Plan Review Details - Permit 21041147
Plan Review Stops For Permit 21041147
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:38 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 16:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-28 Cont ID  
Sent By rmcdouga Date 2021-05-28 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2021-05-28 Time 10:25 Sent To  
Notes
2021-05-28 10:30:49PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A GENERATOR PAD DRAWING THAT SPECIFIES HOW
 THE GENERATOR IS ANCHORED TO RESIST WIND LOADS. IF YOU
 ARE USING A PREFABRICATED GENERATOR PAD SUBMIT THE
 SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR IT.
 SPECIFY THE WIND LOAD DATA ON THE DRAWING. FBC 107.2.1
  
 2) SEE SIGNATURE REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-18 Cont ID  
Sent By fgiaquin Date 2021-05-18 Time 22:25 Rev Time 0.00
Received By fgiaquin Date 2021-05-18 Time 21:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:38 Rev Time 0.00
Received By rmcdouga Date 2021-06-15 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-11 Cont ID  
Sent By jleahy Date 2021-06-11 Time 15:49 Rev Time 0.00
Received By jleahy Date 2021-05-04 Time 14:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:38 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 16:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-28 Cont ID  
Sent By rmcdouga Date 2021-05-28 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2021-05-28 Time 10:26 Sent To  
Notes
2021-05-28 10:27:53THE SITE SPECIFIC GENERATOR PAD DETAILS ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE DESIGNER. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & 61G1 OR FS 471 & 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-09 Cont ID  
Sent By kalexand Date 2021-06-09 Time 09:28 Rev Time 0.00
Received By kalexand Date 2021-06-09 Time 09:28 Sent To I
Notes
***NONE***