Plan Review Details - Permit 21050792
Plan Review Stops For Permit 21050792
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-09-14 Cont ID  
Sent By jwitmer Date 2021-09-14 Time 13:11 Rev Time 0.00
Received By jwitmer Date 2021-09-14 Time 11:29 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-08-04 Cont ID  
Sent By jwitmer Date 2021-08-04 Time 16:30 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-08-04 16:30:28TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-23 Cont ID  
Sent By jwitmer Date 2021-06-23 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2021-06-23 Time 11:02 Sent To  
Notes
2021-06-23 11:21:56TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2022-01-18 Cont ID  
Sent By jwitmer Date 2022-01-18 Time 14:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-01-18 14:58:50THE DESIGNER OF RECORD HAS DELETED ALL FLOOR WORK. J.
 WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2021-11-23 Cont ID  
Sent By jwitmer Date 2021-11-23 Time 14:23 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-23 14:23:282020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21050792
 ADD: 400 N. FLAGLER DR. # 1705
 CONT: LARSEN BUILDERS CORP
 TEL: 561-403-5851
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: TUES. NOV. 23RD/ 2021
 ACTION: DENIED
  
  
 1) COMPLIED.
  
 2) 5TH REQUEST. EITHER THE CONTRACTOR AND OR DESIGN
 PROFESSIONAL NEED TO SUBMIT TEST RESULTS FOR COMMENTS
 2A, 2B & 2C NOT A SUMMARY SHEET FOR ARMSTRONG RESILIENT
 FLOORING. QUOTING CODE SECTIONS DOES NOT MEET THE CODE
 REQUIREMENTS.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2020 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED AS A
 WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 THE FLOOR PLAN A-1.0 INDICATES IN THE MASTER BEDROOM,
 BEDROOM 1 & 2 ALL ARE TO RECEIVE NEW MARBLE FLOORS.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY (TEST REPORTS ARE USUALLY 4
 PAGES FOR EACH REPORT) / NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) 5TH REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) 5TH REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) 5TH REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3-4) COMPLIED.
  
 5-8) COMPLIED. WINDOW/ DOOR PERMIT 21050794.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-11-09 Cont ID  
Sent By jwitmer Date 2021-11-09 Time 17:19 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-09 17:19:212020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21050792
 ADD: 400 N. FLAGLER DR. # 1705
 CONT: LARSEN BUILDERS CORP
 TEL: 561-403-5851
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4THREVIEW
 DATE: TUES. NOV. 09TH/ 2021
 ACTION: DENIED
  
  
 1) COMPLIED.
  
 2) THE FLOOR PLAN A-1.0 INDICATES IN THE MASTER
 BEDROOM, BEDROOM 1 & 2 ALL ARE TO RECEIVE NEW MARBLE
 FLOORS. FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR
 TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED
 TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY (TEST REPORTS ARE
 USUALLY 4 PAGES FOR EACH REPORT) / NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) 4TH REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) 4TH REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) 4TH REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3-4) COMPLIED.
  
 5) 4TH ROUND OF COMMENTS. PLEASE, PLEASE SUBMIT THE
 PRODUCT APPROVAL COVERSHEET AND TECHNICAL DRAWINGS IN
 THE SAME FILE FOLDER DO NOT SPLIT THEM UP INTO
 DIFFERENT FILE FOLDERS. IF THEY ARE NOT SUBMITTED
 TOGETHER FLORIDA APPROVALS DO NOT ALWAYS HAVE A
 TRACKING NUMBER ON THE TECHNICAL SHEETS. 107.2.1.2.
 ADDITIONAL INFORMATION REQUIRED. 107.2.1.3. QUALITY OF
 PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENT POLICY OTHER STANDARDS FOR THE PLANS AND
 SPECIFICATIONS IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORD MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 6) 4TH ROUND OF COMMENTS. IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY IN THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 7) 4TH ROUND OF COMMENTS. W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF
 APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 8) COMPLIED.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-09-14 Cont ID  
Sent By jwitmer Date 2021-09-14 Time 13:10 Rev Time 0.00
Received By jwitmer Date 2021-09-14 Time 11:29 Sent To  
Notes
2021-09-14 13:09:322020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21050792
 ADD: 400 N. FLAGLER DR. # 1705
 CONT: LARSEN BUILDERS CORP
 TEL: 561-403-5851
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. SEPT. 14TH/ 2021
 ACTION: DENIED
  
 ***** 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 *****
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) 2ND REQUEST. SHEET A-1.0 FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A DOCUMENT IN THE FILE FOLDER,
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) THE FLOOR PLAN INDICATES IN THE MASTER BEDROOM,
 BEDROOM 1 & 2 ALL ARE TO RECEIVE NEW MARBLE FLOORS.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) NO WIND DESIGN PROVIDED 2ND REVIEW.
  
 1ST ROUND OF COMMENTS. THE SUBMITTED WIND DESIGN BY
 MANUEL SIQUES P. E. IS NOT SIGNED NOR SEALED.
 361G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH
 LISTED PAGES OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE'S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.)
  
 4) 2ND ROUND OF COMMENTS. COULD NOT FIND THE COMPUTER
 GENERATED CALCULATIONS.
  
 1ST ROUND COMMENTS. WITHIN THE COMPUTER-GENERATED
 PROGRAM THE INPUT OF THE EAVE HEIGHT IS GIVEN AT 185
 FEET. PLEASE NOTE THE 1ST FLOOR AREAS ARE NOT THE
 NORMAL 8-FOOT-HIGH CEILINGS, PLUS THIS BUILDING BEING
 23 STORIES TALL THE EAVE HEIGHT OF 185 /23 = 8.043 FEET
 TALL OR 8 FEET -0 INCH, NO ROOM FOR THE FLOOR SLABS. I
 BELIEVE THE HEIGHT CALCULATION IS OFF THAT WILL AFFECT
 THE RESULT OF THE +/ - PRESSURES SHOWN IN THE PROGRAM
 AND FLOOR PLAN. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED. WE USUALLY SEE A HEIGHT OF 220 FT. FOR THIS
 BUILDING.
  
 5) 2ND ROUND OF COMMENTS. PLEASE, PLEASE SUBMIT THE
 PRODUCT APPROVAL COVERSHEET AND TECHNICAL DRAWINGS IN
 THE SAME FILE FOLDER DO NOT SPLIT THEM UP INTO
 DIFFERENT FILE FOLDERS. IF THEY ARE NOT SUBMITTED
 TOGETHER FLORIDA APPROVALS DO NOT ALWAYS HAVE A
 TRACKING NUMBER ON THE TECHNICAL SHEETS. 107.2.1.2.
 ADDITIONAL INFORMATION REQUIRED. 107.2.1.3. QUALITY OF
 PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENT POLICY OTHER STANDARDS FOR THE PLANS AND
 SPECIFICATIONS IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORD MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 6) 2ND ROUND OF COMMENTS. IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY IN THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 7) 2ND ROUND OF COMMENTS. W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF
 APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 8) 2ND ROUND OF COMMENTS. THE FLOOR PLAN IN THE
 BATHROOMS STATES NEW FIXTURES. IN BOTH THE GUEST SHOWER
 AND MASTER BATH ARE THE SHOWER WALLS AND SHOWER FLOORS
 BEING REPLACED, THE PLANS ARE NOT CLEAR ON THIS
 SUBJECT. IF SO PLEASE SHOW COMPLIANCE WITH: 2020 FBC-B
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL
 TILE IN TUB AND SHOWER AREAS AND WALLS AND CEILING
 PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN
 TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH
 MANUFACTURER?S RECOMMENDATIONS. WATER RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-04 Cont ID  
Sent By jwitmer Date 2021-08-04 Time 16:28 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-08-04 16:29:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21050792
 ADD: 400 N. FLAGLER DR. # 1705
 CONT: LARSEN BUILDERS CORP
 TEL: 561-403-5851
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. AUGUST 4, 2021
 ACTION: DENIED
 1) FLOOR PLAN A-1 & A-2. FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 (3)(C) A DOCUMENT IN THE FILE FOLDER,
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) 2ND REQUEST. THE FLOOR PLAN A-1 INDICATES IN THE
 MASTER BEDROOM, BEDROOM 1 & 2 ALL ARE TO RECEIVE NEW
 MARBLE FLOORS.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C)2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) SEMI-COMPLIED. NEEDS DIGITAL SIGNATURE OR BRING IN
 THE ORIGINAL PAPER ORIGINAL SIGNATURE AND SEAL.
 SUBMITTED WIND DESIGN BY MANUEL SIQUES P. E. IS NOT
 SIGNED NOR SEALED.
 361G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH
 LISTED PAGES OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.)
  
 4) COMPLIED. MEAN ROOF HEIGHT OF 220 FT.
  
 5) COMPLIED. PRODUCT APPROVAL COVERSHEET AND TECHNICAL
 REPORT IN SAME FOLDER.
  
 6) IDENTIFY GLAZING/ MULLIONS. SEMI-COMPLIED. PLEASE
 REVIEW SHEET A1-0 AND THE ASSOCIATED PRESSURES FOR
 OPENINGS IN WALL ZONE 4 AND WALL ZONE 5.
  
 6A) FIXED WINDOWS. FL26095-R3 TECH SHEET 4 OF 5
 HIGHLIGHTED PRESSURES LOW FOR ZONE 4 WHICH NEEDS =/-
 66.97 AND ZONE 5 +66.97/ -122.79.
  
 6B) SINGLE HUNG WINDOW FL9064-R10 PRESSURES GOOD.
  
 6C) SLIDERS FL251-R33 DOOR SIZES AND PRESSURES PAGES
 14-15 OF 30 NOT HIGHLIGHTED. NOTE PRESSURES ON BOTH
 PAGES ARE ONLY GOOD FOR +60/-60PSF. ZONE 4 -62.18 AND
 ZONE 5 -93.54. SILL HEIGHT MINIMUM 3 ? INCHES TO MEET +
 59.79 PSF.
  
 1ST ROUND OF COMMENTS. PLEASE IDENTIFY IN THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 7) SEMI-COMPLIED, NEW PRODUCT APPROVALS WILL NEED TO BE
 REVIEWED. W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING (SHOP DRAWING STAMP OF APPROVAL) BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 8) COMPLIED.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-23 Cont ID  
Sent By jwitmer Date 2021-06-23 Time 12:01 Rev Time 0.00
Received By jwitmer Date 2021-06-23 Time 11:02 Sent To  
Notes
2021-06-23 12:01:16WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21050792
 ADD: 400 N. FLAGLER DR. # 1705
 CONT: LARSEN BUILDERS CORP
 TEL: 561-403-5851
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 23RD/ 2021
 ACTION: DENIED
 1) FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) THE FLOOR PLAN INDICATES IN THE MASTER BEDROOM,
 BEDROOM 1 & 2 ALL ARE TO RECEIVE NEW MARBLE FLOORS.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) THE SUBMITTED WIND DESIGN BY MANUEL SIQUES P. E. IS
 NOT SIGNED NOR SEALED.
 361G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH
 LISTED PAGES OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET. .
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.)
  
 4) WITHIN THE COMPUTER-GENERATED PROGRAM THE INPUT OF
 THE EAVE HEIGHT IS GIVEN AT 185 FEET. PLEASE NOTE THE
 1ST FLOOR AREAS ARE NOT THE NORMAL 8-FOOT-HIGH
 CEILINGS, PLUS THIS BUILDING BEING 23 STORIES TALL THE
 EAVE HEIGHT OF 185 /23 = 8.043 FEET TALL OR 8 FEET ?
 INCH, NO ROOM FOR THE FLOOR SLABS. I BELIEVE THE HEIGHT
 CALCULATION IS OFF THAT WILL AFFECT THE RESULT OF THE
 +/ - PRESSURES SHOWN IN THE PROGRAM AND FLOOR PLAN.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. WE
 USUALLY SEE A HEIGHT OF 220 FT. FOR THIS BUILDING.
  
 5) PLEASE, PLEASE SUBMIT THE PRODUCT APPROVAL
 COVERSHEET AND TECHNICAL DRAWINGS IN THE SAME FILE
 FOLDER DO NOT SPLIT THEM UP INTO DIFFERENT FILE
 FOLDERS. IF THEY ARE NOT SUBMITTED TOGETHER FLORIDA
 APPROVALS DO NOT ALWAYS HAVE A TRACKING NUMBER ON THE
 TECHNICAL SHEETS. 107.2.1.2. ADDITIONAL INFORMATION
 REQUIRED. 107.2.1.3. QUALITY OF PLANS. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT POLICY OTHER
 STANDARDS FOR THE PLANS AND SPECIFICATIONS IN ORDER TO
 PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 8) THE FLOOR PLAN IN THE BATHROOMS STATES NEW FIXTURES.
 IN BOTH THE GUEST SHOWER AND MASTER BATH ARE THE SHOWER
 WALLS AND SHOWER FLOORS BEING REPLACED, THE PLANS ARE
 NOT CLEAR ON THIS SUBJECT. IF SO PLEASE SHOW COMPLIANCE
 WITH: 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED
 AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND
 WALLS AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-06-17 Cont ID  
Sent By fgiaquin Date 2021-06-17 Time 19:22 Rev Time 0.00
Received By fgiaquin Date 2021-06-15 Time 21:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2022-01-06 Cont ID  
Sent By pleduc Date 2022-01-06 Time   Rev Time 0.00
Received By pleduc Date 2022-01-06 Time 13:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-11-22 Cont ID  
Sent By pleduc Date 2021-11-22 Time   Rev Time 0.00
Received By pleduc Date 2021-11-22 Time 10:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-11-03 Cont ID  
Sent By pleduc Date 2021-11-03 Time   Rev Time 0.00
Received By pleduc Date 2021-11-03 Time 15:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-09-10 Cont ID  
Sent By pleduc Date 2021-09-10 Time   Rev Time 0.00
Received By pleduc Date 2021-09-10 Time 10:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-15 Cont ID  
Sent By pleduc Date 2021-06-11 Time   Rev Time 0.00
Received By fgiaquin Date 2021-06-11 Time 11:35 Sent To  
Notes
2021-06-11 11:41:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF CARPET BEING REMOVED AND
 NEW TILE INSTALLED IN THE BEDROOMS; OWEVER, THERE ARE
 NO FLOOR UNDERLAYMENT OR NEW TYPE OF FLOORING
 SPECIFICATIONS SHEETS THAT INDICATE MEETING THE
 REQUIREMENTS PER NFPA'
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
  
 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE
  
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN
 ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING
 ACTUAL
 INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING
 JURISDICTION IS
 PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY
 MATERIAL FOR WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE
 PROVIDED IN 10.2.1.2 OR 10.2.1.4.
 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO
 MATERIALS HAVING
 A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT
 ARE APPLIED DIRECTLY
 TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE
 FOLLOWING
 CONDITIONS ARE MET:
 (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE
 MATERIAL.
 (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF
 CLASS A INTERIOR
 WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH
 10.2.3,
 USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-01-18 Cont ID  
Sent By jwitmer Date 2022-01-18 Time 14:59 Rev Time 0.00
Received By jwitmer Date 2022-01-06 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2021-12-03 Time   Rev Time 0.00
Received By aoliver Date 2021-11-19 Time 17:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-15 Cont ID  
Sent By mpeterso Date 2021-11-15 Time 15:27 Rev Time 0.00
Received By mpeterso Date 2021-11-15 Time 15:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-16 Cont ID  
Sent By pvalenti Date 2021-09-16 Time 15:48 Rev Time 0.00
Received By pvalenti Date 2021-09-09 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2021-08-04 Time   Rev Time 0.00
Received By aoliver Date 2021-07-28 Time 07:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-06-23 Time 12:01 Rev Time 0.00
Received By cdecoeur Date 2021-06-04 Time 08:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-06-23 Cont ID  
Sent By jwitmer Date 2021-06-23 Time 11:20 Rev Time  
Received By jwitmer Date 2021-06-23 Time 11:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-01-06 Cont ID  
Sent By medwards Date 2022-01-06 Time 08:51 Rev Time 0.00
Received By medwards Date   Time   Sent To  
Notes
2022-01-06 08:51:39NO CHANGE WITH THIS CYCLE REVIEW:
  
 PRIVISO:
 PROVIDE THE COMPLETED "LIKE FOR LIKE" CHANGE OUT FORM
 AND THE AHRI SHEET FOR THE NEW AHU AND CONDENSER TO THE
 INSPECTOR AT INSPECTION. ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-06-15 Cont ID  
Sent By medwards Date 2021-06-15 Time 13:17 Rev Time 0.00
Received By medwards Date 2021-06-15 Time 13:17 Sent To  
Notes
2021-06-15 13:19:20PRIVISO:
 PROVIDE THE COMPLETED "LIKE FOR LIKE" CHANGE OUT FORM
 AND THE AHRI SHEET FOR THE NEW AHU AND CONDENSER TO THE
 INSPECTOR AT INSPECTION. ME

Review Stop P PLUMBING
Rev No 6 Status P Date 2022-01-06 Cont ID  
Sent By jesmith Date 2022-01-06 Time 13:47 Rev Time 0.00
Received By jesmith Date 2022-01-06 Time 13:46 Sent To  
Notes
2022-01-06 13:47:38PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-12-03 Cont ID  
Sent By ccole Date 2021-12-03 Time 09:46 Rev Time 0.00
Received By ccole Date 2021-12-03 Time 09:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2021-11-12 Cont ID  
Sent By cthroop Date 2021-11-12 Time 07:13 Rev Time 0.00
Received By jesmith Date 2022-01-06 Time 08:55 Sent To  
Notes
2021-11-12 07:14:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 4TH REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 FOURTH REQUEST: PER WPB FBC 107.2.1, PROVIDE A SHOWER
 WALL/ LINER/THRESHOLD DETAIL SHOWING THE FOLLOWING
 INFORMATION SHOWING COMPLIANCE WITH FBC PL 421.
  
 PARTIALLY COMPLIED;SEE BELOW
  
 1.DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL 421.5.2
 AS FOLLOWS:
 LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2
 INCHES ABOVE THE FINISHED THRESHOLD LEVEL
 LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED
 BACKING
 LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT
 LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAIN
 LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET
 AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT
 BETWEEN THE LINER AND THE OUTLET
 FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE
 LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE.
  
 2. LINER MATERIAL (SPECIFY LINER MATERIAL COMPLYING
 WITH ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1,
 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR
 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1 PLASTICIZED
 POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE
 REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21050792 400 N FLAGLER DR # 1705
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-09-16 Cont ID  
Sent By pvalenti Date 2021-09-16 Time 15:45 Rev Time 0.00
Received By jesmith Date 2022-01-06 Time 08:55 Sent To  
Notes
2021-09-16 15:46:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 3RD REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 B.DEMO PLAN SPECIFICALLY INDICATES REPLACEMENT OF THE
 WATER HEATER AND BATHROOM PLUMBING FIXTURES WATER
 CLOSETS AND LAVATORIES BUT MAKE NO MENTION OF THE
 SHOWERS. HOWEVER, THE DEMO LEGEND GIVES THE APPEARANCE
 THAT THE SHOWERS ARE TO BE REPLACED AS WELL;
 ARCHITECTURAL FLOOR PLAN INDICATES REPLACEMENT OF THE
 WATER HEATER AND BATHROOM PLUMBING FIXTURES WATER
 CLOSETS AND LAVATORIES AND BOTH SHOWERS. LATEST
 PLUMBING PLAN ONLY ADDRESSES THE WATER HEATER AND ONE
 BATHROOM.
 THIRD REQUEST: PER WPB FBC 107.2.1, PLEASE CLARIFY AND
 RECONCILE ALL THREE PLANS. NEW PLUMBING PLAN INDICATES
 WORK IN HALL BATHROOM ONLY. DEMO AND FLOOR PLAN
 INDICATE MASTER BATH IS AFFECTED AS WELL. IF WORK IS TO
 BE DONE IN THE SHOWER. IF PLUMBING PLAN IS CORRECT THEN
 ARCHITECTURAL AND DEMO PLAN NEEDS TO REFLECT THE SAME.
 TO BE CLEAR, PER WPB FBC 107.2.1, ALL THREE PLANS NEED
 TO REFLECT THE SAME BEFORE APPROVAL FOR PLUMBING
 PERMIT.
  
 ...B2) THIRD REQUEST: PER WPB FBC 107.2.1, PROVIDE A
 SHOWER WALL/ LINER/THRESHOLD DETAIL SHOWING THE
 FOLLOWING INFORMATION SHOWING COMPLIANCE WITH FBC PL
 421.
 RESPONSE IS THAT ARCHITECT TO ADDRESS. THAT WAS NOT
 DONE. APPLY TO THE BALANCE OF ALL COMMENTS BELOW. TO BE
 CLEAR, PER WPB FBC 107.2.1, APPROVAL FOR PLUMBING
 PERMIT WILL NOT BE ISSUED WITH OUT THIS INFORMATION
 BEING ON THE PLANS.
  
 .........B2A) FBC PL 421.3 WASTE OUTLETS SERVING
 SHOWERS SHALL BE NOT LESS THAN 1-1/2 INCHES (38 MM) IN
 DIAMETER AND, FOR OTHER THAN WASTE OUTLETS IN BATHTUBS,
 SHALL HAVE REMOVABLE STRAINERS NOT LESS THAN 3 INCHES
 (76 MM) IN DIAMETER WITH STRAINER OPENINGS NOT LESS
 THAN 1/4 INCH (6.4 MM) IN LEAST DIMENSION. WHERE EACH
 SHOWER SPACE IS NOT PROVIDED WITH AN INDIVIDUAL WASTE
 OUTLET, THE WASTE OUTLET SHALL BE LOCATED, AND THE
 FLOOR PITCHED SO THAT WASTE FROM ONE SHOWER DOES NOT
 FLOW OVER THE FLOOR AREA SERVING ANOTHER SHOWER. WASTE
 OUTLETS SHALL BE FASTENED TO THE WASTE PIPE IN AN
 APPROVED MANNER.
 .........B2B) FBC PL 421.4.1 BATHTUB FLOORS, SHOWER
 FLOORS, WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE
 INSTALLED SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL
 EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) ABOVE THE DRAIN OF THE TUB OR SHOWER. SUCH
 WALLS SHALL FORM A WATER-TIGHT JOINT WITH EACH OTHER
 AND WITH EITHER THE TUB OR SHOWER FLOOR.
 .........B2C) FBC PL 421.5 FLOOR SURFACES SHALL BE
 CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, NONABSORBENT
 AND WATERPROOF MATERIALS.
 .........B2D) FBC PL 421.5.1 FLOORS OR RECEPTORS UNDER
 SHOWER COMPARTMENTS SHALL BE LAID ON, AND SUPPORTED BY,
 A SMOOTH AND STRUCTURALLY SOUND BASE.
 .........B2E) FBC PL 421.5.2 FLOORS UNDER SHOWER
 COMPARTMENTS, EXCEPT WHERE PREFABRICATED RECEPTORS HAVE
 BEEN PROVIDED, SHALL BE LINED AND MADE WATER-TIGHT
 UTILIZING MATERIAL COMPLYING WITH SECTIONS 421.5.2.1
 THROUGH 421.5.2.6 (SEE BELOW). SUCH LINERS SHALL TURN
 UP ON ALL SIDES NOT LESS THAN 2 INCHES (51 MM) ABOVE
 THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE RECESSED
 AND FASTENED TO AN APPROVED BACKING SO AS NOT TO OCCUPY
 THE SPACE REQUIRED FOR WALL COVERING AND SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH (25
 MM) ABOVE THE FINISHED THRESHOLD. LINERS SHALL BE
 PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
 .........B2E1) FBC PL 421.5.2.1 PLASTICIZED POLYVINYL
 CHLORIDE (PVC) SHEETS SHALL MEET THE REQUIREMENTS OF
 ASTM D4551. SHEETS SHALL BE JOINED BY SOLVENT WELDING
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E2) FBC PL 421.5.2.2 NON-PLASTICIZED
 CHLORINATED POLYETHYLENE SHEET SHALL MEET THE
 REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE JOINED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E3) FBC PL 421.5.2.3 SHEET LEAD SHALL WEIGH
 NOT LESS THAN 4 POUNDS PER SQUARE FOOT (19.5 KG/M2) AND
 SHALL BE COATED WITH AN ASPHALT PAINT OR OTHER APPROVED
 COATING. THE LEAD SHEET SHALL BE INSULATED FROM
 CONDUCTING SUBSTANCES OTHER THAN THE CONNECTING DRAIN
 BY 15-POUND (6.80 KG) ASPHALT FELT OR AN EQUIVALENT.
 SHEET LEAD SHALL BE JOINED BY BURNING.
 .........B2E4) FBC PL 421.5.2.4 SHEET COPPER SHALL
 CONFORM TO ASTM B152 AND SHALL WEIGH NOT LESS THAN 12
 OUNCES PER SQUARE FOOT (3.7 KG/M2). THE COPPER SHEET
 SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER
 THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT
 FELT OR AN EQUIVALENT. SHEET COPPER SHALL BE JOINED BY
 BRAZING OR SOLDERING.
 .........B2E5) FBC PL 421.5.2.5 SHEET-APPLIED, LOAD
 BEARING, BONDED, WATERPROOF MEMBRANES SHALL MEET
 REQUIREMENTS OF ANSI A118.10 AND SHALL BE APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E6) FBC PL 421.5.2.6L LIQUID-TYPE,
 TROWEL-APPLIED, LOAD BEARING, BONDED WATERPROOF
 MATERIALS SHALL MEET THE REQUIREMENTS OF ANSI A118.10
 AND SHALL BE APPLIED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21050792 400 N FLAGLER DR # 1705
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-07-29 Cont ID  
Sent By jesmith Date 2021-07-29 Time 16:59 Rev Time 0.00
Received By jesmith Date 2021-07-29 Time 16:51 Sent To  
Notes
2021-07-29 16:59:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A. COMPLIED
 B.DEMO PLAN SPECIFICALLY INDICATES REPLACEMENT OF THE
 WATER HEATER AND BATHROOM PLUMBING FIXTURES WATER
 CLOSETS AND LAVATORIES BUT MAKE NO MENTION OF THE
 SHOWERS. HOWEVER, THE DEMO LEGEND GIVES THE APPEARANCE
 THAT THE SHOWERS ARE TO BE REPLACED AS WELL;
 ARCHITECTURAL FLOOR PLAN INDICATES REPLACEMENT OF THE
 WATER HEATER AND BATHROOM PLUMBING FIXTURES WATER
 CLOSETS AND LAVATORIES AND ONE SHOWER. PLUMBING PLAN
 ONLY ADDRESSES THE WATER HEATER.
 SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE CLARIFY AND
 RECONCILE ALL THREE PLANS. NEW PLUMBING PLAN INDICATES
 WORK IN HALL BATHROOM ONLY. DEMO AND FLOOR PLAN
 INDICATE MASTER BATH IS AFFETED AS WELL. IF WORK IS TO
 BE DONE IN THE SHOWER, INDICATE THE SCOPE AND PROVIDE
 ON THE PLUMBING PLAN THE FOLLOWING:
  
 ...B1) COMPLIED
  
 ...B2) PROVIDE A SHOWER WALL/DRAIN AND THRESHOLD DETAIL
 SHOWING THE FOLLOWING INFORMATION SHOWING COMPLIANCE
 WITH FBC PL 421
 RESPONSE IS THAT ARCHITECT TO ADDRESS. THAT WAS NOT
 DONE. APPLY TO THE BALANCE OF ALL COMMENTS BELOW.
  
 .........B2A) FBC PL 421.3 WASTE OUTLETS SERVING
 SHOWERS SHALL BE NOT LESS THAN 1-1/2 INCHES (38 MM) IN
 DIAMETER AND, FOR OTHER THAN WASTE OUTLETS IN BATHTUBS,
 SHALL HAVE REMOVABLE STRAINERS NOT LESS THAN 3 INCHES
 (76 MM) IN DIAMETER WITH STRAINER OPENINGS NOT LESS
 THAN 1/4 INCH (6.4 MM) IN LEAST DIMENSION. WHERE EACH
 SHOWER SPACE IS NOT PROVIDED WITH AN INDIVIDUAL WASTE
 OUTLET, THE WASTE OUTLET SHALL BE LOCATED, AND THE
 FLOOR PITCHED SO THAT WASTE FROM ONE SHOWER DOES NOT
 FLOW OVER THE FLOOR AREA SERVING ANOTHER SHOWER. WASTE
 OUTLETS SHALL BE FASTENED TO THE WASTE PIPE IN AN
 APPROVED MANNER.
 .........B2B) FBC PL 421.4.1 BATHTUB FLOORS, SHOWER
 FLOORS, WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE
 INSTALLED SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL
 EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) ABOVE THE DRAIN OF THE TUB OR SHOWER. SUCH
 WALLS SHALL FORM A WATER-TIGHT JOINT WITH EACH OTHER
 AND WITH EITHER THE TUB OR SHOWER FLOOR.
 .........B2C) FBC PL 421.5 FLOOR SURFACES SHALL BE
 CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, NONABSORBENT
 AND WATERPROOF MATERIALS.
 .........B2D) FBC PL 421.5.1 FLOORS OR RECEPTORS UNDER
 SHOWER COMPARTMENTS SHALL BE LAID ON, AND SUPPORTED BY,
 A SMOOTH AND STRUCTURALLY SOUND BASE.
 .........B2E) FBC PL 421.5.2 FLOORS UNDER SHOWER
 COMPARTMENTS, EXCEPT WHERE PREFABRICATED RECEPTORS HAVE
 BEEN PROVIDED, SHALL BE LINED AND MADE WATER-TIGHT
 UTILIZING MATERIAL COMPLYING WITH SECTIONS 421.5.2.1
 THROUGH 421.5.2.6 (SEE BELOW). SUCH LINERS SHALL TURN
 UP ON ALL SIDES NOT LESS THAN 2 INCHES (51 MM) ABOVE
 THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE RECESSED
 AND FASTENED TO AN APPROVED BACKING SO AS NOT TO OCCUPY
 THE SPACE REQUIRED FOR WALL COVERING AND SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH (25
 MM) ABOVE THE FINISHED THRESHOLD. LINERS SHALL BE
 PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
 .........B2E1) FBC PL 421.5.2.1 PLASTICIZED POLYVINYL
 CHLORIDE (PVC) SHEETS SHALL MEET THE REQUIREMENTS OF
 ASTM D4551. SHEETS SHALL BE JOINED BY SOLVENT WELDING
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E2) FBC PL 421.5.2.2 NON-PLASTICIZED
 CHLORINATED POLYETHYLENE SHEET SHALL MEET THE
 REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE JOINED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E3) FBC PL 421.5.2.3 SHEET LEAD SHALL WEIGH
 NOT LESS THAN 4 POUNDS PER SQUARE FOOT (19.5 KG/M2) AND
 SHALL BE COATED WITH AN ASPHALT PAINT OR OTHER APPROVED
 COATING. THE LEAD SHEET SHALL BE INSULATED FROM
 CONDUCTING SUBSTANCES OTHER THAN THE CONNECTING DRAIN
 BY 15-POUND (6.80 KG) ASPHALT FELT OR AN EQUIVALENT.
 SHEET LEAD SHALL BE JOINED BY BURNING.
 .........B2E4) FBC PL 421.5.2.4 SHEET COPPER SHALL
 CONFORM TO ASTM B152 AND SHALL WEIGH NOT LESS THAN 12
 OUNCES PER SQUARE FOOT (3.7 KG/M2). THE COPPER SHEET
 SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER
 THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT
 FELT OR AN EQUIVALENT. SHEET COPPER SHALL BE JOINED BY
 BRAZING OR SOLDERING.
 .........B2E5) FBC PL 421.5.2.5 SHEET-APPLIED, LOAD
 BEARING, BONDED, WATERPROOF MEMBRANES SHALL MEET
 REQUIREMENTS OF ANSI A118.10 AND SHALL BE APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E6) FBC PL 421.5.2.6L LIQUID-TYPE,
 TROWEL-APPLIED, LOAD BEARING, BONDED WATERPROOF
 MATERIALS SHALL MEET THE REQUIREMENTS OF ANSI A118.10
 AND SHALL BE APPLIED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21050792 400 N FLAGLER DR # 1705

