Plan Review Details - Permit 21041075
Plan Review Stops For Permit 21041075
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-07-23 Cont ID  
Sent By rmcdouga Date 2021-07-23 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2021-07-23 Time 08:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-07 Cont ID  
Sent By rmcdouga Date 2021-07-07 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2021-07-07 Time 11:29 Sent To  
Notes
2021-07-07 11:31:17PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING / PREVIOUS COMMENTS WERE NOT
 ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT COMPLIED. THE GENERATOR PAD DRAWING THAT WAS
 SUBMITTED REFERENCES THE FBC SIXTH EDITION (2017) AND
 ASCE 7-10. THE FBC SEVENTH EDITION (2020) WENT INTO
 EFFECT ON DECEMBER 31, 2020. ALL NEW PERMITS APPLIED
 FOR ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH
 AND REFERENCE THE 2020 FBC SEVENTH EDITION AND ASCE
 7-16. FS CHAPTER 553
  
 2) NOT COMPLIED. THIS PROJECT IS LOCATED IN A SPECIAL
 FLOOD HAZARD AREA. THE GENERATOR AND ALL RELATED
 EQUIPMENT THAT IS SUBJECT TO DAMAGE FROM FLOOD WATERS
 ARE REQUIRED TO BE ELEVATED TO OR ABOVE THE FINISH
 FLOOR OF THE HABITABLE AREA OF THE EXISTING HOME. FBC
 R-322

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-11 Cont ID  
Sent By rmcdouga Date 2021-05-11 Time 08:30 Rev Time 0.00
Received By rmcdouga Date 2021-05-11 Time 08:30 Sent To  
Notes
2021-05-11 08:38:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWING THAT WAS SUBMITTED
 REFERENCES THE FBC SIXTH EDITION (2017) AND ASCE 7-10.
 THE FBC SEVENTH EDITION (2020) WENT INTO EFFECT ON
 DECEMBER 31, 2020. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE 2020 FBC SEVENTH EDITION AND ASCE 7-16.
 FS CHAPTER 553
  
 2) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA. THE GENERATOR AND ALL RELATED EQUIPMENT THAT IS
 SUBJECT TO DAMAGE FROM FLOOD WATERS ARE REQUIRED TO BE
 ELEVATED TO OR ABOVE THE FINISH FLOOR OF THE HABITABLE
 AREA OF THE EXISTING HOME. FBC R-322

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-07 Cont ID  
Sent By equinone Date 2021-05-07 Time 12:35 Rev Time 0.00
Received By equinone Date 2021-05-07 Time 12:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-07-03 Cont ID  
Sent By ccole Date 2021-07-03 Time 08:16 Rev Time 0.00
Received By ccole Date 2021-07-03 Time 08:06 Sent To  
Notes
2021-07-03 08:22:41PROVISO NOTE ON GAS RISER DRAWING:
 NOTE-
 THE GENERATOR IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA. THE GENERATOR AND ALL RELATED EQUIPMENT THAT ARE
 SUBJECT TO DAMAGE FROM FLOOD WATERS ARE REQUIRED TO BE
 ELEVATED TO OR ABOVE THE FINISH FLOOR OF THE HABITABLE
 AREA OF THE EXISTING HOME. FBC R-322

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By ccole Date 2021-05-07 Time 14:03 Rev Time 0.00
Received By ccole Date 2021-05-07 Time 13:36 Sent To  
Notes
2021-05-07 14:05:021ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041075
 5/7/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: THE CITY OF WPB RECORDS SHOW A COMPLETED
 GAS PERMIT FOR THE RESIDENCE- #15020463- THAT INCLUDED
 GAS SUPPLY PIPING TO A 40,000 BTU BBQ AND A FUTURE
 400,000 BTU POOL HEATER. PLEASE REVISE THE RISER
 DRAWING TO SHOW THE GAS PIPING TO THE APPLIANCES AND
 THE ADDITIONAL GAS LOADS- SECTION G2412.3 & G2412.4 FBC
 RES.
  
 2) GAS RISER: PROVIDE THE TOTAL DEVELOPED LENGTH OF THE
 SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET-
 SECTION G2413.4.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
2021-05-07 14:04:081ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041290
 5/5/2021
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
 1) GAS RISER: THE CITY OF WPB RECORDS SHOW A COMPLETED
 GAS PERMIT FOR THE RESIDENCE- #15020463- THAT INCLUDED
 GAS SUPPLY PIPING TO A 40,000 BTU BBQ AND A FUTURE
 400,000 BTU POOL HEATER. PLEASE REVISE THE RISER
 DRAWING TO SHOW THE GAS PIPING TO THE APPLIANCES AND
 THE ADDITIONAL GAS LOADS- SECTION G2412.3 & G2412.4 FBC
 RES.
 2) GAS RISER: PROVIDE THE TOTAL DEVELOPED LENGTH OF THE
 SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET-
 SECTION G2413.4.1 FBC RES.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-23 Cont ID  
Sent By rmcdouga Date 2021-07-23 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2021-07-23 Time 08:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-07 Cont ID  
Sent By rmcdouga Date 2021-07-07 Time 11:31 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-17 Cont ID  
Sent By medwards Date 2021-06-17 Time 09:36 Rev Time 0.00
Received By medwards Date 2021-04-20 Time 14:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-07-03 Cont ID  
Sent By ccole Date 2021-07-03 Time 08:08 Rev Time 0.00
Received By ccole Date 2021-07-03 Time 08:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-05-08 Cont ID  
Sent By ccole Date 2021-05-08 Time 07:46 Rev Time 0.00
Received By ccole Date 2021-05-07 Time 13:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-23 Cont ID  
Sent By rmcdouga Date 2021-07-23 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2021-07-23 Time 08:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-07-07 Cont ID  
Sent By rmcdouga Date 2021-07-07 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2021-07-07 Time 11:29 Sent To  
Notes
2021-07-07 11:29:19THE PREFABRICATED GENERATOR PAD DRAWINGS DO NOT HAVE
 THE ENGINEER'S DIGITAL SIGNATURE. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-11 Cont ID  
Sent By rmcdouga Date 2021-05-11 Time 08:30 Rev Time 0.00
Received By rmcdouga Date 2021-05-11 Time 08:30 Sent To  
Notes
2021-05-11 08:35:19THE PREFABRICATED GENERATOR PAD DRAWINGS DO NOT HAVE
 THE ENGINEER'S DIGITAL SIGNATURE. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15

Review Stop Z ZONING
Rev No 2 Status P Date 2021-07-23 Cont ID  
Sent By kalexand Date 2021-07-23 Time 09:39 Rev Time 0.00
Received By kalexand Date 2021-07-23 Time 09:39 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-16 Cont ID  
Sent By kalexand Date 2021-06-16 Time 13:41 Rev Time 0.00
Received By kalexand Date 2021-06-16 Time 13:41 Sent To I
Notes
***NONE***