Plan Review Details - Permit 21050378
Plan Review Stops For Permit 21050378
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-09-15 Cont ID  
Sent By rmcdouga Date 2021-09-15 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2021-09-15 Time 15:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-07-29 Cont ID  
Sent By rmcdouga Date 2021-07-29 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2021-07-29 Time 11:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-07-24 Cont ID  
Sent By fgiaquin Date 2021-07-24 Time 13:53 Rev Time 0.00
Received By fgiaquin Date 2021-07-24 Time 12:53 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-09-16 Cont ID  
Sent By lcrespo Date 2021-09-16 Time 11:59 Rev Time 0.00
Received By lcrespo Date 2021-09-16 Time 11:59 Sent To  
Notes
2021-09-16 11:59:4209/16/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-07-21 Cont ID  
Sent By lcrespo Date 2021-07-21 Time 09:58 Rev Time 0.00
Received By lcrespo Date 2021-07-21 Time 09:58 Sent To  
Notes
2021-07-21 09:58:18GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-07-23 Cont ID  
Sent By jroach Date 2021-07-23 Time 13:19 Rev Time 0.00
Received By jroach Date 2021-07-23 Time 13:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-15 Cont ID  
Sent By rmcdouga Date 2021-09-15 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2021-08-24 Time 07:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-29 Cont ID  
Sent By rmcdouga Date 2021-07-29 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2021-07-12 Time 11:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-09-03 Cont ID  
Sent By lcrespo Date 2021-09-03 Time 09:54 Rev Time 0.00
Received By lcrespo Date 2021-09-03 Time 09:50 Sent To  
Notes
2021-09-03 09:54:4709/03/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By lcrespo Date 2021-07-21 Time 09:56 Rev Time 0.00
Received By lcrespo Date 2021-07-21 Time 09:56 Sent To  
Notes
2021-07-21 09:57:137/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW
 THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS.
 THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVE, FILTER,
 ETC., BUT THERE IS NO FRICTION LOSS OF THE GAS HEATER.
 WOULD YOU PLEASE ADD AND RECALCULATE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 3. HEATED SWIMMING POOLS AND INGROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS PER THE 2017
 FBC- ENERGY- SEC. R 403.10.3. WOULD YOU PLEASE PLACE A
 NOTE ON THE PLANS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-15 Cont ID  
Sent By rmcdouga Date 2021-09-15 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2021-09-15 Time 15:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-24 Cont ID  
Sent By fgiaquin Date 2021-07-24 Time 17:10 Rev Time 0.00
Received By fgiaquin Date 2021-07-24 Time 17:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-07-23 Cont ID  
Sent By jroach Date 2021-07-23 Time 13:21 Rev Time 0.00
Received By jroach Date 2021-07-23 Time 13:21 Sent To  
Notes
2021-07-23 13:21:50PROVISOS:
  
 1. ALL POOL EQUIPMENT SHALL BE A MINIMUM OF ONE (1)
 FOOT FROM THE SIDE PROPERTY LINE.
  
 2. POOL SHALL BE ENCLOSED BY A PERMANENT FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED
 (?BABY FENCE? DOES NOT MEET THIS REQUIREMENT). BARRIERS
 OR FENCES SHALL BE AT LEAST 4 FEET IN HEIGHT ABOVE
 GRADE.
  
 3. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.
  
 4. PATIO OR PAVED AREA ADJACENT TO OR SURROUNDING THE
 POOL SHALL BE DESIGNED TO DRAIN AWAY FROM THE POOL, BUT
 NOT ONTO ADJACENT PROPERTIES.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved