |
Sent To |
I |
|
Notes |
2021-07-20 13:53:14 | PREVIOUS ZONING COMMENTS NOT MET | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2021-05-24 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2021-05-24 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2021-05-24 |
Time |
16:55 |
Sent To |
I |
|
Notes |
2021-05-24 17:01:10 | | | ZONING PLAN REVIEW | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PROVIDE THE TOTAL HEIGHT OF THE PROPOSED HOME ON AN | | ELEVATION PLAN. PURSUANT TO THE ZLDR, SECTION 94-611, | | HEIGHT OF STRUCTURE MEANS THE VERTICAL DISTANCE FROM | | THE AVERAGE ELEVATION OF THE FINISHED GRADE OF THE | | STRUCTURE TO THE HIGHEST PORTION OF THE STRUCTURE, | | SUBJECT TO SPECIFIED HEIGHT REQUIREMENTS OF THIS | | CHAPTER. FOR BUILDINGS, THE HEIGHT SHALL BE MEASURED AS | | THE VERTICAL DISTANCE FROM THE AVERAGE ELEVATION OF THE | | FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT OF | | THE TOP OF THE STRUCTURE OF A FLAT ROOF, OR TO THE DECK | | LINE OF A MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL | | BETWEEN EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL | | ROOFS. | | | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | LIKE TO RESUBMIT ELECTRONICALLY, EMAIL | | [email protected] AND REQUEST TO HAVE YOUR | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG | | IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | ARE FINISHED UPLOADING. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | KIZZI ALEXANDRE, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|