Plan Review Details - Permit 21050047
Plan Review Stops For Permit 21050047
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-18 Cont ID  
Sent By cpuell Date 2021-05-18 Time 10:50 Rev Time 0.00
Received By cpuell Date 2021-05-18 Time 10:50 Sent To  
Notes
2021-05-18 10:53:24HAS A UNITY OF TITLE BEEN APPLIED FOR, IF NOT CONTACT
 VINCE NOEL [email protected], HAVE YOU GIVEN THE UNITY OF
 TITLE TO THE COUNTY PROPERTY APPRAISER AND HAVE THEY
 GIVEN YOU A SINGLE PROPERTY CONTROL NUMBER FOR THE
 SINGLE UNIT? ONCE THESE STEPS HAVE HAPPENED, PLEASE
 CONTACT [email protected] TO BE ASSIGNED AN ADDRESS FOR
 THE SINGLE UNIT, PLEASE LET IF YOU HAVE A PREFERENCE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-23 Cont ID  
Sent By jwitmer Date 2021-05-23 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2021-05-23 Time 13:01 Sent To  
Notes
2021-05-23 13:29:37COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-23 Cont ID  
Sent By jwitmer Date 2021-05-23 Time 14:26 Rev Time 0.00
Received By jwitmer Date 2021-05-23 Time 13:00 Sent To  
Notes
2021-05-23 14:22:24WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21050047
 ADD: 1551 N. FLAGLER DR. UNIT: PH-U1
 CONT: IMPRESS CONSTRUCTION CORP
 TEL: 561-282-7943
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. MAY 23, 2021
 ACTION: DENIED
 1) PLEASE NOTE THE COVERSHEET IS SIGNED BY THE
 CONTRACTOR OF RECORD & LICENSE NUMBER BUT WITHIN THE
 TITLEBLOCK THE PLAN STATES IT WAS THE CONSTRUCTION AND
 ARCHITECTURAL GROUP INC. /SANDRA PUERTA AND AR LICENSE
 NUMBER 95385. FL ADMIN CODE 61G16.003(1) ARCHITECTS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003.
 2) COMMERCIAL ASBESTOS. TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
 3) BOTH THE PERMIT APPLICATION AND PLANS INDICATE UNDER
 THE SCOPE OF THIS PERMIT 2 CONDOMINIUMS ARE TO BE A
 JOINED TO FORM ONE UNIT.
 A UNITY OF TITLE IS REQUIRED AND TO BE RECORDED AT THE
 COURT HOUSE BY THE CITY SURVEYOR VINCE NOEL. THE
 PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL BOUNDARY
 LINES BETWEEN THE LOTS WHICH COMBINE TO FORM 'THE
 SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 4) THE COVER SHEET:
  
 4A) UNDER THE HEADING OF PROPERTY INFORMATION THE PLANS
 ARE DESIGNED UNDER THE 2017 FBC 6TH EDITION OF THE
 FLORIDA BUILDING CODE. PLEASE UPDATE, THE 2020 FBC 7TH
 EDITION OF THE FLORIDA FAMILY OF CODES WAS ADOPTED
 STATEWIDE ON DEC. 31/ 2020.
  
 4B) UNDER THE HEADING FBC. 2020 ASCE 7-10 / EXP. C.
 PLEASE NOTE THE 2020 FBC-BUILDING 7TH EDITION
 REFERENCES ASCE 7-16 PLEASE REVIEW CHAPTER 35. THE
 OTHER ISSUE IS THE EXPOSURE IS STATED AS EXPOSURE C
 WHEN IT SHOULD READ EXPOSURE D. SECTION 1609.4 OF THE
 2020 FBC-BUILDING CODE.
  
 4C) UNDER THE HEADING FBC. 2020 ASCE 7-10 / EXP. C. THE
 HEIGHT OF THE BUILDING IS LISTED AS 12 FEET. PLEASE
 NOTE THIS IS A 15 STORY HIGHRISE CONDOMINIUM. PLEASE
 UPDATE THE PLAN, APPROXIMATELY 150 FEET TALL.
 DISCREPANCY IN THE PLAN.107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4D) UNDER THE HEADING FBC. 2020 ASCE 7-10 / EXP. C. THE
 BUILDING CLASSIFICATION TYPE IS LISTED AS IIIB. PLEASE
 NOTE IN THE 2020 FBC-BUILDING CODE TABLE 504.4 FOR A
 CONDOMINIUM SPRINKLERED LIST THE CONSTRUCTION TYPE AS
 TYPE IA.
  
