Plan Review Stops For Permit 21050739 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2022-08-23 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2022-08-23 |
Time |
19:31 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2022-08-22 |
Time |
20:33 |
Sent To |
|
|
Notes |
2022-08-23 19:15:41 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ENGINEERED DRAWGINGS PROVIDED ARE NOT SIGNED BY | | ENGINEER. | | ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND | | SIGNED/SEALED BY A DESIGN PROFESSIONAL PROVIDE | | CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | 2. NO LOAD CALCULATION PROVIDED AS PER LAST PLAN REVIEW | | COMMENTS NEC 220 FBC 107.2.1 | | | | 3. 4- 4/0 AND #8 EGC DO NOT FIT IN 1-1/4'' CONDUIT. | | PROVIDE CORRECTION. | | | | 4. OCP SHOWN FOR CHARGER IS 75 AMPS. OCP OVER 60AMPS | | REQUIRES DISCONNECT WITHIN SITE OF CHARGER PER NEC | | 625.43. PROVIDE CORRECTION. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-805-6744 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2021-10-01 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-10-01 |
Time |
21:13 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-10-01 |
Time |
20:41 |
Sent To |
|
|
Notes |
2021-10-01 21:03:51 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. NO REPONSE LETTER HAS BEEN PROVIDED. BASED OFF OF | | INFORMATION PROVIDED EXISTING SERVICE IS 480V AND PLANS | | WILL HAVE TO BE ENGINEERED. F.S. 471.003(2)(H)(2A) | | | | 2. LOAD CALCULATION REQUIRED (ENGINEERED) NEC 220. | | | | 3. VALUE STILL LOW. PROVIDE ACCURATE VALUE AND SIGNED | | CONTRACT BY OWNER AS INSTRUCTED. VALUE TO INCLUDE ALL | | MATERIALS AND LABOR. FBC 109.3 | | | | 4. OCP STILL NOT PROVIDED FOR CHARGERS. FBC 107.2.1 | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-805-6744 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-05-25 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-05-25 |
Time |
22:00 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-05-25 |
Time |
20:22 |
Sent To |
|
|
Notes |
2021-05-25 22:00:32 | CTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ARE YOU PROPOSING A NEW 400AMP SERVICE? OR IS THAT | | THE LOCATION OF THE EXISTING SERVICE? FBC 107.2.1 | | | | INFORMATIONAL NOTE: PER NEC 230.2 ONLY ONE SERVICE IS | | PERMITTED PER BUILDING UNLESS ONE OF THE CONDITIONS OF | | NEC 230.2 IS MET. | | | | 2. PROVIDE LOAD CALCULATION. NEC 215, 220 | | | | 3. PROVIDE PANEL SCHEDULES. FBC 107.2.1 | | | | 4. PROVIDE ONE-LINE DIAGRAM OF PROPOSED WORK AND | | SERVICE. FBC 107.2.1 | | | | 5. NO OVERCURRENT PROTECTION SHOWN FOR NEW CAR | | CHARGERS. FBC 107.2.1 | | | | 6. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE ACCURATE | | VALUE AND SIGNED CONTRACT. SIGNED BY BOTH OWNER AND | | CONTRACTOR. FBC 109.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2022-08-25 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2022-08-25 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2022-08-14 |
Time |
08:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-10-01 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-10-01 |
Time |
21:17 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-09-10 |
Time |
09:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-05-28 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-05-28 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-05-14 |
Time |
11:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2022-08-23 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2022-08-23 |
Time |
19:31 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2022-08-23 19:31:43 | MUST BE DIGITALLY SIGNED BY PE |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-10-01 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-10-01 |
Time |
21:16 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-10-01 |
Time |
21:15 |
Sent To |
|
|
Notes |
2021-10-01 21:16:56 | PLANS MUST BE DESIGNED AND SIGNED SEALED BY A DESIGN | | PROFESSIONAL. VOLTAGE IS 480. F.S. 471.003(2)(H)(2A) |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-05-28 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-05-28 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-05-28 |
Time |
16:14 |
Sent To |
|
|
Notes |
2021-05-28 16:16:24 | PLAN REVIEW / SIGNATURES | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NEC2017 | | | | 1ST REVIEW | | RESULTS: DENIED | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD | | SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN | | SHEETS UNDER THEIR AUTHORITY. | | 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1, SECTION 107.2.1. | | | | 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL | | WITH SIGNATURE OF DESIGNER AS APPLICABLE; USE THE | | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT OR DROP | | OFF (OR MAIL) ONE PAPER ORIGINAL WITH CONTRACTORS/O/B | | SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | CITY OF WEST PALM BEACH | | 401 CLEMATIS ST | | WEST PALM BEACH, FL 33401 | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2022-08-25 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2022-08-25 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2022-08-25 |
Time |
|
Sent To |
|
|
Notes |
2022-08-25 10:21:19 | ZONING APPROVED WITH THE FOLLOWING PROVISOS: | | | | 1.) LANDSCAPE HEDGE/SCREEN REQUIRED AROUND BROOKS BOX | | TO SCREEN FROM VIEW (IF APPLICABLE). | | | | 2.) SEE ATTACHED STAMPED SHEETS IN PERMIT SET FOR | | ZONING APPROVAL. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-09-30 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2021-09-30 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2021-09-30 |
Time |
|
Sent To |
|
|
Notes |
2021-09-30 08:23:07 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE (COMMENTS NOT ADDRESSED FROM 5/26/2021): | | | | 1.) IT IS NOT CLEAR WHICH PARKING STALLS ON SITE WILL | | BE IMPACTED BY THE SCOPE OF WORK. THE PLANS MUST SHOW | | WHICH PARKING STALLS WILL BE IMPACTED. IF THE CHARGING | | STATIONS ARE TO BE LOCATED WITHIN AN EXISTING BUILDING, | | THEN THE PLANS MUST CLEARLY SPECIFY. | | | | 2.) ANY EXTERIOR SITE IMPROVEMENT(S) WHICH WILL IMPACT | | THE APPROVED SITE PLAN WILL REQUIRE A MINOR PLANNED | | DEVELOPMENT (PD) AMENDMENT TO THE APPROVED PLANS WITH | | THE DEVELOPMENT SERVICES DEPARTMENT-PLANNING DIVISION. | | THIS IS A SEPARATE PROCESS AND APPROVAL FROM THE | | BUILDING PERMIT PROCESS. | | | | | | NOTES: | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. | | | | * ZONE: CPD (SCHUMACHER) | | | | * SPOKE TO CLAY AT CARPENTER ELECTRIC TO GO OVER | | OUTSTANDING ZONING COMMENTS ON 9/29/2021. ALSO EMAILED | | CLAY THE LATEST SITE PLAN FOR VOLVO TO SHOW HOW THE | | SITE WILL BE IMPACTED BY THE PROPOSED CHANGES. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2021-05-26 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2021-05-26 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2021-05-26 |
Time |
|
Sent To |
|
|
Notes |
2021-05-26 09:06:40 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) IT IS NOT CLEAR WHICH PARKING STALLS ON SITE WILL | | BE IMPACTED BY THE SCOPE OF WORK. THE PLANS MUST SHOW | | WHICH PARKING STALLS WILL BE IMPACTED. IF THE CHARGING | | STATIONS ARE TO BE LOCATED WITHIN AN EXISTING BUILDING, | | THEN THE PLANS MUST CLEARLY SPECIFY. | | | | 2.) ANY EXTERIOR SITE IMPROVEMENT(S) WHICH WILL IMPACT | | THE APPROVED SITE PLAN WILL REQUIRE A MINOR PLANNED | | DEVELOPMENT (PD) AMENDMENT TO THE APPROVED PLANS WITH | | THE DEVELOPMENT SERVICES DEPARTMENT-PLANNING DIVISION. | | THIS IS A SEPARATE PROCESS AND APPROVAL FROM THE | | BUILDING PERMIT PROCESS. | | | | | | NOTES: | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. | | | | * ZONE: CPD (SCHUMACHER) | | |
|
|