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-17 Cont ID  
Sent By jesmith Date 2021-06-17 Time 09:40 Rev Time 0.00
Received By jesmith Date 2022-01-06 Time 13:46 Sent To  
Notes
2021-06-17 09:20:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A. WATER HEATER DETAIL; LACKS THERMAL EXPANSION DEVICE
 AND HEATER PAN. PER WPB FBC 107.2.1, SHOW AND SPECIFY A
 SIZED THERMAL EXPANSION DEVICE AS REQUIRED BY FBC PL
 607.3. IT IS NOTED THAT PER FBC PL 504.7.2 A PAN IS NOT
 REQUIRED FOR A REPLACEMENT WATER HEATER IF A PAN WAS
 NOT PREVIOUSLY INSTALLED. PER WPB FBC 107.2.1, PROVIDE
 NOTE ON THE PLAN IF A HEATER PAN WAS NOT PREVIOUSLY
 INSTALLED; OTHERWISE PROVIDE A PAN AND DRAIN PER FBC PL
 504.7.1.
  
 B. DEMO PLAN SPECIFICALLY INDICATES REPLACEMENT OF THE
 WATER HEATER AND BATHROOM PLUMBING FIXTURES WATER
 CLOSETS AND LAVATORIES BUT MAKE NO MENTION OF THE
 SHOWERS. HOWEVER, THE DEMO LEGEND GIVES THE APPEARANCE
 THAT THE SHOWERS ARE TO BE REPLACED AS WELL;
 ARCHITECTURAL FLOOR PLAN INDICATES REPLACEMENT OF THE
 WATER HEATER AND BATHROOM PLUMBING FIXTURES WATER
 CLOSETS AND LAVATORIES AND ONE SHOWER. PLUMBING PLAN
 ONLY ADDRESSES THE WATER HEATER. PER WPB FBC 107.2.1,
 PLEASE CLARIFY AND RECONCILE ALL THREE PLANS. IF WORK
 IS TO BE DONE IN THE SHOWER, INDICATE THE SCOPE AND
 PROVIDE ON THE PLUMBING PLAN THE FOLLOWING:
 ...B1) SHOWER VALVE SPECIFICATION; SHALL COMPLY WITH
 FBC PL 412.3, WHICH SHALL BE PRESSURE BALANCED PB,
 THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE
 TYPES WITH HIGH TEMPERATURE LIMITING STOP THAT CONFORM
 TO THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE.
 ...B2) PROVIDE A SHOWER WALL/DRAIN AND THRESHOLD DETAIL
 SHOWING THE FOLLOWING INFORMATION SHOWING COMPLIANCE
 WITH FBC PL 421
 .........B2A) FBC PL 421.3 WASTE OUTLETS SERVING
 SHOWERS SHALL BE NOT LESS THAN 1-1/2 INCHES (38 MM) IN
 DIAMETER AND, FOR OTHER THAN WASTE OUTLETS IN BATHTUBS,
 SHALL HAVE REMOVABLE STRAINERS NOT LESS THAN 3 INCHES
 (76 MM) IN DIAMETER WITH STRAINER OPENINGS NOT LESS
 THAN 1/4 INCH (6.4 MM) IN LEAST DIMENSION. WHERE EACH
 SHOWER SPACE IS NOT PROVIDED WITH AN INDIVIDUAL WASTE
 OUTLET, THE WASTE OUTLET SHALL BE LOCATED, AND THE
 FLOOR PITCHED SO THAT WASTE FROM ONE SHOWER DOES NOT
 FLOW OVER THE FLOOR AREA SERVING ANOTHER SHOWER. WASTE
 OUTLETS SHALL BE FASTENED TO THE WASTE PIPE IN AN
 APPROVED MANNER.
 .........B2B) FBC PL 421.4.1 BATHTUB FLOORS, SHOWER
 FLOORS, WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE
 INSTALLED SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL
 EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) ABOVE THE DRAIN OF THE TUB OR SHOWER. SUCH
 WALLS SHALL FORM A WATER-TIGHT JOINT WITH EACH OTHER
 AND WITH EITHER THE TUB OR SHOWER FLOOR.
 .........B2C) FBC PL 421.5 FLOOR SURFACES SHALL BE
 CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, NONABSORBENT
 AND WATERPROOF MATERIALS.
 .........B2D) FBC PL 421.5.1 FLOORS OR RECEPTORS UNDER
 SHOWER COMPARTMENTS SHALL BE LAID ON, AND SUPPORTED BY,
 A SMOOTH AND STRUCTURALLY SOUND BASE.
 .........B2E) FBC PL 421.5.2 FLOORS UNDER SHOWER
 COMPARTMENTS, EXCEPT WHERE PREFABRICATED RECEPTORS HAVE
 BEEN PROVIDED, SHALL BE LINED AND MADE WATER-TIGHT
 UTILIZING MATERIAL COMPLYING WITH SECTIONS 421.5.2.1
 THROUGH 421.5.2.6 (SEE BELOW). SUCH LINERS SHALL TURN
 UP ON ALL SIDES NOT LESS THAN 2 INCHES (51 MM) ABOVE
 THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE RECESSED
 AND FASTENED TO AN APPROVED BACKING SO AS NOT TO OCCUPY
 THE SPACE REQUIRED FOR WALL COVERING AND SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH (25
 MM) ABOVE THE FINISHED THRESHOLD. LINERS SHALL BE
 PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
 .........B2E1) FBC PL 421.5.2.1 PLASTICIZED POLYVINYL
 CHLORIDE (PVC) SHEETS SHALL MEET THE REQUIREMENTS OF
 ASTM D4551. SHEETS SHALL BE JOINED BY SOLVENT WELDING
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E2) FBC PL 421.5.2.2 NON-PLASTICIZED
 CHLORINATED POLYETHYLENE SHEET SHALL MEET THE
 REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE JOINED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E3) FBC PL 421.5.2.3 SHEET LEAD SHALL WEIGH
 NOT LESS THAN 4 POUNDS PER SQUARE FOOT (19.5 KG/M2) AND
 SHALL BE COATED WITH AN ASPHALT PAINT OR OTHER APPROVED
 COATING. THE LEAD SHEET SHALL BE INSULATED FROM
 CONDUCTING SUBSTANCES OTHER THAN THE CONNECTING DRAIN
 BY 15-POUND (6.80 KG) ASPHALT FELT OR AN EQUIVALENT.
 SHEET LEAD SHALL BE JOINED BY BURNING.
 .........B2E4) FBC PL 421.5.2.4 SHEET COPPER SHALL
 CONFORM TO ASTM B152 AND SHALL WEIGH NOT LESS THAN 12
 OUNCES PER SQUARE FOOT (3.7 KG/M2). THE COPPER SHEET
 SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER
 THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT
 FELT OR AN EQUIVALENT. SHEET COPPER SHALL BE JOINED BY
 BRAZING OR SOLDERING.
 .........B2E5) FBC PL 421.5.2.5 SHEET-APPLIED, LOAD
 BEARING, BONDED, WATERPROOF MEMBRANES SHALL MEET
 REQUIREMENTS OF ANSI A118.10 AND SHALL BE APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
 .........B2E6) FBC PL 421.5.2.6L LIQUID-TYPE,
 TROWEL-APPLIED, LOAD BEARING, BONDED WATERPROOF
 MATERIALS SHALL MEET THE REQUIREMENTS OF ANSI A118.10
 AND SHALL BE APPLIED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21050792 400 N FLAGLER DR # 1705
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2022-01-18 Cont ID  
Sent By jwitmer Date 2022-01-18 Time 14:59 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-11-23 Cont ID  
Sent By mpeterso Date 2021-11-23 Time 10:35 Rev Time 0.00
Received By mpeterso Date 2021-11-23 Time 10:43 Sent To  
Notes
2021-11-23 10:40:51PAPER PLANS LABELED "D-1, A-1, A-2, AND P-1 " WERE
 SUBMITTED ON 11/19/2021 WITH A WET SIGNATURE AND SEAL.
  
