Plan Review Details - Permit 21041388
Plan Review Stops For Permit 21041388
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-08-04 Cont ID  
Sent By pvalenti Date 2021-08-04 Time 06:20 Rev Time 0.00
Received By pvalenti Date 2021-08-04 Time 06:16 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-29 Cont ID  
Sent By pvalenti Date 2021-04-29 Time 10:30 Rev Time 0.00
Received By pvalenti Date 2021-04-29 Time 09:30 Sent To  
Notes
2021-04-29 10:31:31ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-08-19 Cont ID  
Sent By pvalenti Date 2021-08-19 Time 09:59 Rev Time 0.00
Received By pvalenti Date 2021-08-19 Time 09:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-04 Cont ID  
Sent By pvalenti Date 2021-08-04 Time 06:37 Rev Time 0.00
Received By pvalenti Date 2021-08-04 Time 06:17 Sent To  
Notes
2021-08-04 06:53:09PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 1. UTILITY RELEASE ? FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION.
  
 (CITY RESPONSE: PLEASE PROVIDE THE FPL RELEASE ON THE
 FPL LETTERHEAD RELEASE FORM.)
  
  
 3. UTILITY RELEASE ? CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT?SERVICES/FORMS/B
 UILDING?PERMIT?FORMS
  
 IF A WATER TRUCK IS DESIRED FOR WATERING DOWN SITE,
 DETAILS WILL BE REQUIRED.
  
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
 IF A BACKFLOW PREVENTER DEVICE HAS BEEN SELECTED FOR
 THE WATER DOWN METHOD AND A PERMIT HAS BEEN OBTAINED ?
 BEFORE SCHEDULING THE FINAL INSPECTION, THE BACKFLOW
 DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S
 UTILITIES DEPT, 561?822?2244.
  
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561?822?2183.
  
 (CITY RESPONSE: PLEASE PROVIDE THE PUBLIC UTILITIES
 DEMOLITION APPLICATION THAT HAS BEEN COMPLETED AND
 RETURNED BY THE PUBLIC UTILITIES DEPARTMENT AND PROVIDE
 THE PUBLIC UTILITIES DEPARTMENT UPDATED APPROVAL FOR
 THE EXISTING BACKFLOW PREVENTER DEVICE.)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-29 Cont ID  
Sent By pvalenti Date 2021-04-29 Time 10:32 Rev Time 0.00
Received By pvalenti Date 2021-04-29 Time 09:30 Sent To  
Notes
2021-04-29 11:17:45PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION"
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF A WATER TRUCK IS DESIRED FOR WATERING DOWN SITE,
 DETAILS WILL BE REQUIRED.
  
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
 IF A BACKFLOW PREVENTER DEVICE HAS BEEN SELECTED FOR
 THE WATER DOWN METHOD AND A PERMIT HAS BEEN OBTAINED -
 BEFORE SCHEDULING THE FINAL INSPECTION, THE BACKFLOW
 DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S
 UTILITIES DEPT, 561-822-2244.
  
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL
 PLUMBING #703.
  
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT DEMOLITION ADDRESS HAS
 BEEN INSPECTED AND/OR TREATED FOR RODENTS.
  
 6. COMPLETE THE DEMO DEBRIS REMOVAL FORM:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
  
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED, FBC 107.
  
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
  
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2021-08-04 Cont ID  
Sent By rrossano Date 2021-08-04 Time   Rev Time 0.00
Received By mgonzale Date 2021-08-04 Time   Sent To  
Notes
2021-08-04 12:19:38PLEASE ADDRESS BUILDING COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By rrossano Date 2021-05-12 Time   Rev Time  
Received By rrossano Date 2021-05-12 Time   Sent To I
Notes
2021-05-12 16:19:44PLEASE ADDRESS BUILDING COMMENTS.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-08-06 Cont ID  
Sent By fmittner Date 2021-08-06 Time 15:17 Rev Time 0.00
Received By fmittner Date 2021-08-06 Time 15:17 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-05-03 Cont ID  
Sent By aborngra Date 2021-05-03 Time 15:42 Rev Time 0.00
Received By aborngra Date 2021-05-03 Time 15:41 Sent To  
Notes
2021-05-03 15:42:03REMOVAL OF TREES MAY REQUIRE A TREE ALTERATION PERMIT -
 AB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-19 Cont ID  
Sent By pvalenti Date 2021-08-19 Time 10:05 Rev Time 0.00
Received By pvalenti Date 2021-08-16 Time 10:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-09 Cont ID  
Sent By pvalenti Date 2021-08-09 Time 08:02 Rev Time 0.00
Received By pvalenti Date 2021-07-30 Time 08:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 15:19 Rev Time 0.00
Received By jleahy Date 2021-04-26 Time 10:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-19 Cont ID  
Sent By pvalenti Date 2021-08-19 Time 10:05 Rev Time 0.00
Received By pvalenti Date 2021-08-19 Time 10:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-04 Cont ID  
Sent By pvalenti Date 2021-08-04 Time 06:56 Rev Time 0.00
Received By pvalenti Date 2021-08-04 Time 06:17 Sent To  
Notes
2021-08-04 06:57:03SIGNATURE REVIEW DENIED:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD/EMAIL A DIGITALLY SIGNED (THIRD PARTY VERIFIED)
 PLAN OR YOU CAN MAIL/HAND DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 401 CLEMATIS STREET
 P.O. BOX 3147
 WEST PALM BEACH, FL 33402
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES/BUILDING DEPT.
 561 805 6673
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-29 Cont ID  
Sent By pvalenti Date 2021-04-29 Time 11:23 Rev Time 0.00
Received By pvalenti Date 2021-04-29 Time 11:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-05-03 Cont ID  
Sent By aborngra Date 2021-05-03 Time 15:41 Rev Time 0.00
Received By aborngra Date 2021-05-03 Time 15:40 Sent To  
Notes
***NONE***