 4E) UNDER THE HEADING FBC. 2020 ASCE 7-10 / EXP. C. THE
 OCCUPANCY CLASSIFICATION IS LISTED AS RM/ RESIDENTIAL
 M-F. PLEASE REVIEW SECTION 310.4 APARTMENTS/
 CONDOMINIUMS ARE LISTED AS OCCUPANCY TYPE R2 OF THE
 2020 FBC-B CODE.
  
 4F) UNDER THE HEADING DESIGN WIND PRESSURES. THE
 PRESSURES ARE NOT STATED IF THEY ARE IN VULT OR VASD.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 4G) UNDER THE HEADING DESIGN WIND PRESSURES. FOR DOORS
 AND WINDOWS, THE PRESSURES STATED ARE STATED TO BE
 WORST CASE ALL OPENINGS, THAT WOULD CONCLUDE WALL ZONE
 5 THE PRESSURES STATED IN VASD @ 10 SQ. FT. APPROXIMATE
 BUILDING HEIGHT 150, EXPOSURE D. PRESSURES ARE LOW.
 PRESSURES ABOVE 60 FEET ARE TO BE TAKEN FROM ASCE 7-16
 AND FIGURED BY A DESIGN PROFESSIONAL.
  
 4H)) UNDER THE HEADING DESIGN WIND PRESSURES. FOR ROOF
 PRESSURES APPEAR TO BE LOW, THEY ARE NOT STATED IF THEY
 REPRESENT VULT OR VASD. WHAT HEIGHT THEY WERE TAKEN
 ASSUMED 12 FEET ABOVE GRADE AND EXPOSURE C. THE
 BUILDING IS APPROX.. 150 FEET TALL, AND EXPOSURE D.
 PRESSURES ABOVE 60 FEET ARE TO BE TAKEN FROM ASCE 7-16
 AND FIGURED BY A DESIGN PROFESSIONAL.
  
 5) SHEET A-1 CONSTRUCTION PLANS INDICATES A PENETRATION
 THROUGH A COMMON WALL ELEMENT THAT IS OWNED BY THE
 CONDOMINIUM ASSOCIATION. FL. STATUTE 718 FOR
 CONDOMINIUMS WILL REQUIRE A NOTARIZED LETTER FROM
 EITHER THE CONDOMINIUM BOARD OR THE MANAGEMENT COMPANY
 FOR BUILDINGS WITH 100 UNITS OR MORE GIVING PERMISSION
 FOR ALTERATIONS TO THE COMMON AREA PROPERTY.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-19 Cont ID  
Sent By jleahy Date 2021-05-19 Time 10:23 Rev Time 0.00
Received By jleahy Date 2021-05-19 Time 08:05 Sent To  
Notes
2021-05-19 10:34:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC WORK SHOWN. SUBMIT PLANS SHOWING HOW TWO
 INTO ONE UNITS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-05-20 Cont ID  
Sent By pleduc Date 2021-05-20 Time   Rev Time 0.00
Received By pleduc Date 2021-05-20 Time 10:27 Sent To  
Notes
2021-05-20 10:27:55FIRE PROVISO:
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 WITH ANY REMOVAL OF WALLS, ENSURE CODE COMPLIANT
 SPRINKLER HEAD COVERAGE IS MAINTAINED.
  
 ANY REQUIRED FIRE SPRINKLER WORK, INCLUDING DEMO, SHALL
 BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-05-23 Time 14:27 Rev Time 0.00
Received By cdecoeur Date 2021-05-04 Time 09:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-23 Cont ID  
Sent By equinone Date 2021-05-05 Time 08:46 Rev Time 0.00
Received By jwitmer Date 2021-05-05 Time 08:46 Sent To  
Notes
2021-05-23 13:28:32PAPER PLANS WERE SUBMITTED AND UPLOADED TO DIGITAL
 PLANS. NO SIGNATURE IS SHOWN FROM THE DESIGNER OF
 RECORD. PLEASE NOTE THE COVERSHEET IS SIGNED BY THE
 CONTRACTOR OF RECORD & LICENSE NUMBER BUT WITHIN THE
 TITLEBLOCK THE PLAN STATES IT WAS THE CONSTRUCTION AND
 ARCHITECTURAL GROUP INC. /SANDRA PUERTA AND AR LICENSE
 NUMBER 95385. FL ADMIN CODE 61G16.003(1) ARCHITECTS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-13 Cont ID  
Sent By llouie Date 2021-05-13 Time   Rev Time  
Received By llouie Date 2021-05-13 Time   Sent To  
Notes
***NONE***