Plan Review Stops For Permit 21050758 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2021-05-21 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-05-21 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-05-21 |
Time |
13:42 |
Sent To |
|
|
Notes |
2021-05-21 13:43:16 | CONTRACTOR CLARIFIED THAT THE UNIT IS INDEED 101, | | UPDATED PERMIT |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2021-05-14 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-05-14 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-05-14 |
Time |
16:00 |
Sent To |
|
|
Notes |
2021-05-14 16:02:21 | APPLICATION FOR LISTS PCN 74434315420010010 HOWEVER | | THAT PCN HAS AN ADDRESS OF 101 AND THE APPLICATION FORM | | LIST 102. PLEASE CONFIRM THE PCN AND SUITE NUMBER. | | PLEASE EMAIL [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2021-08-04 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-08-04 |
Time |
22:40 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-08-04 |
Time |
20:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2021-07-27 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-07-27 |
Time |
21:47 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-07-27 |
Time |
20:49 |
Sent To |
|
|
Notes |
2021-07-27 21:47:45 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE LOAD CALCULATION. NEC 215, 220 LOAD | | CALCULATION PROVIDED SHOWS NO CALCULATION ONLY A PANEL | | SCHEDULE. | | | | 2. SATISFIED. | | | | 3. SATISFIED. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-05-24 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-05-24 |
Time |
19:23 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-05-24 |
Time |
19:16 |
Sent To |
|
|
Notes |
2021-05-24 19:22:48 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE LOAD CALCULATION. NEC 215, 220 | | | | 2. SPEC SHEET DOES NOT SPECIFY MODEL OF CHARGER. FBC | | 107.2.1 | | | | 3. NEWEST UPLOADED PERMIT APPLICATION IS NOT SIGNED BY | | OWNER. PLEASE PROVIDE CORRECTION. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2021-07-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-07-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-07-30 |
Time |
11:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2021-07-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-07-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-07-22 |
Time |
11:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2021-05-21 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-05-21 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-05-21 |
Time |
12:58 |
Sent To |
|
|
Notes |
2021-05-21 13:03:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF ELECTIRCAL EQUIPMENT | | BREACHING THE ELECTRICAL ROOM FIRE WALL. THERE ARE NO | | INDICATIONS OF PROPTECTING THIS BREACH WITH A LISTED | | FIRE WALL OPENING PROTECTION. | | | | PLEASE REVIEW AND PROVIDE THE REQUIRED LISTED OPENING | | PROTECTION. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-08-04 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-08-04 |
Time |
22:40 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-07-29 |
Time |
08:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-07-27 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-07-27 |
Time |
21:48 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-07-21 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-05-24 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-05-24 |
Time |
19:28 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-05-18 |
Time |
11:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-08-04 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-08-04 |
Time |
22:40 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-08-04 |
Time |
22:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-07-27 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-07-27 |
Time |
21:46 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-07-27 |
Time |
21:46 |
Sent To |
|
|
Notes |
2021-07-27 21:46:27 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-805-6744 | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-05-24 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-05-24 |
Time |
19:28 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-05-24 |
Time |
19:24 |
Sent To |
|
|
Notes |
2021-05-24 19:28:28 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-805-6744 | | | | | | | | | | | | | | |
|
|