Plan Review Details - Permit 21050228
Plan Review Stops For Permit 21050228
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-06-15 Cont ID  
Sent By cpuell Date 2021-06-15 Time 15:38 Rev Time 0.00
Received By cpuell Date 2021-06-15 Time 15:38 Sent To  
Notes
2021-06-15 15:38:58SUITE 1204 ADDED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-06 Cont ID  
Sent By cpuell Date 2021-05-06 Time 08:37 Rev Time 0.00
Received By cpuell Date 2021-05-06 Time 08:37 Sent To  
Notes
2021-05-06 08:41:47SUITE 1204 IS NOT CURRENTLY IN OUR SYSTEM, PLEASE
 PROVIDE A FULL FLOOR PLAN INCLUDING ALL THE SUITES ON
 THE FLOOR. PLEASE EMAIL [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 10:01 Rev Time 0.00
Received By rmcphers Date 2021-06-24 Time 10:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-04 Cont ID  
Sent By rmcphers Date 2021-06-04 Time 11:16 Rev Time 0.00
Received By rmcphers Date 2021-06-04 Time 11:16 Sent To  
Notes
2021-06-04 11:16:36PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 10:00 Rev Time 0.00
Received By rmcphers Date 2021-06-24 Time 10:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-06-04 Cont ID  
Sent By rmcphers Date 2021-06-04 Time 11:14 Rev Time 0.00
Received By rmcphers Date 2021-06-04 Time 10:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-26 Cont ID  
Sent By equinone Date 2021-05-26 Time 09:34 Rev Time 0.00
Received By equinone Date 2021-05-26 Time 08:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-06-16 Time   Rev Time 0.00
Received By bdolan Date 2021-06-16 Time 11:17 Sent To  
Notes
2021-06-16 11:17:32THIS PLAN HAS BEEN REVIEWED AND APPROVED BY THE
 DIVISION OF FIRE PREVENTION WITH THE FOLLOWING
 COMMENTS:
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE ALARM/SPRINKLER
 SYSTEM/EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By bdolan Date 2021-05-21 Time   Rev Time 0.00
Received By bdolan Date 2021-05-20 Time 12:54 Sent To  
Notes
2021-05-21 12:57:00THIS PLAN HAS BEEN REVIEWED AND APPROVED BY THE
 DIVISION OF FIRE PREVENTION WITH THE FOLLOWING
 COMMENTS:
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 ANY AND ALL WORK ON THE FIRE ALARM/SPRINKLER
 SYSTEM/EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 10:02 Rev Time 0.00
Received By rmcphers Date 2021-06-15 Time 13:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-04 Cont ID  
Sent By rmcphers Date 2021-06-04 Time 11:16 Rev Time 0.00
Received By rmcphers Date 2021-05-13 Time 06:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-23 Cont ID  
Sent By medwards Date 2021-06-22 Time 11:52 Rev Time 0.00
Received By medwards Date 2021-06-22 Time 11:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-26 Cont ID  
Sent By medwards Date 2021-05-26 Time 13:35 Rev Time 0.00
Received By medwards Date 2021-05-26 Time 13:35 Sent To  
Notes
2021-05-26 13:35:161ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21050228
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON
 2020 FBC M 403.3.1.1. YOU DO NOT USE THE OCCUPANT COUNT
 GIVEN BY THE A SHEETS. STEP 1: YOU WOULD TAKE THE SQ.
 FT. OF THE SPACE AND DIVIDE BY 1000, TAKE THIS NUMBER
 AND MULTIPLY BY THE NUMBER IN THE (OCCUPANT DENSITY)
 COLUMN, THEN MULTIPLY THAT NUMBER BY THE NUMBER IN THE
 (PEOPLE OUTDOOR AIRFOW RATE IN BREATHING ZONE) COLUMN.
 STEP 2: TAKE THE SQ. FT. OF THE AREA AND MULTIPLY THIS
 BY THE NUMBER IN THE (AREA OUTDOOR AIRFLOW RATE IN
 BREATHING ZONE) COLUMN. LAST STEP IS TO TAKE THE ANSWER
 FROM THE FIRST STEP AND SECOND STEP AND ADD TOGETHER.
 THIS IS THE MINIMUM OUTDOOR AIR RATE FOR THIS SPACE.
 (VENTILATION SYSTEMS SHALL BE DESIGNED TO HAVE THE
 CAPACITY TO SUPPLY THE MINIMUM OUTDOOR AIRFLOW RATE,
 DETERMINED IN ACCORDANCE WITH THIS SECTION. IN EACH
 OCCUPIABLE SPACE, THE VENTILATION SYSTEM SHALL BE
 DESIGNED TO DELIVER THE REQUIRED RATE OF OUTDOOR
 AIRFLOW TO THE BREATHING ZONE. THE OCCUPANT LOAD
 UTILIZED FOR DESIGN OF THE VENTILATION SYSTEM SHALL BE
 NOT LESS THAN THE NUMBER DETERMINED FROM THE ESTIMATED
 MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE
 403.3.1.1.)
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By jesmith Date 2021-06-22 Time 11:46 Rev Time 0.00
Received By jesmith Date 2021-06-17 Time 16:46 Sent To  
Notes
2021-06-22 11:46:2121050228 250 S AUSTRALIAN AVE # 1204
  
 PLUMBING APPROVED
  
 PROVISO:
  
 1. PLAN SHEET P0.1 AND P2.1 SHALL BE REVISED TO REFLECT
 THE RED-LINED COMMENTS ON THOSE PAGES AND ARE NOTED IN
 THIS PROVISO. THE REVISED PLANS SHALL BE SUBMITTED,
 APPROVED AND ON SITE PRIOR TO THE FIRST INSPECTION.
 ...PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATION
 FOR SUMP PUMP DISCHARGE (PRESSURE RATED) PIPING FROM
 PUMP TO CONNECTION WITH SANITARY DRAINAGE
 ...PROVIDE FULL OPEN VALVE ON SUMP PUMP DISCHARGE PER
 FBC PL 712.2
 ?ADD TO KEY NOTE 1, ?WHERE THE DISCHARGE CONNECTS INTO
 HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE
 MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE
 PIPING AND SAID WYE SHALL BE LOCATED NOT LESS THAN 10
 PIPE DIAMETERS FROM THE BASE OF ANY STACK OR FIXTURE
 DRAIN PER FBC PL 712.3.5.?
  
 2.PROJECT SUBMITTAL FOR SUMP PUMP REVIEWED AND APPROVED
 BY ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL
 INSPECTION.
  
 3.PROJECT SUBMITTAL FOR TANKLESS WATER HEATER REVIEWED
 AND APPROVED BY ENGINEER OF RECORD SHALL BE ON SITE
 PRIOR TO FINAL INSPECTION
  
 4.PROJECT SUBMITTAL FOR ASSE 1070 COMPLIANT
 THERMOSTATIC MIXING VALVE REVIEWED AND APPROVED BY
 ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL
 INSPECTION
  
  
  
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-05-20 Cont ID  
Sent By jesmith Date 2021-05-20 Time 10:25 Rev Time 0.00
Received By jesmith Date 2021-05-20 Time 08:18 Sent To  
Notes
2021-05-20 10:17:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 A. ACCESSIBILITY
 1. PROVIDE LOCATION OF THE DRINKING FOUNTAIN; PROVIDE
 ROUTE AND DISTANCE TO SHOW COMPLIANCE WITH FBC PL
 403.5; DRINKING FOUNTAINS SHALL NOT BE REQUIRED TO BE
 LOCATED IN INDIVIDUAL TENANT SPACES PROVIDED THAT
 PUBLIC DRINKING FOUNTAINS ARE LOCATED WITHIN A DISTANCE
 OF TRAVEL OF 500 FEET (152 M) OF THE MOST REMOTE
 LOCATION IN THE TENANT SPACE AND NOT MORE THAN ONE
 STORY ABOVE OR BELOW THE TENANT SPACE.
  
 2. IS THE EXISTING DRINKING FOUNTAIN ACCESSIBLE,
 COMPLYING WITH FBC PL 410.3 AND FBC ACC 602? PLEASE SEE
 FBC ACC 202.4.1 DISPROPORTIONATE COST AND 202.4.2
 ACCESSIBLE FEATURES IN THE EVENT OF DISPROPORTIONALITY,
 (V) ACCESSIBLE DRINKING FOUNTAINS.
  
 B. PLUMBING
 1.PROJECT SUBMITTAL FOR SUMP PUMP REVIEWED AND APPROVED
 BY ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL
 INSPECTION.
  
 2.PROJECT SUBMITTAL FOR TANKLESS WATER HEATER REVIEWED
 AND APPROVED BY ENGINEER OF RECORD SHALL BE ON SITE
 PRIOR TO FINAL INSPECTION
  
 3.PROJECT SUBMITTAL FOR ASSE 1070 COMPLIANT
 THERMOSTATIC MIXING VALVE REVIEWED AND APPROVED BY
 ENGINEER OF RECORD SHALL BE ON SITE PRIOR TO FINAL
 INSPECTION
  
 4.RE: SUMP PUMP:
 4A)PER WPB FBC 107.2.1, DELETE THE WORDS "OR EQUAL"
 FROM P0.1 SANITARY ISOMETRIC AND P2.1 KEY NOTE 3.
 4B)PER FBC PL 909.2, IF THE DRAIN INLET OF THE NOTED
 SUMP PUMP IS BELOW THE WEIR OF THE TRAP, BLOCKING THE
 SOURCE OF AIR FROM THE PUMP VENT, A SEPARATE VENT SHALL
 BE PROVIDED FOR THE FIXTURE DRAIN.
  
 5.PER WPB FBC 107.2.1, DELETE THE WORDS "EQUAL TO" FROM
 P0.1, INSTANTANEOUS WATER HEATER DETAIL
  
 6.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21050228 250 S AUSTRALIAN AVE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By medwards Date 2021-06-22 Time 11:54 Rev Time 0.00
Received By medwards Date 2021-06-22 Time 11:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-04 Cont ID  
Sent By rmcphers Date 2021-06-04 Time 11:16 Rev Time 0.00
Received By rmcphers Date 2021-06-04 Time 11:16 Sent To  
Notes
***NONE***