Plan Review Details - Permit 21040907
Plan Review Stops For Permit 21040907
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-05-05 Cont ID  
Sent By lcrespo Date 2021-05-05 Time 14:40 Rev Time 0.00
Received By lcrespo Date 2021-05-05 Time 14:33 Sent To  
Notes
2021-05-05 14:41:4405/05/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-04-28 Cont ID  
Sent By lcrespo Date 2021-04-28 Time 09:33 Rev Time 0.00
Received By lcrespo Date 2021-04-28 Time 09:05 Sent To  
Notes
2021-04-28 09:32:5904/28/21 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 2. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. THERE ARE NO SIZES ON PE PIPE, AND THE FIRE PIT CALL
 FOR 65 BTUS ON ISO AND SPECS IS 290 BTUS. PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PLEASE LIST THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD
 SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN A 2
 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO 2
 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES PER THE 2020 FBC RES. SECS.
 G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. LIST THE
 BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. G2413.
  
 5. WHERE IS THE DRYER LOCATED, AND IS IT IN A CLOSET,
 DOES LOVER DOOR, SO PLEASE SUBMIT CALCULATIONS FOR
 COMBUSTION AIR PER THE 2020 FBC RES. SEC. G2407.1 AND
 G2439.4 (CLOTHES DRYERS).
  
 6. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 7. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.2.
  
 8. PLEASE LABEL THE SHUT-OFF VALVE ON GAS ISOMERIC PER
 THE 2020 FBC RES. SEC. G2401.1.3.
  
 9. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR
 APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC
 RES. SEC. G2419.2.
  
 10. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC 109.3.
 BUILDING PERMITS VALUATIONS.
  
 11. PLEASE SHOW THE DISTANCE OF THE LOCATION OF THE
 TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF
 ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 12. THIS UNIT REQUIRES CONDENSATE, AND IT NEEDS TO BE
 1' AWAY FROM THE STRUCTURE PER THE 2017 FBC SEC.
 R318.5. PLEASE PUT NOT ON PLANS.
  
 13. PIPES OR TANK-LEES NEED TO BE INSULATED WITH A
 MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3 PLEASE PUT
 A NOTE ON PLANS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By lcrespo Date 2021-04-21 Time 13:40 Rev Time 0.00
Received By lcrespo Date 2021-04-21 Time 13:17 Sent To  
Notes
2021-04-21 13:41:0404/21/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 2. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER THE 2020 FBC RES. SEC. G2413.2. WHAT IS
 THE LONGEST LENGTH?
  
 4. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED TO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS APPROPRIATELY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 PER THE 2020 FBC RES. SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3. LIST THE BTU LOAD OF EACH APPLIANCE
 AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020
 FBC RES. SEC. G2413.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020
 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 8. SUBMIT A SIZING TABLE USED IN THE DESIGN FOR THE GAS
 SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING
 THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD
 USED IN THE DESIGN OF THIS SYSTEM PER THE 2020 FBC RES.
 SEC. G2413.3.
  
 9. PLEASE SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 10. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1? OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.2.
  
 11. PLEASE LABEL THE SHUT-OFF VALVE ON GAS ISOMERIC PER
 THE 2020 FBC RES. SEC. G2401.1.3.
  
 12. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR
 APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC
 RES. SEC. G2419.2.
  
 13. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC 109.3.
 BUILDING PERMITS VALUATIONS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-05 Cont ID  
Sent By lcrespo Date 2021-05-05 Time 14:41 Rev Time 0.00
Received By lcrespo Date 2021-05-04 Time 12:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-28 Cont ID  
Sent By lcrespo Date 2021-04-28 Time 09:33 Rev Time 0.00
Received By lcrespo Date 2021-04-26 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-21 Cont ID  
Sent By lcrespo Date 2021-04-21 Time 13:41 Rev Time 0.00
Received By lcrespo Date 2021-04-16 Time 12:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-05-05 Cont ID  
Sent By lcrespo Date 2021-05-05 Time 14:41 Rev Time 0.00
Received By lcrespo Date 2021-05-05 Time 14:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-04-28 Cont ID  
Sent By lcrespo Date 2021-04-28 Time 09:05 Rev Time 0.00
Received By lcrespo Date 2021-04-28 Time 09:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-21 Cont ID  
Sent By lcrespo Date 2021-04-21 Time 13:40 Rev Time 0.00
Received By lcrespo Date 2021-04-21 Time 13:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-04-21 Cont ID  
Sent By lcrespo Date 2021-04-21 Time 13:41 Rev Time 0.00
Received By lcrespo Date 2021-04-21 Time 13:41 Sent To  
Notes
***NONE***