Plan Review Details - Permit 21041080
Plan Review Stops For Permit 21041080
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-01 Cont ID  
Sent By rmcdouga Date 2021-07-01 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2021-07-01 Time 11:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-11 Cont ID  
Sent By rmcdouga Date 2021-05-11 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2021-05-11 Time 07:54 Sent To  
Notes
2021-05-11 08:00:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD
 ANCHORING DETAILS. IF A PREFABRICATED GENERATOR PAD
 WILL BE USED, SUBMIT SIGNED AND SEALED SITE SPECIFIC
 ENGINEERING FOR IT. FBC AMENDMENTS 107.2.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-25 Cont ID  
Sent By jleahy Date 2021-06-25 Time 14:39 Rev Time 0.00
Received By jleahy Date 2021-06-25 Time 14:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-11 Cont ID  
Sent By jleahy Date 2021-05-11 Time 09:57 Rev Time 0.00
Received By jleahy Date 2021-05-11 Time 09:46 Sent To  
Notes
2021-05-11 10:06:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOWS 2/0'A FEEDING THE LOADS, BECAUSE THERE IS 2
 PANELS THE FEEDER IS NOT FEEDING THE ENTIRE LOAD SO
 3/0'S WILL BE REQUIRED. 310.15(B)(7)(2)
  
 310.15(B)(7)(2) FOR A FEEDER RATED 100 THROUGH 400
 AMPERES, THE FEEDER CONDUCTORS SUPPLYING THE ENTIRE
 LOAD ASSOCIATED WITH A ONE-FAMILY DWELLING, OR THE
 FEEDER CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED
 WITH AN INDIVIDUAL DWELLING UNIT IN A TWO-FAMILY OR
 MULTIFAMILY DWELLING, SHALL BE PERMITTED TO HAVE AN
 AMPACITY NOT LESS THAN 83 PERCENT OF THE FEEDER RATING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-01 Cont ID  
Sent By rmcdouga Date 2021-07-01 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2021-06-21 Time 06:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-17 Cont ID  
Sent By medwards Date 2021-06-17 Time 09:35 Rev Time 0.00
Received By medwards Date 2021-04-20 Time 14:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-07-01 Cont ID  
Sent By rmcdouga Date 2021-07-01 Time 11:25 Rev Time 0.00
Received By rmcdouga Date 2021-07-01 Time 11:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-11 Cont ID  
Sent By rmcdouga Date 2021-05-11 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2021-05-11 Time 07:54 Sent To  
Notes
2021-05-11 08:04:46SIGNATURE WILL NEED TO BE EVALUATED WHEN BUILDING
 COMMENTS ARE ADDRESSED. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-16 Cont ID  
Sent By kalexand Date 2021-06-16 Time 13:37 Rev Time 0.00
Received By kalexand Date 2021-06-16 Time 13:37 Sent To I
Notes
***NONE***