Plan Review Details - Permit 21041148
Plan Review Stops For Permit 21041148
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 16:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-28 Cont ID  
Sent By rmcdouga Date 2021-05-28 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2021-05-28 Time 10:01 Sent To  
Notes
2021-05-28 10:15:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A GENERATOR PAD PLAN WITH GENERATOR TO PAD
 ANCHORING DETAILS. IF YOU ARE USING A PREFABRICATED
 GENERATOR PAD SUBMIT THE SIGNED AND SEALED SITE
 SPECIFIC ENGINEERING FOR IT. SPECIFY THE WIND LOAD DATA
 ON THE DRAWING. FBC 107.2.1
  
 2) SEE SIGNATURE REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-19 Cont ID  
Sent By fgiaquin Date 2021-05-19 Time 21:25 Rev Time 0.00
Received By fgiaquin Date 2021-05-18 Time 21:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:44 Rev Time 0.00
Received By rmcdouga Date 2021-06-15 Time 09:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-11 Cont ID  
Sent By jleahy Date 2021-06-11 Time 15:50 Rev Time 0.00
Received By jleahy Date 2021-05-04 Time 14:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 16:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-28 Cont ID  
Sent By rmcdouga Date 2021-05-28 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2021-05-28 Time 10:01 Sent To  
Notes
2021-05-28 10:17:12THE SITE SPECIFIC ENGINEERING IS REQUIRED OT HAVE THE
 ENGINEER'S SIGNATURE. ELECTRONICALLY SUBMITTED DRAWINGS
 ARE REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO
 BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF
 THE SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 &
 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-09 Cont ID  
Sent By kalexand Date 2021-06-09 Time 09:31 Rev Time 0.00
Received By kalexand Date 2021-06-09 Time 09:31 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved