Plan Review Stops For Permit 21041199 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2021-05-27 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-05-27 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-05-27 |
Time |
13:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-05-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-05-10 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-05-10 |
Time |
16:06 |
Sent To |
|
|
Notes |
2021-05-10 16:08:40 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) IT APPEARS THAT SHEET 1 OF 3 IS MISSING FROM THE | | PLANS. ONLY SHEETS 2 OF 3 AND 3 OF 3 WERE UPLOADED. | | PLEASE SUBMIT THE MISSING SHEET 1 OF 3. FBC AMENDMENTS | | 107.2.1 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-05-04 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2021-05-04 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2021-05-04 |
Time |
08:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2021-04-26 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-04-26 |
Time |
17:22 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-04-26 |
Time |
17:22 |
Sent To |
|
|
Notes |
2021-04-26 17:23:30 | GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN | | THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN | | PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS | | WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE | | RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT | | REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | | A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR | | FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC | | SEC. 105.1. | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2021-05-06 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2021-05-06 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2021-05-06 |
Time |
15:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-05-27 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-05-27 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-05-13 |
Time |
09:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-05-11 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-05-11 |
Time |
17:17 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-04-23 |
Time |
13:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-05-20 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-05-20 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-05-20 |
Time |
10:07 |
Sent To |
|
|
Notes |
2021-05-20 10:07:39 | 05/20/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2021-04-26 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-04-26 |
Time |
17:20 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-04-26 |
Time |
17:12 |
Sent To |
|
|
Notes |
2021-04-26 17:20:35 | 04/26/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-05-27 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-05-27 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-05-27 |
Time |
13:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-05-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-05-10 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-05-10 |
Time |
16:08 |
Sent To |
|
|
Notes |
2021-05-10 16:09:54 | THE ENGINEER'S SIGNATURE ON THE MISSING PLAN SHEET WILL | | HAVE TO BE REVIEWED. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2021-05-06 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2021-05-06 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2021-05-06 |
Time |
15:13 |
Sent To |
|
|
Notes |
2021-05-06 15:14:13 | EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR | | SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS | | BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE | | RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | HEIGHT ABOVE GRADE. | | | | ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH A | | BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING | | GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES | | PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. AT | | LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN | | ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH | | AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL | | BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A | | 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE, | | AT THE PROPERTY LINE, TO ENSURE PRIVACY. | | | | IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT TO OR | | SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN AWAY | | FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES. | | | | AARON BORNGRABER, AICP | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|