Plan Review Details - Permit 21040978
Plan Review Stops For Permit 21040978
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-06-04 Cont ID  
Sent By rmcphers Date 2021-06-04 Time 13:08 Rev Time 0.00
Received By rmcphers Date 2021-06-04 Time 13:08 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-11 Cont ID  
Sent By rmcphers Date 2021-05-11 Time 16:13 Rev Time 0.00
Received By jgomez Date 2021-05-11 Time 16:22 Sent To  
Notes
2021-05-11 16:28:27ASBESTOS REVIEW
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGMENT FROM THE
 CONTRACTOR, ON CONTRACTOR'S LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 NOTE:
 THE INFORMATION SHOULD INCLUDE THE ADDRESS, PERMIT
 NUMBER AND ASBESTOS IN THE SUBJECT LINE.
  
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
2021-05-11 16:13:46PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-23 Cont ID  
Sent By rmcphers Date 2021-06-23 Time 10:19 Rev Time 0.00
Received By rmcphers Date 2021-06-23 Time 10:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-04 Cont ID  
Sent By rmcphers Date 2021-06-04 Time 12:58 Rev Time 0.00
Received By rmcphers Date 2021-06-04 Time 12:32 Sent To  
Notes
2021-06-04 12:56:56FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 I LOOKED UP THE BUILDINGS PLANS AND I SEE THAT THE
 STRUCTURAL FLOOR SYSTEM IS BAR JOIST WITH A 2.5 INCH
 CONCRETE SLAB. THE TEST REPORT THAT YOU PROVIDED IS FOR
 AN 6 INCH SLAB. THE ACOUSTICAL TEST REPORT WILL NEED TO
 BE FOR A SIMILAR TYPE FLOOR SYSTEM. YOU CAN ALSO
 PROVIDE AN ANALYSIS FROM A DESIGN PROFESSIONAL TO
 COMPLY WITH THE SOUND REQUIREMENTS OF FBC 1207
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). PLEASE EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY
 BEFORE RESUBMITTING TO PROJECTDOX ( [email protected]
 )
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-11 Cont ID  
Sent By rmcphers Date 2021-05-11 Time 16:12 Rev Time 0.00
Received By rmcphers Date 2021-05-11 Time 16:07 Sent To  
Notes
2021-05-11 16:12:40FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). PLEASE EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY
 BEFORE RESUBMITTING TO PROJECTDOX ( [email protected]
 )
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2021-05-04 Cont ID  
Sent By jleahy Date 2021-05-04 Time 15:57 Rev Time 0.00
Received By jleahy Date 2021-05-04 Time 15:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-14 Cont ID  
Sent By cwalker Date 2021-06-14 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-22 Cont ID  
Sent By cwalker Date 2021-04-22 Time   Rev Time 0.00
Received By cwalker Date 2021-04-22 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-23 Cont ID  
Sent By lcrespo Date 2021-06-23 Time 17:00 Rev Time 0.00
Received By lcrespo Date 2021-06-11 Time 12:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-09 Cont ID  
Sent By dbattles Date 2021-06-09 Time 12:54 Rev Time 0.00
Received By dbattles Date 2021-05-17 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-11 Cont ID  
Sent By rmcphers Date 2021-05-11 Time 16:13 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 07:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-05-03 Cont ID  
Sent By medwards Date 2021-05-03 Time 11:23 Rev Time 0.00
Received By medwards Date 2021-05-03 Time 11:18 Sent To  
Notes
2021-05-03 11:23:48NO MECHANICAL WORK SHOWN ON DRAWING. ME

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-23 Cont ID  
Sent By lcrespo Date 2021-06-23 Time 16:56 Rev Time 0.00
Received By lcrespo Date 2021-06-23 Time 16:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-05-03 Cont ID  
Sent By tklarge Date 2021-05-03 Time 05:43 Rev Time 0.00
Received By tklarge Date 2021-05-03 Time 05:24 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2021-06-09 Cont ID  
Sent By dbattles Date 2021-06-09 Time 12:52 Rev Time 0.00
Received By dbattles Date 2021-06-09 Time 12:52 Sent To  
Notes
2021-06-09 12:54:37ALL PRIVATE PROVIDER DOCUMENTS ARE IN PROJECTDOX AND
 COMPLY WITH F.S. 553.791

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2021-04-22 Cont ID  
Sent By shill Date 2021-04-22 Time 11:59 Rev Time 0.00
Received By shill Date 2021-04-22 Time 11:59 Sent To  
Notes
2021-04-22 12:00:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PRIVATE PROVIDER INSPECTIONS HAS BEEN REQUESTED.
  
 FS553.791, SUBMIT PRIVATE PROVIDER CERTIFICATE OF
 INSURANCE, RESUMES.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-05-03 Cont ID  
Sent By medwards Date 2021-05-03 Time 11:24 Rev Time 0.00
Received By medwards Date 2021-05-03 Time 11:24 Sent To  
Notes
***NONE***