Plan Review Details - Permit 21041618
Plan Review Stops For Permit 21041618
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2021-06-24 Time 10:12 Rev Time 0.00
Received By jwitmer Date 2021-06-24 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-23 Cont ID  
Sent By jwitmer Date 2021-05-23 Time 17:13 Rev Time 0.00
Received By jwitmer Date 2021-05-23 Time 16:45 Sent To  
Notes
2021-05-23 17:13:17WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 21041618
 W. P. B. PERMIT: 20071234
 ADD: 3950 GEORGIA AVE.
 CONT: BUILTMORE CONTRACTING
 TEL: 561-331-1476
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
  
  
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 2ND REVIEW
 DATE: SUN. MAY 23RD/ 2021
 ACTION: DENIED
  
 1) 2ND REVIEW. THIS REVISION # 3 ON SHEET 1 OF 3
 INDICATES THE BUILDING CONSTRUCTION TYPE IS TYPE II-B
 CONSTRUCTION NO WOOD FRAMING FOR THE BUILDING AND ROOF
 FRAMING MEMBERS. THE REVISION INDICATES THE USE OF 2 X4
 WOOD FRAMING MEMBERS. PLEASE REVIEW IN THE 2017 FBC-B
 SECTION 603.1. REQUIRES FIRE RETARDANT TREATED WOOD
 THROUGH OUT THE WALL FRAMING, SHEATHING WALL & ROOF AS
 WELL AS EITHER TRUSSES OR WOOD RAFTERS.
 1ST REVIEW. THIS REVISION # 3 ON SHEET 1 OF 3 INDICATES
 THE BUILDING CONSTRUCTION TYPE IS TYPE II CONSTRUCTION
 NO WOOD FRAMING FOR THE BUILDING AND ROOF FRAMING
 MEMBERS. THE REVISION INDICATES THE USE OF 2 X4 WOOD
 FRAMING MEMBERS. PLEASE REVIEW IN THE 2017 FBC-B
 SECTION 603.1.
  
 2A) COMPLIED.
  
 2B) 2ND REQUEST NO INSTLATION KEEY NOR SCHEDULE. STORM
 SHUTTERS. PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.2.
  
 FL BLD CODE 2010 SECTION 107.2.5., 1609.1.2, 1715.8 &
 EXIST BUILD CODE 706.4 PROCEDURES: A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC.
  
 2C) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-13 Cont ID  
Sent By jwitmer Date 2021-05-13 Time 11:14 Rev Time 0.00
Received By jwitmer Date 2021-05-13 Time 09:58 Sent To  
Notes
2021-05-13 11:14:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 21041618
 W. P. B. PERMIT: 20071234
 ADD: 3950 GEORGIA AVE.
 CONT: BUILTMORE CONTRACTING
 TEL: 561-331-1476
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAY 13TH/ 2021
 ACTION: DENIED
  
 1) THIS REVISION # 3 ON SHEET 1 OF 3 INDICATES THE
 BUILDING CONSTRUCTION TYPE IS TYPE II CONSTRUCTION NO
 WOOD FRAMING FOR THE BUILDING AND ROOF FRAMING MEMBERS.
 THE REVISION INDICATES THE USE OF 2 X4 WOOD FRAMING
 MEMBERS. PLEASE REVIEW IN THE 2017 FBC-B SECTION 603.1.
  
 2A) THE LETTER INFORMS THE BUILDING DEPARTMENT THAT THE
 EXISTING WINDOWS ARE NOT IMPACT RESISTANT TESTED AND
 WILL APPLY AN APPROVED SHUTTER PANEL SYSTEM OVER THE
 EXISTING WINDOWS. SUBMITTED IN THIS REVISION PACKAGE A
 PRODUCT EVALUATION REPORT FOR 24 GAGE BERTH GALVANIZED
 STEEL STORM SHUTTERS AND 10-PAGE TECHNICAL DRAWINGS BUT
 NEITHER THE REPORT OR TECHNICAL DRAWINGS SHOW EITHER A
 FLORIDA APPROVAL OR MIAMI-DADE NOA NUMBER. THIS REPORT
 DOES NOT SHOW THEY HAVE A 3RD PARTY CERTIFICATION
 PROGRAM.
 COMPONENTS & CLADDING
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)( E ) STORM SHUTTERS
  
 2B) STORM SHUTTERS. PROVIDE STORM PANEL INFORMATION
 WITH INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.2.
  
 FL BLD CODE 2010 SECTION 107.2.5., 1609.1.2, 1715.8 &
 EXIST BUILD CODE 706.4 PROCEDURES: A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC.
  
 2C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By pleduc Date 2021-06-22 Time   Rev Time 0.00
Received By pleduc Date 2021-06-22 Time 10:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-05-07 Cont ID  
Sent By pleduc Date 2021-05-07 Time   Rev Time 0.00
Received By pleduc Date 2021-05-07 Time 14:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-06-24 Time 10:12 Rev Time 0.00
Received By aoliver Date 2021-06-21 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-23 Cont ID  
Sent By jwitmer Date 2021-05-23 Time 17:13 Rev Time 0.00
Received By jwitmer Date 2021-05-19 Time 06:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-13 Cont ID  
Sent By jwitmer Date 2021-05-13 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2021-05-06 Time 12:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-06-24 Time 10:12 Rev Time 0.00
Received By jwitmer Date 2021-06-24 Time 09:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-13 Cont ID  
Sent By jwitmer Date 2021-05-13 Time 11:14 Rev Time 0.00
Received By jwitmer Date 2021-05-13 Time 09:58 Sent To  
Notes
***NONE***