Plan Review Stops For Permit 21050495 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
P |
Date |
2021-07-19 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2021-07-19 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2021-07-19 |
Time |
07:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2021-05-13 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2021-05-13 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2021-05-13 |
Time |
14:46 |
Sent To |
|
|
Notes |
2021-05-13 14:52:40 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | ASBESTOS REQUIREMENTS: | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2021-07-19 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2021-07-19 |
Time |
07:50 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2021-07-19 |
Time |
07:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-05-13 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2021-05-13 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2021-05-13 |
Time |
14:46 |
Sent To |
|
|
Notes |
2021-05-13 15:00:45 | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING REVIEW FAILED: | | | | THE SUBMITTED PLANS ARE REQUIRED TO BE SIGNED/SEALED BY | | A DESIGN PROFESSIONAL (ENGINEER OR ARCHITECT) AS PER | | THE FLORIDA STATUTES FS 471 & FS 481. | | | | | | PROVISO: | | | | ALL WORK NEEDS TO MEET THE REQUIREMENTS OF FBC B | | CHAPTER 33 (SAFEGUARDS DURING CONSTRUCTION). | | | | NOTE: THIS DEMO PERMIT COVERS ONLY THE DEMOLITION OF | | NON-BEARING & NON FIRE RATED WALLS AS INDICATED ON THE | | SUBMITTED PLANS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2021-07-20 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-07-20 |
Time |
06:29 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-07-20 |
Time |
06:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-07-06 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-07-06 |
Time |
09:59 |
Sent To |
|
|
Notes |
2021-07-06 10:04:13 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT | | APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL | | PERMIT APPLICATION TO [email protected] AND CC | | [email protected] SO I RECEIVE IT ALSO. WHEN THIS EMAIL | | IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN | | REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-05-13 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-05-13 |
Time |
22:53 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-05-13 |
Time |
22:22 |
Sent To |
|
|
Notes |
2021-05-13 22:53:43 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. APPLICATION REQUIRED BY LICENSED ELECTRICAL | | CONTRACTOR FOR PROPOSED ELECTRIC DEMO. FBC 105.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-07-06 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-07-06 |
Time |
13:46 |
Sent To |
|
|
Notes |
2021-07-06 13:51:19 | FIRE SPRINKLER LETTER STATES A REVIEW WILL TAKE PLACE | | ON COMPLETION | | TO ENSURE NO MODIFICATION IS REQUIRED. | | | | PLEASE ENSURE COMPLIANCE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2021-05-25 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-05-25 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-05-25 |
Time |
09:04 |
Sent To |
|
|
Notes |
2021-05-25 09:08:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PLAN SHEET CLEARLY SHOWS THE REMOVAL OF INTERIOR | | WALLS; HOWEVER THE COVER SHEET INDICATES NO WALLS BEING | | REMOVED. | | | | PPLEASE PROVIDE CLARIFICATIONS. | | | | | | 2) ANY REMOVAL OF WALLS REQUIRES AN EVALUTION OF THE | | FIRE SPRINKLER HEAD LOCATIONS FOR CODE COMPLIANT | | COVERAGE. | | | | ANY REQUIRED WORK ON THE FS SYSTEM SHALL BE DONE UNDER | | SEPARATE PERMIT AND SHOP DRAWINGS. | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-07-19 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2021-07-19 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2021-07-01 |
Time |
08:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-05-13 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2021-05-13 |
Time |
22:53 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2021-05-12 |
Time |
14:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-07-01 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-07-01 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-07-01 |
Time |
17:02 |
Sent To |
|
|
Notes |
2021-07-01 17:04:27 | ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS ROUTED TO | | STORAGE.ME |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2021-05-13 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-05-13 |
Time |
07:00 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-05-13 |
Time |
06:58 |
Sent To |
|
|
Notes |
2021-05-13 07:01:11 | ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO | | STORAGE.ME |
|
|