2021-06-01 09:52:18 | 06/01/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.1 GENERAL. |
| |
| 3. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR ALL |
| GAS EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC RES. |
| SEC. G2408.1. |
| |
| 4. THIS TANK-LESS UNIT MAY CALL FOR A 10.5" WATER |
| COLUMN, AND THE SERVICE METER DISCHARGES IS A 12" WATER |
| COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURERES |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| SEC. G2421.1. |
| |
| 5. SUBMIT MANUFACTURERES SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| |
| 6. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| G2413. |
| |
| 7. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020 |
| FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS). |
| |
| 8. SUPPOSE LOUVERS ARE BEING INSTALLED FOR THE |
| COMBUSTION AIR AND SHOW LOCATION. THE LOUVERS CANNOT BE |
| LOCATED ON AN EXTERIOR WALL THAT IS FIRE RATED AS THE |
| FIRE RATING OF THE WALL MUST BE MAINTAINED PER THE WPB |
| AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 9. PLEASE SUBMIT A HOUSE PLAN SHOWING THE LOCATION OF |
| THE TANK-LESS WATER HEATER AND THE LOCATION AND |
| DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 10. ALL GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE INSPECTION TIME PER THE 2020 FBC |
| RES. SEC. G2413.2 AND G2404.3. |
| PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF REGULATOR |
| 1" OF EITHER SIDE PER THE 2020 FBC RES. SEC G2421.2. |
| |
| 11. SHOW AND LABEL DRIP LEG ON EQUIPMENT INSTALLED, |
| EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD GRILLS PER |
| THE 2020 FBC RES. SEC. G2419.2. |
| |
| 12. IF PIPES NOT IN CONDITION, SPACE NEEDS TO BE |
| INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| 403.5.3. PUT A NOTE ON PLANS. |
| |
| 13. SOME TANK-LESS UNITS REQUIRED CONDENSATE, AND THEY |
| NEED TO BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC |
| SEC. R318.5. PUT A NOTE ON PLANS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |