Plan Review Details - Permit 21041507
Plan Review Stops For Permit 21041507
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-15 Cont ID  
Sent By rmcdouga Date 2021-07-15 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2021-07-15 Time 10:50 Sent To  
Notes
2021-07-15 10:51:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC SIXTH
 EDITION (2017). THE FBC SEVENTH EDITION (2020) WENT
 INTO EFFECT ON DECEMBER 31, 2020. ALL NEW PERMITS
 APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED TO
 COMPLY WITH AND REFERENCE THE 2020 FBC SEVENTH EDITION.
 FS CHAPTER 553
  
 2) THE ENGINEERING ON THE PLANS REFERENCE ASCE 7 - 10
 AND THE CURRENT CODE REFERENCES ASCE 7-16. PLEASE
 CORRECT. 2020 FBC CHAPTER 35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-15 Cont ID  
Sent By rmcdouga Date 2021-07-15 Time 10:51 Rev Time 0.00
Received By rmcdouga Date 2021-06-14 Time 10:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-15 Cont ID  
Sent By rmcdouga Date 2021-07-15 Time 10:51 Rev Time 0.00
Received By rmcdouga Date 2021-07-15 Time 10:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By llouie Date 2021-06-29 Time   Rev Time  
Received By llouie Date 2021-06-29 Time   Sent To  
Notes
2021-06-29 14:47:53** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE EXISTING BUILDING APPEARS TO BE A MULTI-TENANT
 BUILDING. PER THE SIGN CODE OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), ONLY ONE SIGN IS
 PERMITTED PER TENANT/BUSINESS. THE PLANS INDICATE THAT
 THERE MAY MULTIPLE SIGNS PROPOSED FOR THE PERMIT. [ZLDR
 S.94-408(D)]
  
 2.) IT IS NOT CLEAR WHAT THE OVERALL SITE PLAN SHEET IS
 DEPICTING, AS THERE IS NO LEGEND IDENTIFYING THE
 REFERENCES IN THE SITE PLAN.
  
 3.) BUILDING FACADE DIMENSIONS ARE REQUIRED FOR THE
 TENANT SPACE TO CALCULATE THE MAXIMUM ALLOWABLE SIGN
 AREA. [ZLDR S.94-409].
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: NORTHPOINT CPD
  