Plan Review Details - Permit 21050513
Plan Review Stops For Permit 21050513
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-18 Cont ID  
Sent By jgomez Date 2022-07-18 Time 15:18 Rev Time 0.00
Received By jgomez Date 2022-07-18 Time 10:37 Sent To  
Notes
2022-07-18 15:19:57RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21050513
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- LOT DRAINAGE (SEC. 606 FBC-EXISTING BUILDING)
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 3- OK.
  
 4- SHEET S1.1 (NOTE: CHANGE OF DESIGN PROFESSIONAL. NEW
 DRAWINGS S-1 THRU S-6 SUBMITTED):
  
 ORIGINAL COMMENT:
 (A)PARTIAL FLOOR PLAN: PROVIDE LAYOUT OF ROOMS ADJACENT
 TO THE PROPOSED ADDITION. NEED THIS TO VERIFY IF THERE
 ARE BEDROOMS ADJACENT TO THE ADDITION AND EXISTING
 EGRESS REQUIREMENTS ARE NOT CHANGED OR BLOCKED.
 SEC. 606 FBC-EXISTING BUILDING. SEC. 107.3.5.3 CITY
 AMENDMENTS.
  
 RESPONSE:
 REVISED PLANS SHOW EXISTING BEDROOM ADJACENT TO THE
 ADDITION. ACCORDING TO PLAN SUBMITTED THERE IS AN
 EXISTING DOOR LEADING TO THE OUTSIDE. THE PROPOSED
 ADDITION IS BLOCKING THE BEDROOM EMERGENCY EGRESS. NEED
 TO SHOW EMERGENCY ESCAPE COMPLIANCE FOR EXISTING
 BEDROOM. CLEARLY SPECIFY IF THERE IS ANY EXISTING
 WINDOW COMPLYING WITH SEC. R310.2.1 FBC-RESIDENTIAL.
 SPECIFY WINDOW TYPE AND SIZE (WIDTH X HEIGHT)
  
 (B)OK.
  
 ORIGINAL COMMENT:
 (C)REVISE DESIGN CRITERIA: WIND EXPOSURE DOESN'T MATCH
 WIND EXPOSURE IN TRUSS NOTE #1 ON SHEET S1.2. REVISE AS
 REQUIRED.
 SEC. 606 FBC-EXISTING BUILDING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 REVISED PLANS ARE MISSING THE WIND EXPOSURE.
  
 ORIGINAL COMMENT:
 (D)DESIGN CRITERIA SPECIFIES: FULLY OPEN DESIGN AND
 INTERNAL PRESSURE COEFFICIENT = N/A. THIS BUILDING IS
 NOT OPEN. REVISE AS REQUIRED.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REVISED PLANS ARE MISSING THIS INFORMATION.
  
 ORIGINAL COMMENT:
 (E)REVISE BUILDING CATEGORY. THIS BUILDING IS NOT
 CATEGORY I. IT IS CATEGORY II. SEE SEC. 1604.5
 FBC-BUILDING.
 SEC. 606 FBC-EXISTING BUILDING.
  
 RESPONSE:
 REVISED PLANS ARE MISSING THIS INFORMATION.
  
 ORIGINAL COMMENT:
 (F) FOUNDATION PLAN DOESN'T PROVIDE SPECIFICATIONS FOR
 CONCRETE SLAB. PROVIDE COMPLETE SPECIFICATIONS. FOOTING
 SIZE, REINFORCEMENT, VAPOR BARRIER, ETC.
 SEC. 606 FBC-EXISTING BUILDING. SEC. 107.3.5.3 CITY
 AMENDMENTS.
  
 RESPONSE:
 INFORMATION SUBMITTED IS NOT CLEAR. THERE ARE SEVERAL
 DIFFERENT DETAILS SUBMITTED SHOWING NEW CONCRETE SLAB
 OVER EXISTING. THIS INFORMATION DOESN'T MATCH PROPOSED
 ADDITION. PROVIDE ONLY THE DETAILS THAT APPLY TO THIS
 JOB. ALSO, TYPE OF FOOTING AND PROPOSED EXTERIOR WALLS
 DON'T MATCH. COORDINATE ALL DETAILS TO AVOID MORE
 CONFLICTS/DELAYS. SPECIFY VAPOR BARRIER AND CONCRETE
 SLAB REINFORCEMENT.
  
 ORIGINAL COMMENT:
 (G)WALL SECTION AND EXTERIOR ELEVATIONS DON'T SPECIFY
 THE ROOF PITCH.
 PROVIDE INFORMATION.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R905.2
 FBC-RESIDENTIAL.
  
 RESPONSE:
 ROOF PITCH IS NOT CLEAR. SEE ROOF PLANS AND REVISE AS
 REQUIRED TO MATCH. ALSO, FOOTING ON THE TYPICAL WALL
 SECTION ON SHEET S-5 DOESN'T MATCH FOUNDATION PLAN.
 NOTE: THIS APPLIES TO OTHER WALL SECTIONS SHOWN ON
 OTHER DRAWINGS SUBMITTED.
  
 (H) OK.
  
 ORIGINAL COMMENT:
 (I)WALL SECTION: SPECIFY ROOFING UNDERLAYMENT SHOWING
 COMPLIANCE WITH ANY OF THE OPTIONS OF SEC. R905.1.1.1
 FBC-RESIDENTIAL.
 SEC. 606 FBC-EXISTING BUILDING.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 (J)WALL SECTION TO PROVIDE COMPLETE INFORMATION FOR
 SOFFIT CONSTRUCTION.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R703.1.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REVISED TYPICAL WALL SECTION ON SHEET S-5 ONLY
 SPECIFIES "GAL. MTL. LATH" AS THE METAL BASE TO SUPPORT
 THE STUCCO. THIS METAL BASE DOESN'T COMPLY WITH TABLE 3
 OF ASTM C1063 BASED ON THE CEILING TRUSS SPACING. SEE
 TABLE 3 OF ASTM C1063 AND REVISE AS REQUIRED.
  
 (K) OK.
  
 ORIGINAL COMMENT:
 (L)REVISE MASONRY BUCK DETAIL. BEVELED BUCKS ARE NOT
 ALLOWED. 2X4 BUCKS DON'T PROVIDE FULL SUPPORT TO THE
 DOOR FRAME AS REQUIRED BY R609.7.2.1 FBC-RESIDENTIAL.
 REVISE AS REQUIRED.
 SEC. 606 FBC-EXISTING BUILDING.
  
 RESPONSE:
 DETAILS SUBMITTED ARE FOR WOOD FRAME CONSTRUCTION. NEED
 TO PROVIDE DETAILS FOR MASONRY CONSTRUCTION PROVIDING
 THE INFORMATION REQUESTED ABOVE.
  
 NEW COMMENTS BASED ON NEW PLANS SUBMITTED:
 (M)THE DIGITAL SIGNATURE OF THE NEW ENGINEER OF RECORD
 HAS A SELF CERTIFIED DIGITAL SIGNATURE. A THIRD PARTY
 CERTIFICATION IS REQUIRED. FBPE DOES NOT ALLOW USE OF
 SELF CERTIFIED SIGNATURES. PLEASE OBTAIN A DIGITAL
 SIGNATURE ISSUED BY A CERTIFICATE AUTHORITY (OFTEN
 CALLED 3RD PARTY).
 FAC 61G15-23.004
  
 (N)THE PERMIT APPLICATION AND PREVIOUS PLANS CALLED FOR
 A NEW "BEDROOM" ADDITION. PLANS SUBMITTED NOW CALL FOR
 "STORAGE" ADDITION. IT IS NOT CLEAR WHAT IS GOING TO BE
 THE USE OF THE PROPOSED ADDITION. SEC. 102.2 CITY
 AMENDMENTS.
 NOTE: THE DESCRIPTION ON THE PERMIT APPLICATION AND
 PLANS MUST MATCH TO AVOID CONFLICTS/DELAYS. REVISE AS
 REQUIRED TO MATCH. ENGINEER OF RECORD TO CLEARLY LABEL
 ON THE FLOOR PLAN THE ROOM NAME.
  
 (O)PLANS ARE MISSING THE ROOF TRUSSES LOAD INFORMATION.
 ENGINEER OF RECORD TO SPECIFY ALL ROOF LIVE AND DEAD
 LOADS. CLEARLY SPECIFY TRUSS TOP AND BOTTOM CHORDS LIVE
 AND DEAD LOADS INCLUDING THE ATTIC LIVE LOAD AS
 REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. NOTE: SEE
 FOOTNOTES "B" AND "G".
  
 (P)ENGINEER OF RECORD TO PROVIDE ALL THE WIND DESIGN
 CRITERIA AS REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
 SPECIFY THE ULTIMATE AND NOMINAL WIND LOAD, BUILDING
 EXPOSURE, BUILDING MEAN ROOF HEIGHT, ETC.
  
 (Q)ROOF SHEATHING SPECS ON SHEET S-5: SPECIFY ROOF
 SHEATHING THICKNESS AND SPECIFY RING SHANK NAILS AS
 REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL
  
 (R) SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807.1
 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 5- PROVIDE COMPLETE INFORMATION FOR ATTACHMENT OF
 PROPOSED ADDITION TO EXISTING STRUCTURE AT WALLS AND
 ROOFING AREAS.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R301.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 6- SHEET S1.2 (NOTE: CHANGE OF DESIGN PROFESSIONAL. NEW
 DRAWINGS S-1 THRU S-6 SUBMITTED):
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR GABLE
 END CONSTRUCTION. IS THERE A RAKED BEAM?. IF SO,
 PROVIDE SPECS. SHOW BEAM IN THE ROOF FRAMING PLAN.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 7-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
  
 ORIGINAL COMMENT:
 A)EXTERIOR DOORS.
  
 RESPONSE:
 NOA 20-1230.07 SUBMITTED IS FOR "INSWING" DOOR. PLANS
 SHOW "OUTSWING" DOOR. REVISE AS REQUIRED TO MATCH.
 ALSO, NOA SUBMITTED IS EXPIRED.
  
 B)OK.
 C) OK.
  
 D)ROOF SHINGLES.
  
 E)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-30 Cont ID  
Sent By jgomez Date 2021-06-30 Time 17:09 Rev Time 0.00
Received By jgomez Date 2021-06-30 Time 10:17 Sent To  
Notes
2021-06-30 17:11:14RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21050513
  
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 606
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORRMS ARE PROPERLY SIGNED BY
 ALL REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO
 AVOID CONFLICTS/DELAYS.
  
 2- LOT DRAINAGE (SEC. 606 FBC-EXISTING BUILDING)
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3-PROVIDE SITE PLAN SHOWING THE LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE AND
 DISTANCES FROM LOT LINES. SITE PLAN TO BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY.
 SEC. 606 FBC-EXISTING BUILDING. SEC. 107.2.5 CITY
 AMENDMENTS.
  
 4- SHEET S1.1:
 (A)PARTIAL FLOOR PLAN: PROVIDE LAYOUT OF ROOMS ADJACENT
 TO THE PROPOSED ADDITION. NEED THIS TO VERIFY IF THERE
 ARE BEDROOMS ADJACENT TO THE ADDITION AND EXISTING
 EGRESS REQUIREMENTS ARE NOT CHANGED OR BLOCKED.
 SEC. 606 FBC-EXISTING BUILDING. SEC. 107.3.5.3 CITY
 AMENDMENTS.
  
 (B)PARCEL CONTROL NUMBER SHOWN UNDER DATA GATHERED FROM
 PAPA IS INCORRECT. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (C)REVISE DESIGN CRITERIA: WIND EXPOSURE DOESN'T MATCH
 WIND EXPOSURE IN TRUSS NOTE #1 ON SHEET S1.2. REVISE AS
 REQUIRED.
 SEC. 606 FBC-EXISTING BUILDING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 (D)DESIGN CRITERIA SPECIFIES: FULLY OPEN DESIGN AND
 INTERNAL PRESSURE COEFFICIENT = N/A. THIS BUILDING IS
 NOT OPEN. REVISE AS REQUIRED.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 (E)REVISE BUILDING CATEGORY. THIS BUILDING IS NOT
 CATEGORY I. IT IS CATEGORY II. SEE SEC. 1604.5
 FBC-BUILDING.
 SEC. 606 FBC-EXISTING BUILDING.
  
 (F) FOUNDATION PLAN DOESN'T PROVIDE SPECIFICATIONS FOR
 CONCRETE SLAB. PROVIDE COMPLETE SPECIFICATIONS. FOOTING
 SIZE, REINFORCEMENT, VAPOR BARRIER, ETC.
 SEC. 606 FBC-EXISTING BUILDING. SEC. 107.3.5.3 CITY
 AMENDMENTS.
  
 (G)WALL SECTION AND EXTERIOR ELEVATIONS DON'T SPECIFY
 THE ROOF PITCH.
 PROVIDE INFORMATION.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R905.2
 FBC-RESIDENTIAL.
  
 (H) WINDOW AND DOOR SCHEDULE. CLEARLY SPECIFY THE
 DESIGN PRESSURES FOR ALL DOORS AND WINDOWS. MISSING
 SOME. REVISE/UPDATE PRODUCT APPROVALS NUMBERS. SOME ARE
 EXPIRED.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 (I)WALL SECTION: SPECIFY ROOFING UNDERLAYMENT SHOWING
 COMPLIANCE WITH ANY OF THE OPTIONS OF SEC. R905.1.1.1
 FBC-RESIDENTIAL.
 SEC. 606 FBC-EXISTING BUILDING.
  
 (J)WALL SECTION TO PROVIDE COMPLETE INFORMATION FOR
 SOFFIT CONSTRUCTION.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R703.1.2.1
 FBC-RESIDENTIAL.
  
 (K)WALL SECTION TO PROVIDE COMPLETE INFORMATION FOR
 ATTIC VENT.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R806
 FBC-RESIDENTIAL.
  
 (L)REVISE MASONRY BUCK DETAIL. BEVELED BUCKS ARE NOT
 ALLOWED. 2X4 BUCKS DON'T PROVIDE FULL SUPPORT TO THE
 DOOR FRAME AS REQUIRED BY R609.7.2.1 FBC-RESIDENTIAL.
 REVISE AS REQUIRED.
 SEC. 606 FBC-EXISTING BUILDING.
  
 5- PROVIDE COMPLETE INFORMATION FOR ATTACHMENT OF
 PROPOSED ADDITION TO EXISTING STRUCTURE AT WALLS AND
 ROOFING AREAS.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R301.1
 FBC-RESIDENTIAL.
  
 6- CLARIFY SHEET S1.2:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR GABLE
 END CONSTRUCTION. IS THERE A RAKED BEAM?. IF SO,
 PROVIDE SPECS. SHOW BEAM IN THE ROOF FRAMING PLAN.
 SEC. 606 FBC-EXISTING BUILDING. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 7-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
 A)EXTERIOR DOORS.
 B)WINDOWS.
 C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 D)SHINGLES.
 E)ROOFING UNDERLAYMENT SPECIFIED ON TWO STORY WALL
 SECTION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-01 Cont ID  
Sent By jleahy Date 2022-07-01 Time 16:09 Rev Time 0.00
Received By jleahy Date 2022-07-01 Time 16:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-26 Cont ID  
Sent By jleahy Date 2021-05-26 Time 10:41 Rev Time 0.00
Received By jleahy Date 2021-05-26 Time 10:39 Sent To  
Notes
2021-05-26 10:42:20ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL LAYOUT FOR OUTLETS LIGHTS AND SWITCHES.

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2022-07-12 Cont ID  
Sent By amhamilt Date 2022-07-12 Time 15:01 Rev Time 0.00
Received By amhamilt Date 2022-07-12 Time 15:01 Sent To  
Notes
2022-07-12 15:02:06THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 WINDOW SCHEDULE INDICATES GLASS WILL BE TINTED, ONLY
 CLEAR GLASS PERMITTED IN HISTORIC DISTRICTS. PLEASE
 REVISE TO CLEAR GLASS (LOW E PERMISSIBLE ON NON-STREET
 FACING ELEVATIONS)
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-07-01 Cont ID  
Sent By aborngra Date 2021-07-01 Time 08:59 Rev Time 0.00
Received By aborngra Date 2021-07-01 Time 08:58 Sent To  
Notes
2021-07-01 08:59:08THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. A CERTIFICATE OF APPROPRIATENESS (COA) APPLICATION
 IS REQUIRED TO BE SUBMITTED AND HEARD BY THE HISTORIC
 PRESERVATION BOARD. PLEASE CONTACT STAFF AT
 [email protected] (ON OR BEFORE JULY 2ND) OR
 [email protected] (AFTER JULY 2ND) TO REQUEST THE
 APPLICATION. THE APPLICATION IS ALSO LISTED ON THE
 CITY?S WEBSITE AT HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELO
 PMENT-SERVICES/FORMS. THE REQUEST WILL BE FOR
 ?ADDITIONS: ALL OTHER ADDITIONS?. THE APPLICATION FEE
 IS $100.00. THE APPLICATION HAS A LIST OF ALL REQUIRED
 MATERIALS. THE APPLICATION DEADLINES ARE LISTED ON PAGE
 2. THE NEXT DEADLINE IS JULY 14, 2021 FOR THE AUGUST
 24, 2021 HISTORIC PRESERVATION BOARD MEETING.
  
 PLEASE NOTE, FULL ELEVATIONS AND FLOOR PLANS ARE
 REQUIRED TO BE SUBMITTED. A PARTIAL ELEVATION WILL NOT
 BE ACCEPTED.
  
 2. PROVIDE A SURVEY AND A SITE PLAN INDICATING SETBACKS
 FOR THE PROPOSED STRUCTURE.
 3. PROVIDE THE PROJECT DATA TABLE INDICATING LOT
 COVERAGE FOR THE PROPERTY. THIS IS ALL ROOFED SPACES.
 4. REVISE THE ELEVATIONS TO INDICATE A SCORE LINE OF A
 MINIMUM HALF AN INCH TO INDICATE WHERE THE ADDITION
 STARTS ON BOTH ELEVATIONS.
 5. PROVIDE ON A SITE PLAN INDICATING WHERE TWO PARKING
 SPACES OF AT LEAST 8.5 FEET BY 18 FEET ARE ON THE
 PROPERTY.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 AT [email protected] OR 561-822-1457.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-18 Cont ID  
Sent By jgomez Date 2022-07-18 Time 15:21 Rev Time 0.00
Received By jgomez Date 2022-06-14 Time 17:05 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-01 Cont ID  
Sent By jgomez Date 2021-07-01 Time 13:42 Rev Time 0.00
Received By jgomez Date 2021-05-11 Time 14:30 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-06-30 Cont ID  
Sent By jgomez Date 2021-06-30 Time 17:21 Rev Time 0.00
Received By jgomez Date 2021-06-30 Time 17:21 Sent To  
Notes
2021-06-30 17:22:00IMPACT FEES
  
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-06-22 Cont ID  
Sent By medwards Date 2022-06-22 Time 09:10 Rev Time 0.00
Received By medwards Date 2022-06-22 Time 09:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-25 Cont ID  
Sent By medwards Date 2021-05-25 Time 15:23 Rev Time 0.00
Received By medwards Date 2021-05-25 Time 15:23 Sent To  
Notes
2021-05-25 15:28:311ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21050513
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7.1
  
 3) PLEASE PROVIDE CONDENSING UNIT ANCHORING DETAILS.
 FBC RES R1307.2
  
 4) PLEASE SHOW THE CONDENSATE DISPOSAL. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-05-27 Cont ID  
Sent By lcrespo Date 2021-05-27 Time 10:39 Rev Time 0.00
Received By lcrespo Date 2021-05-27 Time 10:23 Sent To  
Notes
2021-05-27 10:39:35NO PLUMBING IN THIS SCOPE OF WORK.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-07-18 Cont ID  
Sent By jgomez Date 2022-07-18 Time 15:20 Rev Time 0.00
Received By jgomez Date 2022-07-18 Time 15:20 Sent To  
Notes
2022-07-18 15:20:58ROOFING REVIEW COMMENTS:
  
 1--PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 A)SHINGLES.
 B)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-06-30 Cont ID  
Sent By jgomez Date 2021-06-30 Time 17:22 Rev Time 0.00
Received By jgomez Date 2021-06-30 Time 17:22 Sent To  
Notes
2021-06-30 17:22:52ROOFING REVIEW COMMENTS:
  
 1--PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
 A)SHINGLES.
 B)ROOFING UNDERLAYMENT SPECIFIED ON TWO STORY WALL
 SECTION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-06-22 Cont ID  
Sent By medwards Date 2022-06-22 Time 09:12 Rev Time 0.00
Received By medwards Date 2022-06-22 Time 09:12 Sent To  
Notes
2022-06-22 09:15:42PLEASE SEE PREVIOUS REVIEW COMMENTS BELOW. AN ENGINEER
 MUST HAVE THEIR DIGITAL SIGNATURE THIRD PARTY VERIFIED.
  
 DESIGNER MUST PROVIDE THE ORIGINAL DITALLY SIGN
 DRAWINGS OR YOU CAN BRING THE ORIGINAL SIGNED AND
 SEALED DRAWINGS TO OUR OFFICE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-25 Cont ID  
Sent By medwards Date 2021-05-25 Time 15:28 Rev Time 0.00
Received By medwards Date 2021-05-25 Time 15:28 Sent To  
Notes
2021-05-25 15:30:01DESIGNER MUST PROVIDE THE ORIGINAL DITALLY SIGN
 DRAWINGS OR YOU CAN BRING THE ORIGINAL SIGNED AND
 SEALED DRAWINGS TO OUR OFFICE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-07-12 Cont ID  
Sent By afowlkes Date 2022-07-12 Time 11:39 Rev Time 0.00
Received By amhamilt Date 2022-07-12 Time 11:39 Sent To  
Notes
2022-07-12 11:42:41THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PLEASE SHOW ON SITE PLAN HOW PARKING REQUIREMENT WILL
 BE MET. PLEASE ALSO INDICATE THAT AT LEAST 75% OR 1,000
 SF (WHICHEVER IS LESS) OF THE FRONT SETBACK OFF OF 37TH
 STREET WILL BE GREENSPACE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-06-09 Cont ID  
Sent By kalexand Date 2021-06-09 Time 15:29 Rev Time 0.00
Received By kalexand Date 2021-06-09 Time 15:17 Sent To I
Notes
2021-06-09 15:31:47ZONING PLAN REVIEW
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A CURRENT SURVEY, WHICH INCLUDES THE
 PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. PLEASE
 ILLUSTRATE THE FOLLOWING ON THE SURVEY AND/OR SITE
 PLAN:
 - LOCATION OF THE PROPOSED ADDITION.
 - SETBACK DIMENSIONS FROM ANY EXTERIOR IMPROVEMENTS TO
 ALL ADJACENT PROPERTY LINES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved