Plan Review Details - Permit 21041043
Plan Review Stops For Permit 21041043
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-04-30 Cont ID  
Sent By cpuell Date 2021-04-30 Time 16:38 Rev Time 0.00
Received By cpuell Date 2021-04-30 Time 16:38 Sent To  
Notes
2021-04-30 16:39:50SUITE HAD BEEN READDRESSED IN NOV 2020 THE NEW ADDRESS
 FOR THIS SUITE IS 2676 FLORIDA AVE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-08-12 Cont ID  
Sent By pvalenti Date 2021-08-12 Time 06:50 Rev Time 0.00
Received By pvalenti Date 2021-08-12 Time 06:45 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-07-12 Cont ID  
Sent By jwitmer Date 2021-07-12 Time 15:31 Rev Time 0.00
Received By jwitmer Date 2021-07-12 Time 15:15 Sent To  
Notes
2021-07-12 15:31:32COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] . THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-05 Cont ID  
Sent By jwitmer Date 2021-05-05 Time 15:05 Rev Time 0.00
Received By jwitmer Date 2021-05-05 Time 14:00 Sent To  
Notes
2021-05-05 15:04:25COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-08-12 Cont ID  
Sent By pvalenti Date 2021-08-12 Time 07:17 Rev Time 0.00
Received By pvalenti Date 2021-08-12 Time 06:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-12 Cont ID  
Sent By jwitmer Date 2021-07-12 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2021-07-12 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-05 Cont ID  
Sent By jwitmer Date 2021-05-05 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2021-05-05 Time 14:00 Sent To  
Notes
2021-05-05 15:03:20WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21041043
 ADD: 2600 FLORIDA AVE. SUITE: 100 (BUILT 1965)
 CONT: TAYMACK DEVELOPERS
 TEL: 844-482-9622
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 05TH/ 2021
 ACTION: DENIED
  
 1) BOTH THE PERMIT APPLICATION AND THE PLANS ARE USING
 A OUT OF DATE ADDRESS FOR THIS SITE. PLEASE UPDATE THE
 PLANS. PLEASE SEE THE ADDRESSING STOP, LAST NOV. THIS
 SITE WAS RE-ADDRESSED TO THE CITY?S ADDRESSING STANDARD
 FOR SITES WITH MULTIPLE TENANT ADDRESSES. CITY MUNI
 CODE SEC.78-6 (1-7) (2) LOCATION, BUILDINGS CONTAINING
 MORE THAN ONE ADDRESS.
 2020 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) THE INDEX SHEET LISTS A COVERSHEET WHICH WAS NOT
 UPLOADED WITH THE SET OF PLANS. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) THE LIFE SAFETY SHEET LIST THIS AS A LEVEL II
 ALTERATION. PLEASE PROVIDE THE LAST KNOWN USE (THAT HAD
 A BUSINESS TAX CERTIFICATE) FOR THIS TENANT SPACE. IT
 APPEARS THAT MOST OF THE TENANTS IN THIS BUILDING ARE
 SOME TYPE OF AUTO REPAIR SHOP WHICH WOULD BE A F-1
 OCCUPANCY TYPE. THEN THIS WOULD BECOME A CHANGE OF
 OCCUPANCY AND NEED TO FOLLOW THE GUIDELINES FOR PARTIAL
 CHANGE OF OCCUPANCY SECTION 1001.2.2.1 OF THE 2020
 FBC-EXISTING BUILDING CODE.
  
 4) THE LIFE SAFETY SHEET DOES NOT SHOW ANY ACCESSIBLE
 SEATING IN THE DINING ROOM.
 4A ) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT (40X
 0.05= 2 SEATS ACCESSIBLE) OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902.
  
 4B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 4C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 4D) 902.1. DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS
  
 4E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) SHEET A2.1.1 THE ENLARGED RESTROOMS SHOW WALL
 ELEVATION DETAILS ON SHEER A3.1.1. ONE OF THE WALL
 ELEVATIONS ARE SHOWN ON THIS SHEET. ACCESSIBLE ELEMENTS
 FOR RESTROOMS CAN NOT BE REVIEWED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-07-21 Cont ID  
Sent By jleahy Date 2021-07-21 Time 18:23 Rev Time 0.00
Received By jleahy Date 2021-07-21 Time 18:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-14 Cont ID  
Sent By equinone Date 2021-05-14 Time 15:21 Rev Time 0.00
Received By equinone Date 2021-05-14 Time 15:21 Sent To  
Notes
2021-05-14 15:30:37CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) PANEL SCHEDULE AND POWER PLAN DO NOT MATCH. SOME
 CIRCUITS ON PANEL SCHEDULE (A-14. A-4) ARE NOT SHOWN ON
 POWER PLAN
 AND SOME CIRCUITS ON POWER PLAN (A-26) ARE NOT SHOWN ON
 PANEL SCHEDULE. POWER PLAN SHOWS TWO CIRCUITS A-23
 CONNECTED TO RECEPTACLES
 BUT SPACE 23 IS ALREADY ALLOCATED FOR CONDENSER UNIT 1.
 PLEASE CORRECT DISCREPANCIES AND SUBMIT NEW POWER PLAN
 AND PANEL SCHEDULES.
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-07-12 Cont ID  
Sent By cwalker Date 2021-07-12 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-30 Cont ID  
Sent By cwalker Date 2021-04-30 Time   Rev Time 0.00
Received By cwalker Date 2021-04-30 Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-08-27 Cont ID  
Sent By ccole Date 2021-08-27 Time 12:25 Rev Time 0.00
Received By ccole Date 2021-08-27 Time 11:44 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-08-09 Cont ID  
Sent By ccole Date 2021-08-09 Time 15:04 Rev Time 0.00
Received By ccole Date 2021-08-09 Time 12:15 Sent To  
Notes
2021-08-09 15:05:223RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041043
 8/9/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE
 1ST REVIEW IS LISTED BELOW WITH NOTES ADDED FOR FURTHER
 CLARIFICATION.
  
 4) FAILED. P5.1: PROVIDE COMBUSTION AIR CALCULATIONS
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION
 304.1 FBC FG. THE REVISED CALCS ARE USING THE EQUATION
 FOUND IN SECTION 304.5.2 WHICH CAN ONLY BE USED WHEN
 THERE IS A KNOWN AIR INFILTRATION RATE LESS THAN .40
 AIR CHANGES PER HOUR (ACH). THE CALCULATIONS PROVIDED
 ARE USING AN ACH OF 17.6. THE CALCULATION IS ALSO USING
 700 CFMS OF O/A AS THE BASIS OF THE ACH, HOWEVER THE
 AIR IS BEING SUPPLIED MECHANICALLY AS OPPOSED TO
 INFILTRATION. IF USING MECHANICAL AIR PLEASE REFER TO
 SECTION 304.9 AND PROVIDE THE CALCULATION. PLEASE
 REVIEW SECTION 304.5.1 BELOW:
 THE REQUIRED VOLUME OF INDOOR AIR SHALL BE DETERMINED
 IN ACCORDANCE WITH SECTION 304.5.1 OR 304.5.2, EXCEPT
 THAT WHERE THE AIR INFILTRATION RATE IS KNOWN TO BE
 LESS THAN 0.40 AIR CHANGES PER HOUR (ACH), SECTION
 304.5.2 SHALL BE USED. THE TOTAL REQUIRED VOLUME SHALL
 BE THE SUM OF THE REQUIRED VOLUME CALCULATED FOR ALL
 APPLIANCES LOCATED WITHIN THE SPACE. ROOMS
 COMMUNICATING DIRECTLY WITH THE SPACE IN WHICH THE
 APPLIANCES ARE INSTALLED THROUGH OPENINGS NOT FURNISHED
 WITH DOORS, AND THROUGH COMBUSTION AIR OPENINGS SIZED
 AND LOCATED IN ACCORDANCE WITH SECTION 304.5.3, ARE
 CONSIDERED TO BE PART OF THE REQUIRED VOLUME.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-07-16 Cont ID  
Sent By ccole Date 2021-07-16 Time 14:53 Rev Time 0.00
Received By ccole Date 2021-07-16 Time 11:39 Sent To  
Notes
2021-08-09 15:04:052ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041043
 7/16/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE
 1ST REVIEW IS LISTED BELOW WITH NOTES ADDED FOR FURTHER
 CLARIFICATION.
  
 4) FAILED. P5.1: PROVIDE COMBUSTION AIR CALCULATIONS
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION
 304.1 FBC FG. THE CALCULATIONS ON THE TOP LEFT OF THE
 SHEET APPEAR TO INDICATE A DEFICIENT AMOUNT OF CUBIC FT
 PROVIDED FOR INDOOR COMBUSTION AIR. PLEASE NOTE THAT
 THE VOLUME OF THE DINING ROOM CANNOT BE USED UNLESS
 OPENINGS SIZED IN ACCORDANCE WITH SECTION 304.5.3 FBC
 FG ARE PROVIDED. THE CALCULATION AT THE BOTTOM LEFT OF
 THE PAGE IS INDICATING 1000 CFMS OF O/A HOWEVER THE
 KITCHEN AC SYSTEM SHOWN ON SHEET M.6.1 INDICATES 700
 CFMS. PLEASE PROVIDE REVISED CALCULATIONS.
 NEW COMMENT.
  
 1) SHEETS P3.1 & P5.1: THE REQUESTED SPECS FOR THE
 GAS-FIRED TANKLESS WATER WERE NOT SUBMITTED AND MAY BE
 DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB.
 PLEASE CLEARLY SHOW THE LOCATIONS OF THE NEW METER AND
 THE WATER HEATER WITH ALL REQUIRED CLEARANCES INCLUDING
 THE DOOR OPENING INTO THE KITCHEN- SECTION 624.1 FBC
 FG. FOR CONDENSING TYPE WATER HEATER SHOW HOPW
 CONDENSATE FROM THE UNIT WILL BE DISCHARGED TO AN
 APPROVED PLACE OF DISPOSAL- SECTIONS 307.2 & 307.3 FBC
 FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2021-07-16 14:54:292ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041043
 7/16/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE
 1ST REVIEW IS LISTED BELOW WITH NOTES ADDED FOR FURTHER
 CLARIFICATION.
  
 4) FAILED. P5.1: PROVIDE COMBUSTION AIR CALCULATIONS
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION
 304.1 FBC FG. THE CALCULATIONS ON THE TOP LEFT OF THE
 SHEET APPEAR TO INDICATE A DEFICIENT AMOUNT OF CUBIC FT
 PROVIDED FOR INDOOR COMBUSTION AIR. PLEASE NOTE THAT
 THE VOLUME OF THE DINING ROOM CANNOT BE USED UNLESS
 OPENINGS SIZED IN ACCORDANCE WITH SECTION 304.5.3 FBC
 FG ARE PROVIDED. THE CALCULATION AT THE BOTTOM LEFT OF
 THE PAGE IS INDICATING 1000 CFMS OF O/A HOWEVER THE
 KITCHEN AC SYSTEM SHOWN ON SHEET M.6.1 INDICATES 700
 CFMS. PLEASE PROVIDE REVISED CALCULATIONS.
 NEW COMMENT.
  
 1) SHEETS P3.1 & P5.1: THE REQUESTED SPECS FOR THE
 GAS-FIRED TANKLESS WATER WERE NOT SUBMITTED AND MAY BE
 DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB.
 PLEASE CLEARLY SHOW THE LOCATIONS OF THE NEW METER AND
 THE WATER HEATER WITH ALL REQUIRED CLEARANCES INCLUDING
 THE DOOR OPENING INTO THE KITCHEN- SECTION 624.1 FBC
 FG. FOR CONDENSING TYPE WATER HEATER SHOW HOPW
 CONDENSATE FROM THE UNIT WILL BE DISCHARGED TO AN
 APPROVED PLACE OF DISPOSAL- SECTIONS 307.2 & 307.3 FBC
 FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-05-13 Cont ID  
Sent By ccole Date 2021-05-13 Time 12:04 Rev Time 0.00
Received By ccole Date 2021-05-13 Time 10:32 Sent To  
Notes
2021-05-13 12:05:091ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041043
 5/13/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P5.1: LIST THE 2 PSI PIPE SIZING TABLE
 402.4(5) FBC FG.
  
 2) P5.1: PROVIDE THE BRANCH PIPE SIZES TO THE COOKING
 APPLIANCES- TABLE 402.4(2) FBC FG.
  
 3) P5.1: SHOW THE LOCATIONS OF REQUIRED PIPE UNIONS AT
 THE REGULATORS- SECTION 410.2&7) FBC FG.
  
 4) P5.1: PROVIDE COMBUSTION AIR CALCULATIONS AND
 INDICATE HOW THE AIR WILL BE PROVIDED- SECTION 304.1
 FBC FG.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCES AND WATER HEATER- SECTIONS 623.1 AND 624.1
 FBC FG. DEFERRED SUBMITTALS ARE ACCEPTABLE PER SECTION
 107.3.4.1 WPB.
  
