Plan Review Details - Permit 21041429
Plan Review Stops For Permit 21041429
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2021-06-01 Cont ID  
Sent By scwelter Date 2021-06-01 Time 15:21 Rev Time 0.00
Received By scwelter Date 2021-06-01 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 15:11 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 15:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 12:50 Rev Time 0.00
Received By rmcphers Date 2021-06-29 Time 10:59 Sent To  
Notes
2021-06-29 11:34:56UTILITY BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE ROOF SHEATHING ATTACHMENT (NAILING
 SIZE AND TYPE) FBC 2304.10.1
 2) PRODUCT APPROVAL PROVIDED FOR THE SKY LIGHT DOES NOT
 MEET THE REQUIRED WIND DESIGN PRESSURES SHOWN ON
 DRAWING A-3.
 3) PRODUCT APPROVAL PROVIDED FOR THE SWING DOOR DOES
 NOT MEET THE REQUIRED WIND DESIGN PRESSURES SHOWN ON
 DRAWING A-3.
 4) PRODUCT APPROVAL PROVIDED FOR THE OVERHEAD DOOR DOES
 NOT MEET THE REQUIRED WIND DESIGN PRESSURES SHOWN ON
 DRAWING A-3.
 5) THE INSTALLATION DRAWINGS FOR THE SWING DOOR
 (DRAWING NUMBER D015726) IS NOT PART OF THE PRODUCT
 APPROVAL (FRONT PAGE PROVIDED FL16708 R13) - PLEASE
 PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE SWING DOOR.
 6) PRODUCT APPROVAL (FL14672-R6) FOR THE FLAT DECK
 ROOFING = NEED TO CHOOSE A ROOFING SYSTEM IN THE
 PRODUCT APPROVAL INSTALLATION INSTRUCTIONS THAT SHOWS
 THE REQUIRED WIND DESIGN PRESSURE AS SHOWN ON DRAWING
 (A-3) - PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN
 THE PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE
 ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR
 ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A
 HIGHER WIND PRESSURE THEN THE CHOSEN ROOFING SYSTEM -
 SEE NOTES ON THE PRODUCT APPROVAL.
 7) PLEASE PROVIDE A PRODUCT APPROVAL FOR THE WINDOWS,
 LOUVERS OR SHUTTERS - DRAWINGS NEED TO SAY WHETHER THE
 SIDE OPENINGS ARE WINDOWS, LOUVERS OR SHUTTERS.
 8) ROOFING SYSTEM AND WINDOW AND DOOR PRODUCT APPROVALS
 MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE
 DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-18 Cont ID  
Sent By rmcphers Date 2021-05-18 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2021-05-18 Time 07:38 Sent To  
Notes
2021-05-18 08:14:10UTILITY BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ROOF SHEATHING TYPE, SIZE, AND
 ATTACHMENTS FBC 2304.8
 2) PLEASE PROVIDE COMPLETE COPIES (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) OF THE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVALS FOR THE SWING DOOR, ROLLUP
 DOOR, WINDOW, SKY LIGHT AND ROOFING SYSTEM.
 3) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR SHOWN BY
 PRODUCT APPROVAL NUMBER ON THE DRAWINGS. FBC 107.3.4
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-29 Cont ID  
Sent By jleahy Date 2021-06-29 Time 11:57 Rev Time 0.00
Received By jleahy Date 2021-06-29 Time 11:57 Sent To  
Notes
2021-06-29 11:57:53SEE PERMIT 21050466 FOR THE SERVICE TO THIS BUILDING
 JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-06-28 Cont ID  
Sent By jleahy Date 2021-06-28 Time 11:31 Rev Time 0.00
Received By jleahy Date 2021-06-28 Time 11:31 Sent To  
Notes
2021-06-28 11:31:59SEE REVIEW NOTES FROM 5/18 REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-18 Cont ID  
Sent By jleahy Date 2021-05-18 Time 07:32 Rev Time 0.00
Received By jleahy Date 2021-05-18 Time 06:59 Sent To  
Notes
2021-05-18 07:32:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 BUILDINGS WITH MORE THAN ONE CIRCUIT NEED A PANEL
 INSTALLED AND A GROUNDING ELECRODE SYSTEM, 225.30,
 250.32
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S). (A) GROUNDING ELECTRODE.
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH
 PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN
 250.50 SHALL BE INSTALLED.
  
 225.30 NUMBER OF SUPPLIES. A BUILDING OR OTHER
 STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR FEEDER
 ON THE LOAD SIDE OF A SERVICE DISCONNECTING MEANS SHALL
 BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS
 PERMITTED IN 225.30(A) THROUGH (E). FOR THE PURPOSE OF
 THIS SECTION, A MULTIWIRE BRANCH CIRCUIT SHALL BE
 CONSIDERED A SINGLE CIRCUIT.
  
 PLEASE SUBMIT A RISER DIAGRM SHOWING THE LOCATION OF
 THE SERVICE. 215.5

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-05-18 Cont ID  
Sent By rrossano Date 2021-05-18 Time   Rev Time 0.00
Received By rrossano Date 2021-05-18 Time   Sent To  
Notes
2021-05-18 10:27:35 
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-05-18 Cont ID  
Sent By cwalker Date 2021-05-18 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 15:13 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 08:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 12:51 Rev Time 0.00
Received By rmcphers Date 2021-06-11 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-25 Cont ID  
Sent By lcrespo Date 2021-05-25 Time 16:20 Rev Time 0.00
Received By lcrespo Date 2021-05-05 Time 17:06 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-05-18 Cont ID  
Sent By rmcphers Date 2021-05-18 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2021-05-18 Time 10:33 Sent To  
Notes
2021-05-18 10:34:54UTILITY BUILDING - NO AC SPACE

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 15:11 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 15:11 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 12:50 Rev Time 0.00
Received By rmcphers Date 2021-06-29 Time 12:50 Sent To  
Notes
2021-06-29 12:51:11SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-05-18 Cont ID  
Sent By rmcphers Date 2021-05-18 Time 10:35 Rev Time 0.00
Received By rmcphers Date 2021-05-18 Time 10:35 Sent To  
Notes
2021-05-18 10:35:35SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 15:11 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 15:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 12:50 Rev Time 0.00
Received By rmcphers Date 2021-06-29 Time 12:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-18 Cont ID  
Sent By rmcphers Date 2021-05-18 Time 10:39 Rev Time 0.00
Received By rmcphers Date 2021-05-18 Time 10:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-24 Cont ID  
Sent By awooten Date 2021-05-24 Time   Rev Time 0.00
Received By awooten Date 2021-05-24 Time   Sent To  
Notes
***NONE***