Plan Review Details - Permit 21040946
Plan Review Stops For Permit 21040946
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-05-26 Cont ID  
Sent By pvalenti Date 2021-05-26 Time 09:42 Rev Time 0.00
Received By pvalenti Date 2021-05-26 Time 09:42 Sent To  
Notes
2021-05-26 11:31:38 
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 AT TIME OF INSPECTION, PROVIE MANUFACTURER'S
 SPECIFICATIONS ON-SITE.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-19 Cont ID  
Sent By jleahy Date 2021-05-19 Time 10:46 Rev Time 0.00
Received By jleahy Date 2021-05-19 Time 10:42 Sent To  
Notes
2021-05-19 10:47:35ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRC WORK SHOWN

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2021-05-20 Cont ID  
Sent By pleduc Date 2021-05-20 Time   Rev Time 0.00
Received By pleduc Date 2021-05-20 Time 10:50 Sent To  
Notes
2021-05-20 10:51:00SFH, LIFE SAFETY REVIEW BY FIRE IS NOT REQUIRED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-06-02 Cont ID  
Sent By ccole Date 2021-06-02 Time 11:18 Rev Time 0.00
Received By ccole Date 2021-06-02 Time 10:52 Sent To  
Notes
2021-06-02 11:20:171ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21040946
 6/2/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A FL. LICENSED ENGINEER OR THE LICENSED GAS
 CONTRACTOR OF RECORD SHALL PROVIDE COMPLETE GAS PLANS
 FOR THE FIREPLACE INSTALLATIONS INCLUDING COMBUSTION
 AIR CALCULATIONS, VENTING DIAGRAMS, CLEARANCES TO
 COMBUSTIBLES AND A GAS RISER DRAWING. THE CURRENT FLOOR
 PLAN DRAWING BY TOM CARDILLO SHOWING SOME GAS PIPING
 HAS INCOMPLETE INFORMATION. THE AUTHOR OF THE PLAN TOM
 CARDILLO SHALL PROVIDE HIS LICENSURE INFORMATION ON THE
 PLAN- I WAS UNABLE TO LOCATE ANY LICENSE INFORMATION-
 FLORIDA STATUTES 471.003(2)(H) & 471.025 AND SECTION
 107.2.1 WPB.
  
 2) PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES
 ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE
 RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO
 FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, DRIP LEGS,
 AND PIPE UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 3) REFER TO SECTION G2407.1 FBC RES AND PROVIDE
 COMBUSTION AIR CALCULATIONS FOR THE FIREPLACES.
  
 4) REFER TO SECTIONS G2408.1 & G2427.1 FBC RES AND
 PROVIDE VENTING DIAGRAMS AND SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-06-02 Time   Rev Time 0.00
Received By cdecoeur Date 2021-05-11 Time 10:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-06-02 Cont ID  
Sent By ccole Date 2021-06-02 Time 10:52 Rev Time 0.00
Received By ccole Date 2021-06-02 Time 10:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-06-02 Cont ID  
Sent By ccole Date 2021-06-02 Time 11:21 Rev Time 0.00
Received By ccole Date 2021-06-02 Time 10:52 Sent To  
Notes
***NONE***