Plan Review Details - Permit 21050031
Plan Review Stops For Permit 21050031
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-05-10 Cont ID  
Sent By cpuell Date 2021-05-10 Time 08:48 Rev Time 0.00
Received By cpuell Date 2021-05-10 Time 08:48 Sent To  
Notes
2021-05-10 08:48:59WORK TO BE DONE ON SUITE 106, UPDATED PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-14 Cont ID  
Sent By pvalenti Date 2021-07-14 Time 14:35 Rev Time 0.00
Received By pvalenti Date 2021-07-14 Time 14:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-05-11 Cont ID  
Sent By pvalenti Date 2021-05-11 Time 11:26 Rev Time 0.00
Received By pvalenti Date 2021-05-11 Time 07:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-07-13 Cont ID  
Sent By jleahy Date 2021-07-13 Time 14:24 Rev Time 0.00
Received By jleahy Date 2021-07-13 Time 14:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-18 Cont ID  
Sent By jleahy Date 2021-06-18 Time 12:12 Rev Time 0.00
Received By jleahy Date 2021-06-18 Time 12:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-19 Cont ID  
Sent By jleahy Date 2021-05-19 Time 16:12 Rev Time 0.00
Received By jleahy Date 2021-05-19 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-14 Cont ID  
Sent By pvalenti Date 2021-07-14 Time 14:35 Rev Time 0.00
Received By pvalenti Date 2021-07-12 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-30 Cont ID  
Sent By lmarchan Date 2021-06-30 Time 11:34 Rev Time 0.00
Received By lmarchan Date 2021-06-10 Time 16:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-27 Cont ID  
Sent By lmarchan Date 2021-05-27 Time 13:33 Rev Time 0.00
Received By lmarchan Date 2021-05-05 Time 16:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-12 Cont ID  
Sent By pvalenti Date 2021-07-12 Time 13:43 Rev Time 0.00
Received By pvalenti Date 2021-07-12 Time 11:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-18 Cont ID  
Sent By jleahy Date 2021-06-18 Time 12:21 Rev Time 0.00
Received By jleahy Date 2021-06-18 Time 12:21 Sent To  
Notes
2021-06-18 12:21:57PLANS ARE STILL NOT SIGNED JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-11 Cont ID  
Sent By pvalenti Date 2021-05-11 Time 11:26 Rev Time 0.00
Received By pvalenti Date 2021-05-11 Time 07:44 Sent To  
Notes
2021-05-11 11:27:15****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURE REVIEW DENIED:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN MAIL AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 401 CLEMATIS STREET
 P.O.BOX 3147
 WEST PALM BEACH, FL 33402
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES/BUILDING DEPT.
 561 805 6673
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-07-14 Cont ID  
Sent By eschneid Date 2021-07-14 Time 13:46 Rev Time 0.25
Received By eschneid Date 2021-07-14 Time 12:00 Sent To  
Notes
2021-07-14 13:47:10SIGN 1 - FASCIA IDENTITY SIGN
  
 PERMITTED: 101.67 SF
 PROPOSED: 12.6 SF
  
 APPROVED BY ZONING.
  
 SIGNS 4 - CEILING MOUNTED BLADE SIGNS
  
 APPROVED BY ZONING.
  
 SIGN 6 - WINDOW GRAPHICS
  
 APPROVED BY ZONING.
  
 SIGN 7 - WINDOW GRAPHICS
  
 APPROVED BY ZONING.
  
 SIGN 8 - SIGN AT REAR ENTRANCE IS CONSIDERED AN
 UNREGULATED SIGN AND DOES NOT REQUIRE ZONING
 REVIEW/APPROVAL.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-06-30 Cont ID  
Sent By eschneid Date 2021-06-30 Time 09:27 Rev Time 0.50
Received By eschneid Date 2021-06-29 Time 10:56 Sent To  
Notes
2021-06-29 11:13:40FAILED
  
 SIGN 1 - FASCIA IDENTITY SIGN
  
 1) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA FOR STOREFRONT TYPE 1 ONLY ALLOWS A FASCIA
 IDENTITY SIGN TO BE INSTALLED ON A CASE BY CASE BASIS.
 CITYPLACE RETAIL MUST SPECIFICALLY PROVIDE WRITTEN
 APPROVAL OF A WAIVER I TO ALLOW THE CASE BY CASE USE OF
 A FASCIA IDENTITY SIGN AT THIS LOCATION. A WAIVER I
 ALLOWING THE FASCIA IDENTITY SIGN WAS NOT PROVIDED.
  
 2) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA PERMIT A MAXIMUM LETTER HEIGHT OF 18 INCHES
 FOR A FASCIA IDENTITY SIGN UNLESS CITYPLACE RETAIL
 SUBMITS AND IS GRANTED WAIVER II (MINOR PLANNED
 DEVELOPMENT AMENDMENT). THE WAIVER II MAY INCREASE THE
 SIGNS DIMENSION BY UP TO 25 PERCENT, SO THE LETTER
 HEIGHT COULD BE UP TO 22.5 INCHES. THE SIGN LETTERS
 CONTINUE TO SHOW THE LETTERS ABOVE 18 INCHES IN HEIGHT.
 NOTE: THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT THE FULL HEIGHT OF THE LETTERS BE COUNTED FOR THE
 SIGN SIZE, WHICH IN THIS CASE IS THE FULL HEIGHT OF THE
 TALLER OF THE "T" OR THE "L", WHICH CONTINUE TO APPEAR
 THE SAME 24.5 INCHES IN HEIGHT, JUST WITH THE DIMENSION
 TAG REMOVED ON THE RESUBMITTED PLANS. LETTERS 24.5
 INCHES IN HEIGHT EXCEED THE WAIVABLE LETTER HEIGHT BY 2
 INCHES.
  
 3) UPDATED COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA REQUIRE THAT THE SIGN COPY AREA SHALL MAINTAIN
 A MARGIN AT LEAST THREE (3) INCHES FROM ANY EDGE OF THE
 PERCEIVED SIGN AREA. THE DIMENSION ABOVE THE SIGN MUST
 BE MEASURED FROM THE TOP OF THE TALLER OF THE "T" OR
 THE "L".
  
 PERMITTED: 101.67 SF
 PROPOSED: 23.24 SF AS SHOWN, BUT HEIGHT DOES NOT MEET
 ROSEMARY SQUARE SIGN CRITERIA
  
 SIGNS 4 - CEILING MOUNTED BLADE SIGNS
  
 4) REPEAT COMMENT: THE ROSEMARY SQUARE TENANT SIGN
 CRITERIA PERMIT BLADE SIGNS TO BE CONSTRUCTED WITH
 PUSH-THROUGH WHITE ACRYLIC LETTERS WITH HALO
 ILLUMINATION. THE PROPOSED PLANS CALL FOR CLEAR PLEX
 WITH A WHITE TRANSLUCENT VINYL OVERLAY. THIS USE OF
 ALTERNATIVE MATERIALS ON THE SIGN REQUIRES A WAIVER I
 WRITTEN APPROVAL FROM CITYPLACE RETAIL TO BE SUBMITTED
 WITH THE PERMIT.
  
 SIGN 6 - WINDOW GRAPHICS
  
 APPROVED BY ZONING.
  
 SIGN 7 - WINDOW GRAPHICS
  
 APPROVED BY ZONING.
  
 SIGN 8 - SIGN AT REAR ENTRANCE IS CONSIDERED AN
 UNREGULATED SIGN AND DOES NOT REQUIRE ZONING
 REVIEW/APPROVAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-05-27 Cont ID  
Sent By eschneid Date 2021-05-27 Time 10:41 Rev Time 1.50
Received By eschneid Date 2021-05-26 Time 16:54 Sent To  
Notes
2021-05-27 10:42:47FAILED
  
 SIGN 1 - FASCIA IDENTITY SIGN
  
 THE ROSEMARY SQUARE SIGN CRITERIA MEASURES SIGNAGE
 ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT OF SIGNAGE FOR
 EACH ONE LINEAR FOOT OF STORE FRONTAGE. PLEASE PROVIDE
 THE LINEAR FEET OF STORE FRONTAGE. ADDITIONAL COMMENTS
 MAY BE FORTHCOMING ONCE THE LINEAR FRONTAGE DIMENSION
 IS PROVIDED.
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA FOR STOREFRONT
 TYPE 1 ONLY ALLOWS A FASCIA IDENTITY SIGN TO BE
 INSTALLED ON A CASE BY CASE BASIS. CITYPLACE RETAIL
 MUST SPECIFICALLY PROVIDE WRITTEN APPROVAL OF A WAIVER
 I TO ALLOW THE CASE BY CASE USE OF A FASCIA IDENTITY
 SIGN AT THIS LOCATION. A WAIVER I ALLOWING THE FASCIA
 IDENTITY SIGN WAS NOT PROVIDED.
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT A
 MAXIMUM LETTER HEIGHT OF 18 INCHES FOR A FASCIA
 IDENTITY SIGN UNLESS CITYPLACE RETAIL SUBMITS AND IS
 GRANTED WAIVER II (MINOR PLANNED DEVELOPMENT
 AMENDMENT). THE WAIVER II MAY INCREASE THE SIGNS
 DIMENSION BY UP TO 25 PERCENT, SO THE LETTER HEIGHT
 COULD BE UP TO 22.5 INCHES. THE SIGN LETTERS ARE SHOWN
 AT 24.5 INCHES IN HEIGHT, WHICH EXCEEDS THE WAIVABLE
 LETTER HEIGHT BY 2 INCHES.
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THAT
 THE SIGN COPY AREA SHALL MAINTAIN A MARGIN AT LEAST
 THREE (3) INCHES FROM ANY EDGE OF THE PERCEIVED SIGN
 AREA. PROVIDE THE DIMENSION ABOVE AND BELOW THE SIGN
 TEXT THAT VERIFIES THE THREE-INCH MARGIN (EQ IS NOT
 ACCEPTABLE).
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT A
 FASCIA IDENTITY SIGN TO BE A MAXIMUM OF 16 FEET FROM
 FINISHED FLOOR GRADE. PLEASE PROVIDE A CLEAR DIMENSION
 LINE SHOWING THAT THIS CRITERIA IS MET.
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THE
 STUD MOUNTS TO BE SERIES 316 STAINLESS STEEL ANCHOR
 BOLTS. PROVIDE VERIFICATION OF THIS REQUIREMENT ON THE
 PLANS.
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE ALL
 CONDUIT, RACEWAYS, WIRING, BALLAST BOXES, TRANSFORMERS,
 JUNCTION BOXES, BELL BOXES, POWER SUPPLY AND OTHER
 EQUIPMENT NECESSARY FOR SIGN CONNECTION SHALL BE
 CONCEALED AND NOT VISIBLE TO THE PUBLIC. THE PERMIT
 DRAWINGS NEED TO PROVIDE DETAILED DRAWINGS VERIFYING
 THAT ALL THE ELECTRICAL COMPONENTS FOR THE SIGN,
 INCLUDING THE POWER SUPPLY AND THE COMPONENTS TO GET
 THE POWER TO THE SIGN ARE CONCEALED. A NOTE SAYING THAT
 THEY WILL BE CONCEALED OR THAT THE ELECTRIC IS BY
 OTHERS IS NOT ACCEPTABLE AND WILL RESULT IN THE SIGN
 PERMIT NOT PASSING ZONING. THE DRAWING ON PAGE 7
 STATING "REMOTE LED POWER SUPPLY" IS NOT ACCEPTABLE.
  
 PERMITTED: UNKNOWN
 PROPOSED: UNKNOWN
  
 SIGNS 4 & 5 - CEILING MOUNTED BLADE SIGNS
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA ONLY PERMIT A
 STORE TO HAVE ONE BLADE SIGN UNLESS IT IS A CORNER
 LOCATION. THE WEST ELM SPACE IS NOT A CORNER LOCATION,
 SO YOU MAY ONLY INSTALL ONE BLADE SIGN. THE ROSEMARY
 SQUARE TENANT SIGN CRITERIA DO NOT PERMIT A WAIVER OF
 THE NUMBER OF BLADE SIGNS.
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRES THAT
 SUSPENDED BLADE SIGN PANELS SHALL BE CENTERED IN THE
 ARCADE CEILING. PROVIDE A DRAWING THAT VERIFIES THIS
 CRITERIA.
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT BLADE
 SIGNS TO BE CONSTRUCTED WITH PUSH-THROUGH WHITE ACRYLIC
 LETTERS WITH HALO ILLUMINATION. THE PROPOSED PLANS CALL
 FOR CLEAR PLEX WITH A WHITE TRANSLUCENT VINYL OVERLAY.
 THIS USE OF ALTERNATIVE MATERIALS ON THE SIGN REQUIRES
 A WAIVER I WRITTEN APPROVAL FROM CITYPLACE RETAIL TO BE
 SUBMITTED WITH THE PERMIT.
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE ALL
 CONDUIT, RACEWAYS, WIRING, BALLAST BOXES, TRANSFORMERS,
 JUNCTION BOXES, BELL BOXES, POWER SUPPLY AND OTHER
 EQUIPMENT NECESSARY FOR SIGN CONNECTION SHALL BE
 CONCEALED AND NOT VISIBLE TO THE PUBLIC. THE PERMIT
 DRAWINGS NEED TO PROVIDE DETAILED DRAWINGS VERIFYING
 THAT ALL THE ELECTRICAL COMPONENTS FOR THE SIGN,
 INCLUDING THE COMPONENTS TO GET THE POWER TO THE SIGN
 ARE CONCEALED. A NOTE SAYING THAT THEY WILL BE
 CONCEALED OR THAT THE ELECTRIC IS BY OTHERS IS NOT
 ACCEPTABLE AND WILL RESULT IN THE SIGN PERMIT NOT
 PASSING ZONING.
  
 SIGN 6 - WINDOW GRAPHICS
  
 APPROVED BY ZONING.
  
 SIGN 7 - WINDOW GRAPHICS
  
 THE ROSEMARY SQUARE TENANT SIGN CRITERIA LIMITS THE
 SIGN COPY TO TRADE NAMES ONLY. THE SLOGAN "SHARE YOUR
 STYLE" REQUIRES A WAIVER I WRITTEN APPROVAL FROM
 CITYPLACE RETAIL TO BE SUBMITTED WITH THE PERMIT.
  
 SIGN 8 - SIGN AT REAR ENTRANCE IS CONSIDERED AN
 UNREGULATED SIGN AND DOES NOT REQUIRE ZONING
 REVIEW/APPROVAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  