 6) SUBMIT REGULATOR SPECS MARKED UP OR HIGHLIGHTED TO
 SHOW INLET AND OUTLET PRESSURES AND PIPE SIZES- SECTION
 410.2 FBC FG. DEFERRED SUBMITTALS ARE ACCEPTABLE-
 SECTION 107.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-08-27 Time   Rev Time 0.00
Received By lmarchan Date 2021-08-19 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-12 Cont ID  
Sent By pvalenti Date 2021-08-12 Time 07:18 Rev Time 0.00
Received By pvalenti Date 2021-07-30 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-21 Cont ID  
Sent By jleahy Date 2021-07-21 Time 18:23 Rev Time 0.00
Received By jleahy Date 2021-07-09 Time 12:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-17 Cont ID  
Sent By rmcdouga Date 2021-05-17 Time 14:29 Rev Time 0.00
Received By rmcdouga Date 2021-04-29 Time 09:25 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-09-20 Cont ID  
Sent By lmarchan Date 2021-09-20 Time 11:21 Rev Time 0.00
Received By lmarchan Date 2021-08-30 Time 12:20 Sent To  
Notes
2021-09-20 11:21:30MU-2021-043249 - $0.00 FEES DUE
2021-08-30 12:21:308/30/21 EMAILED IMPACT FOR REVIEW- AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-05-05 Cont ID  
Sent By jwitmer Date 2021-05-05 Time 15:05 Rev Time 0.00
Received By jwitmer Date 2021-05-05 Time 14:00 Sent To  
Notes
2021-05-05 15:05:37IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-07-19 Cont ID  
Sent By medwards Date 2021-07-19 Time 13:45 Rev Time 0.00
Received By medwards Date 2021-07-19 Time 13:45 Sent To  
Notes
2021-07-19 13:49:16APPROVED WITH PRIVISO:
 AHU-2 - O/A CFM MUST BE AT LEAST THE MINIMUM OF 494 CFM
 REQUIRED FROM THE OUTDOOR AIR CALCULATIONS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-11 Cont ID  
Sent By medwards Date 2021-05-11 Time 15:03 Rev Time 0.00
Received By medwards Date 2021-05-11 Time 15:03 Sent To  
Notes
2021-05-11 15:06:06PLEASE SEE THE BUILDING REVIEWER NOTES FOR POSSIBLE
 CHANGE OF USE. PLEASE PUT A NOTE ON THE DRAWINGS THAT
 THE HOOD AND REFRIGERATION SYSTEMS MUST EACH BE
 SUBMITED UNDER ITS OWN PERMIT AND REVIEW.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-08-27 Cont ID  
Sent By ccole Date 2021-08-27 Time 12:25 Rev Time 0.00
Received By ccole Date 2021-08-27 Time 11:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-08-09 Cont ID  
Sent By ccole Date 2021-08-09 Time 13:40 Rev Time 0.00
Received By ccole Date 2021-08-09 Time 12:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-07-16 Cont ID  
Sent By ccole Date 2021-07-16 Time 14:55 Rev Time 0.00
Received By ccole Date 2021-07-16 Time 11:39 Sent To  
Notes
2021-07-16 14:55:582ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21041043
 7/16/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #2, 3D, 5,
 & 9 ARE LISTED BELOW.
  
 2) FAILED. SHEET A2.1.1: PROVIDE THE KNEE AND TOE
 CLEARANCES FOR THE SINKS- SECTIONS 606.2 & 306.1 FBC
 ACC. REFER TO FIGURES 306.2 & 306.3 AND PROVIDE THE
 ACTUAL CLEARANCE MEASUREMENT IN THE DETAIL.
  
 3D) FAILED. PROVIDE A SITE AND SURVEY PLAN SHOWING THE
 LOCATION OF THE NEW GREASE INTERCEPTOR. IF TO BE
 INSTALLED IN A PARKING LOT OR DRIVE AREA, A HEAVY-DUTY
 TRAFFIC LID WILL BE REQUIRED- SECTION 107.2.1 WPB AND
 1003.3.5 FBC P. PLEASE REVISE KEYNOTES 1-3 ON P5.1 TO
 CLEARLY INDICATE THE WORK DESCRIBED WILL BE UNDER
 SEPARATE PERMIT.
  
 5) FAILED. P2.1: NONCOMPLIANT SANITARY WET VENT- TWO
 WATER CLOSETS UPSTREAM OF THE DRY VENT CONNECTION-
 SECTION 912.2.1 FBC P. NOT CORRECTED.
  
