Plan Review Details - Permit 21050144
Plan Review Stops For Permit 21050144
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-05-15 Cont ID  
Sent By pvalenti Date 2021-05-15 Time 13:28 Rev Time 0.00
Received By pvalenti Date 2021-05-15 Time 13:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By pvalenti Date 2021-05-07 Time 07:35 Rev Time 0.00
Received By pvalenti Date 2021-05-07 Time 07:19 Sent To  
Notes
2021-05-07 07:53:29****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE CORRECT THE SPACING FOR 5/16"
 ANCHORS ON THE SUBMITTED "SCHEDULE FOR INSTALLATION OF
 OPENING PROTECTIVE DEVICES". THE SCHEDULE INDICATES 9"
 O.C. SPACING BUT THE PRODUCT APPROVAL INDICATES 4" O.C.
 SPACING.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-15 Cont ID  
Sent By pvalenti Date 2021-05-15 Time 13:28 Rev Time 0.00
Received By pvalenti Date 2021-05-12 Time 07:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-07 Cont ID  
Sent By pvalenti Date 2021-05-07 Time 07:53 Rev Time 0.00
Received By pvalenti Date 2021-05-06 Time 16:04 Sent To  
Notes
***NONE***