 PLANS LABELED "E-1 AND M-1" WERE NOT SUBMITTED WITH
 PAPER PLANS ON 11/19/2021.
  
 PLANS LABELED 'E-1 AND M-1" IN PROJECT DOX ARE COPIES
 OF SEALS AND SIGNATURES.
  
 CORRECT BY SUBMITTING PROPERLY SIGNED AND SEALED PLANS
 LABELED "E-1" AND "M-1" AS OUTLINED BELOW
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-11-15 Cont ID  
Sent By mpeterso Date 2021-11-15 Time 14:57 Rev Time 0.00
Received By mpeterso Date 2021-11-15 Time 14:57 Sent To  
Notes
2021-11-15 15:26:51PLANS LABELED E 1 AND M1 APPEAR TO BE COPIES OF
 ORIGINAL SEALED AND SIGNED DRAWINGS. ALL OTHER DRAWINGS
 APPEAR TO BE DIGITALLY SEALED AND SIGNED, HOWEVER, THE
 SIGNATURE FROM THE ENGINEER OF RECORD APPEARS TO BE
 SELF AUTHORIZED SIGNATURES. PROFESSIONAL ENGINEERS ARE
 REQUIRE TO HAVE THEIR IDENTITY AUTHENTICATED BY A
 CERTIFICATION AUTHORITY . F.A.C 61G15?23.004
  
 PLEASE CORRECT THESE ISSUES FOLLOWING THE DIRECTIONS
 BELOW
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-09-16 Cont ID  
Sent By pvalenti Date 2021-09-16 Time 15:47 Rev Time 0.00
Received By pvalenti Date 2021-09-16 Time 15:47 Sent To  
Notes
2021-09-16 15:48:21CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTI
  
 SIGNATURE REVIEW DENIED:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-04 Cont ID  
Sent By jwitmer Date 2021-08-04 Time 16:32 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-08-04 16:32:35FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By medwards Date 2021-06-15 Time 13:23 Rev Time 0.00
Received By medwards Date 2021-06-15 Time 13:23 Sent To  
Notes
2021-06-15 13:25:48THE DRAWINGS ARE HAND STAMPED AND SGNED BUT SUBMITTED
 DIGITALLY. WE CAN NOT VERIFY THE STAMP OR SIGNATURE.
 PLEASE BRING THE ORIGINAL SIGNED AND SEALED PAPER
 DRAWINGS TO OUR OFFICE OR PROVIDE DIGITALLY SIGNED
 DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  