 9) FAILED. P5.1: KEY NOTES #1 & 3 SPECIFY CIVIL PLANS
 FOR LOCATIONS OF THE SEWER LATERAL, AND NEW WATER METER
 AND BACKFLOW PREVENTER. PLEASE PROVIDE THE PLANS-
 SECTION 107.2.1. PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR INSTALLATION OF THE POTABLE WATER SERVICE
 BACKFLOW ASSEMBLY- A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. PLEASE
 REVISE KEYNOTES 1-3 ON P5.1 TO CLEARLY INDICATE THE
 WORK DESCRIBED WILL BE UNDER SEPARATE PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-05-13 Cont ID  
Sent By ccole Date 2021-05-13 Time 11:28 Rev Time 0.00
Received By ccole Date 2021-05-12 Time 17:12 Sent To  
Notes
2021-05-13 11:29:041ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21041043
 5/13/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE PLUMBING FIXTURE CALCULATIONS IN ACCORDANCE
 WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE INDICATING
 THE REQUIRED AND PROVIDED NUMBER OF FIXTURES. PLEASE
 NOTE THAT A DRINKING FOUNTAIN IS A REQUIRED PLUMBING
 FIXTURE FOR AN ASSEMBLY OCCUPANCY UNLESS THE EXCEPTION
 UNDER SECTION 410.4 SUBSTITUTION IS CLAIMED: WHERE
 RESTAURANTS PROVIDE DRINKING WATER IN A CONTAINER FREE
 OF CHARGE, DRINKING FOUNTAINS SHALL NOT BE REQUIRED IN
 THOSE RESTAURANTS. IF THIS IS THE INTENTION, PLEASE
 PLACE A NOTE ON THE CALCULATION SCHEDULE.
  
 2) SHEET A2.1.1: PROVIDE THE KNEE AND TOE CLEARANCES
 FOR THE SINKS- SECTIONS 606.2 & 306.1 FBC ACC.
  
 3) SHEETS P0.1, P2.1, & P5.1: PROVIDE AN EQUIPMENT
 SCHEDULE AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE NEW GREASE INTERCEPTOR- SECTION 1003.3.5 FBC P.
  
 A) PROVIDE INTERCEPTOR SIZING CALCULATIONS.
  
 B) THE DRAINAGE FROM THE HAND SINK AND FLOOR DRAINS IN
 THE SERVING AREA SHALL NOT DRAIN INTO THE GREASE
 INTERCEPTOR- SECTION 1003.3.1 FBC P. THE HAND SINK IS
 NOT CONSIDERED A SIGNIFICANT GREASE WASTE CONTRIBUTOR,
 AND THE FLOOR DRAINS IN THE SERVING AREA ARE DRAINING
 CLEAR WATER WASTE.
  
 C) PROVIDE A SAMPLING PORT DETAIL FOR THE INTERCEPTOR-
 SECTION 1003.3.5 FBC P.
  
 D) PROVIDE A SITE AND SURVEY PLAN SHOWING THE LOCATION
 OF THE NEW GREASE INTERCEPTOR. IF TO BE INSTALLED IN A
 PARKING LOT OR DRIVE AREA, A HEAVY-DUTY TRAFFIC LID
 WILL BE REQUIRED- SECTION 107.2.1 WPB AND 1003.3.5 FBC
 P.
  
 4) PROVIDE AN INDIRECT WASTE DETAIL FOR THE
 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P.
  
 5) P2.1: NONCOMPLIANT SANITARY WET VENT- TWO WATER
 CLOSETS UPSTREAM OF THE DRY VENT CONNECTION- SECTION
 912.2.1 FBC P.
  
 6) P0.1: PROVIDE THE EFFICIENCY RATING OF THE TANKLESS
 WATER HEATER- TABLE C404.2 FBC EC.
  
 7) P0.1, P3.1, & P5.1: PROVIDE EITHER A RECIRCULATION
 PUMP FOR THE HOT WATER SYSTEM OR POINT OF USE WATER
 HEATERS AT THE LAVATORIES- SECTION AND TABLE C404.5.1
 FBC EC.
  
 8) P3.1: PROVIDE THE TEXT FOR KEYNOTES 1 & 2- SECTION
 107.2.1 WPB.
  
 9) P5.1: KEY NOTES #1 & 3 SPECIFY CIVIL PLANS FOR
 LOCATIONS OF THE SEWER LATERAL, AND NEW WATER METER AND
 BACKFLOW PREVENTER. PLEASE PROVIDE THE PLANS- SECTION
 107.2.1. PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED
 FOR INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW
 ASSEMBLY- A FL. LICENSED PLUMBING CONTRACTOR SHALL
 OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-08-27 Cont ID  
Sent By ccole Date 2021-08-27 Time 12:25 Rev Time 0.00
Received By ccole Date 2021-08-27 Time 11:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-12 Cont ID  
Sent By pvalenti Date 2021-08-12 Time 07:15 Rev Time 0.00
Received By pvalenti Date 2021-08-12 Time 06:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-07-19 Cont ID  
Sent By medwards Date 2021-07-19 Time 13:51 Rev Time 0.00
Received By medwards Date 2021-07-19 Time 13:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-11 Cont ID  
Sent By medwards Date 2021-05-11 Time 15:45 Rev Time 0.00
Received By medwards Date 2021-05-11 Time 15:45 Sent To  
Notes
***NONE***