Plan Review Details - Permit 21041657
Plan Review Stops For Permit 21041657
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-14 Cont ID  
Sent By jbrooks Date 2021-06-14 Time 14:36 Rev Time 0.00
Received By jbrooks Date 2021-06-14 Time 13:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-10 Cont ID  
Sent By jbrooks Date 2021-06-10 Time 12:09 Rev Time 0.00
Received By jbrooks Date 2021-06-10 Time 07:44 Sent To  
Notes
2021-06-10 12:09:29JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R7 SELECTED SYSTEM NO W-5; EXPOSURE
 (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (20 < H < 30);
 ULTIMATE WIND SPEED (160), IS NOT CORRECT. THE ULTIMATE
 WIND SPEED FOR THE LISTED ADDRESS IS 170 (MPH). PLEASE
 SELECT THE CORRECT OPTIONS; CONSIDER USING FL16709-R8
 SYSTEM NO. W-5; EXPOSURE C; ENCLOSED; 20 < H < 30; 170
 (MPH).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-28 Cont ID  
Sent By jbrooks Date 2021-05-28 Time 10:26 Rev Time 0.00
Received By jbrooks Date 2021-05-28 Time 07:39 Sent To  
Notes
2021-05-28 10:27:15JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R7 SELECTED OPTION FOR SYSTEM NO W-5;
 EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (20
 < 30); ULTIMATE WIND SPEED (180). ZONE 3 IS MARKED
 ?N/A? WHICH INDICATES SYSTEM CANNOT BE USED WITHIN THE
 PRESSURE ZONE. PLEASE SELECT THE CORRECT OPTIONS.
 2. WPB A 109.3 BUILDING PERMIT VALUATIONS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS.
 VALUE TO INCLUDE LABOR AND MATERIALS, ARCHITECTURAL AND
 DESIGN FEES, OVERHEAD AND PROFIT.
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2021-05-27 Cont ID  
Sent By jgomez Date 2021-05-27 Time 14:39 Rev Time 0.00
Received By jgomez Date 2021-05-27 Time 14:39 Sent To  
Notes
2021-05-27 14:40:13FLAT ROOF ONLY. JG

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-14 Cont ID  
Sent By jbrooks Date 2021-06-14 Time 14:36 Rev Time 0.00
Received By jbrooks Date 2021-06-11 Time 09:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-10 Cont ID  
Sent By jbrooks Date 2021-06-10 Time 12:09 Rev Time 0.00
Received By jbrooks Date 2021-06-03 Time 14:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-28 Cont ID  
Sent By jbrooks Date 2021-05-28 Time 10:26 Rev Time 0.00
Received By jbrooks Date 2021-05-27 Time 14:27 Sent To  
Notes
***NONE***