Plan Review Details - Permit 21041061
Plan Review Stops For Permit 21041061
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 13:53 Rev Time 0.00
Received By rmcphers Date 2021-08-30 Time 13:36 Sent To  
Notes
2021-08-30 13:53:12REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING (A2.0), (A1.0 - 8A), (A1.0A), (A1.1) SHOW
 THE DOORS NUMBER 1 AND 2 BLOCKING THE EXIT CORRIDOR -
 PLEASE CORRECT FBC 1005.7.1DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR HEIGHT
 FROM THE FINISHED FLOOR TO THE "REFLECTIVE SURFACE" PER
 FBC 603.3MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 3) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR
 GRAB BAR DIMENSIONS FROM THE CENTER OF THE TIOLET PER
 FBC 604.5.2REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET SIDE
 GRAB BAR LOCATION DIMENSIONS PER FBC 604.5.1SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 5) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER
 HOLDER LOCATION DIMENSIONS FROM THE FACE OF THE TOILET
 PER FBC 604.7DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR
 6) PLEASE SHOW THE RESTROOM FLOOR AND BASE BOARD FINISH
 PER FBC 1210.2.1 FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES (DRYWALL IS NOT CONSIDERED
 A HARD SURFACE).
 7) PLEASE SHOW WALL AROUND THE MOP/SERVICE SINK PER FBC
 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-27 Cont ID  
Sent By rmcphers Date 2021-05-27 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2021-05-27 Time 14:04 Sent To  
Notes
2021-05-27 14:29:37REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING A6.0 APPEARS TO BE A PREVIOUS PLAN THAT
 SHOWS DOOR PRODUCT APPROVALS WHICH WERE NOT APPROVED.
 2) PLEASE SHOW STAIR HANDRAIL EXTENSIONS TOP AND BOTTOM
 TO COMPLY WITH FBC 1014.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS
 WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE
 SAME DIRECTION OF THE FLIGHTS OF STAIRS AT STAIRWAYS
 AND THE RAMP RUNS AT RAMPS.
 3) DRAWING A2.0 APPEARS TO BE A PREVIOUS PLAN WHICH
 SHOWS EXTERIOR CORRIDOR BLOCKED WITH DOORS THAT OPEN
 OUT BETWEEN THE UNITS FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-16 Cont ID  
Sent By fgiaquin Date 2021-09-16 Time 22:09 Rev Time 0.00
Received By fgiaquin Date 2021-09-16 Time 21:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-18 Cont ID  
Sent By pleduc Date 2021-08-18 Time   Rev Time 0.00
Received By pleduc Date 2021-08-18 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-05-19 Cont ID  
Sent By bdolan Date 2021-05-19 Time   Rev Time 0.00
Received By pleduc Date 2021-05-19 Time 10:13 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-05-28 Cont ID  
Sent By fmittner Date 2021-05-28 Time 15:20 Rev Time 0.00
Received By fmittner Date 2021-05-28 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-18 Cont ID  
Sent By aoliver Date 2022-08-18 Time 08:02 Rev Time 0.00
Received By aoliver Date 2021-08-17 Time 16:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-01 Cont ID  
Sent By rmcphers Date 2021-06-01 Time 12:34 Rev Time 0.00
Received By rmcphers Date 2021-05-05 Time 11:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-08-28 Cont ID  
Sent By medwards Date 2021-08-28 Time 07:02 Rev Time 0.00
Received By medwards Date 2021-08-28 Time 07:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-09 Cont ID  
Sent By ccole Date 2021-09-09 Time 17:38 Rev Time 0.00
Received By ccole Date 2021-09-09 Time 17:29 Sent To  
Notes
2021-09-09 17:39:041ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21041061
 9/9/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE IDENTIFY THE PROPOSED USES OF THE SHELL
 SPACES- SECTION 107.2.1 WPB.
  
 2) P301 & P401: PLEASE PROVIDE THE CIVIL PLANS FOR
 WATER SERVICE AND SANITARY SEWER CONTINUATIONS AS
 REFERENCED IN THE NOTES- SECTION 107.2.1 WPB.
  
 3) P301: PLEASE NOTE THAT INDIVIDUAL SEPARATE PERMITS
 ARE REQUIRED FOR INSTALLATION OF THE POTABLE WATER
 SERVICE BACKFLOW PREVENTER, AND THE IRRIGATION SYSTEM
 BACKFLOW PREVENTER. A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN SEPARATE PERMITS FOR INSTALLATION OF THE
 DEVICES IN ACCORDANCE WITH SECTION 105.1WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICES SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 4) P301 & P601: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES- SECTION 419.5 FBC P.
  
 5) P301 & P401: REFER TO TABLE C404.5.1 FBC EC- THE
 MAXIMUM PIPING LENGTH OF 2 FT. FROM THE HEATED WATER
 SOURCE TO THE LAVATORIES IS EXCEEDED WHICH WILL REQUIRE
 INSTALLATION OF A RECIRCULATION PUMP OR POINT OF USE
 WATER HEATERS AT THE LAVS.
  
 6) A2.0B: PLEASE SEE THE FBC ACC CODE SECTIONS BELOW
 AND REVISE THE DRAWINGS WHERE APPLICABLE.
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
  
 B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
  
 C) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
  
 D) TURNING SPACE DIAMETERS- SECTION 304.3.
  
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. THE REAR GRAB BAR POSITION
 SHALL BE DEPICTED IN COMPLIANCE WITH FIGURE 604.5.2.
  
 F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
  
 G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
  
 H) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
  
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 7) A2.0B: DETAIL 11 SHOWS THE MOP SINK WALL SURROUND TO
 BE PAINTED DRYWALL WHICH IS NOT IN COMPLIANCE WITH
 SECTION 1210.2.2 FBC P.
  
 8) P701: REVISE THE WATER HEATER DETAIL TO INCLUDE THE
 LOCATION OF THE REQUIRED THERMAL EXPANSION TANK-
 SECTION 607.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-28 Cont ID  
Sent By medwards Date 2021-08-28 Time 07:03 Rev Time 0.00
Received By medwards Date 2021-08-28 Time 07:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-27 Cont ID  
Sent By rmcphers Date 2021-05-27 Time 14:29 Rev Time 0.00
Received By rmcphers Date 2021-05-27 Time 14:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-17 Cont ID  
Sent By fmittner Date 2022-08-17 Time 12:02 Rev Time 0.00
Received By fmittner Date 2022-08-17 Time 12:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-28 Cont ID  
Sent By aaponte Date 2021-05-28 Time 15:20 Rev Time 0.00
Received By fmittner Date 2021-05-28 Time 15:20 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved