Plan Review Details - Permit 21050658
Plan Review Stops For Permit 21050658
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-25 Cont ID  
Sent By rmcphers Date 2021-06-25 Time 11:19 Rev Time 0.00
Received By rmcphers Date 2021-06-25 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-09 Cont ID  
Sent By rmcphers Date 2021-06-09 Time 15:46 Rev Time 0.00
Received By rmcphers Date 2021-06-09 Time 15:31 Sent To  
Notes
2021-06-09 15:46:25BATH REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE WALL FRAMING DETAILS SHOWING - ON
 CENTER FRAMING, ATTACHMENTS ETC ( FIRE RETARDANT OR NON
 CUMBUSTIBLE FRAMING MATERIAL PER FBC 603.1)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-25 Cont ID  
Sent By jleahy Date 2021-06-25 Time 12:40 Rev Time 0.00
Received By jleahy Date 2021-06-25 Time 12:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-27 Cont ID  
Sent By equinone Date 2021-05-27 Time 11:16 Rev Time 0.00
Received By equinone Date 2021-05-27 Time 11:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-29 Cont ID  
Sent By lcrespo Date 2021-06-29 Time 10:00 Rev Time 0.00
Received By lcrespo Date 2021-06-17 Time 10:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-09 Cont ID  
Sent By rmcphers Date 2021-06-09 Time 15:49 Rev Time 0.00
Received By rmcphers Date 2021-05-14 Time 13:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-29 Cont ID  
Sent By lcrespo Date 2021-06-29 Time 09:59 Rev Time 0.00
Received By lcrespo Date 2021-06-29 Time 09:59 Sent To  
Notes
2021-06-29 10:00:0006/29/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-02 Cont ID  
Sent By lcrespo Date 2021-06-02 Time 12:53 Rev Time 0.00
Received By lcrespo Date 2021-06-02 Time 12:45 Sent To  
Notes
2021-06-02 12:53:2406/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. THIS BUILDING WAS ORIGINALLY BUILT AND DESIGNED
 UNDER THE FAIR HOUSING ACT GUIDELINES AND THE LEVEL OF
 ACCESSIBILITY CANNOT BE DECREASED. THE PLANNED
 ALTERATIONS TO THE MASTER BATH DO NOT COMPLY WITH THE
 REQUIREMENTS OF THE FAIR HOUSING ACT GUIDELINES. IF YOU
 WOULD LIKE TO CONTINUE PLEASE PROVIDE DRAWING THAT SHOW
 THE CLEAR FLOOR SPACE AND FOR FHA COMPLIANCE THAT
 PROVIDES THE TWO SETS OF SPECIFICATIONS TO DESIGN
 BATHROOMS THAT ARE USABLE BY PEOPLE WITH DISABILITIES.
 THOUGH THERE ARE OTHER DIFFERENCES, SPECIFICATION B
 BATHROOMS OFFER GREATER ACCESS TO THE TUB THAN
 SPECIFICATION A BATHROOMS.
  
 IF THE SPECIFICATION A DESIGN IS SELECTED, ALL
 BATHROOMS IN THE UNIT MUST COMPLY WITH SPECIFICATION A
 STANDARD (SECTION 7.14). THIS INCLUDES ACCESS TO ALL
 FIXTURES IN EACH SPECIFICATION A BATHROOM (E.G., TWO
 LAVATORIES IN ONE BATHROOM WOULD BOTH NEED TO MEET FHA
 REGULATIONS).
  
 IF THE SPECIFICATION B DESIGN IS SELECTED, ONLY ONE
 BATHROOM IN THE UNIT, AND ONLY ONE OF EACH TYPE OF
 FIXTURE WITHIN THE BATHROOM, MUST COMPLY WITH
 SPECIFICATION B STANDARDS (SECTION 7.15). ALL OTHER
 BATHROOMS IN THE UNIT MUST MEET THE USABLE BATHROOM
 REQUIREMENTS (SECTION 7.11), EXEMPTING MANEUVERING
 CLEARANCES, AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES.
  
 2. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 PROVIDES AN OPTION FOR THE CHANGING OF AN FHA
 COMPLIANCE STRUCTURE. THE OWNER AND DESIGNER OF RECORD
 ACKNOWLEDGE THAT THE PROPOSED BATHROOM DESIGN DOES NOT
 MEET THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES. THE OWNER AGREES TO REVERT THE UNIT BACK TO
 COMPLIANCE AT THE TIME OF SALE IF SO, REQUESTED BY THE
 BUYER. THIS WILL BE IN A LETTER TYPE FORMAT SIGNED AND
 NOTARIZED BY THE OWNER. WE PROVIDE A SAMPLE LETTER AND
 IT MUST BE SUBMITTED TO THE BUILDING DEPARTMENT OF THE
 CITY OF WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN
 EMAIL TO [email protected] AND I WILL SEND A COPY OF THE
 FAIR HOUSING AFFIDAVIT.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-06-17 Cont ID  
Sent By medwards Date 2021-06-17 Time 16:35 Rev Time 0.00
Received By medwards Date 2021-06-17 Time 16:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-09 Cont ID  
Sent By rmcphers Date 2021-06-09 Time 15:51 Rev Time 0.00
Received By rmcphers Date 2021-06-09 Time 15:50 Sent To  
Notes
2021-06-09 15:55:33SIGNATURE REVIEW
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 1) DRAWINGS NEED DESIGNERS NAME AND SIGNATURE FBC WPB
 107.2.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-05-14 Cont ID  
Sent By equinone Date 2021-05-14 Time 16:26 Rev Time 0.00
Received By equinone Date 2021-05-14 Time 16:26 Sent To  
Notes
***NONE***