Plan Review Details - Permit 21040866
Plan Review Stops For Permit 21040866
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-05-19 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2021-05-19 Time 08:44 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By jwitmer Date 2021-04-27 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2021-04-27 Time 14:30 Sent To  
Notes
2021-04-27 15:16:00TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-21 Cont ID  
Sent By jwitmer Date 2021-06-21 Time 17:07 Rev Time 0.00
Received By jwitmer Date 2021-06-21 Time 16:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-19 Cont ID  
Sent By jwitmer Date 2021-05-19 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2021-05-19 Time 08:44 Sent To  
Notes
2021-05-19 09:37:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21040866
 ADD: 3901 S. FLAGLER DR. # 804 BUILDING BUILT IN 1986
 CONT: COUNHAN CONSTRUCTION LLC
 TEL: 561-585-0084
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MAY 19TH/ 2021
 ACTION: DENIED
  
 NOTICE ONLY!!!!!! 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) 66666WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
  
  
 1A) 2ND REVIEW. PLEASE NOTE THE 8 PAGE SPEC SHEETS ARE
 NOT CONSIDERED PRODUCT TESTING. WHERE SUPER SAM 125 IS
 INVOLVED WHEN TESTED ON A 6 INCH CONCRETE SLAB AND A
 QUARRY TILE IS INVOLVED THE IIC RATING OF 49. THEY ALSO
 DID A ONE TIME USE FIELD TEST WHERE A RESULT OF 50 IIC
 WAS ACHIEVED. THE PROBLEM WITH THIS PRODUCT IS THE IIC
 RATING ON A 6 INCH SLAB. BUILDINGS THAT ARE DOCUMENTED
 THROUGH THE BUILDING DEPARTMENT THAT HAVE 8 INCH
 CONCRETE SLABS DO NOT HAVE A PROBLEM WITH THIS PRODUCT,
 ON A 8 INCH CONCRETE SLAB AND QUARRY TILE A RESULT OF
 51 IIC IS ACHIEVED. THE CITY IS IN RECEIPT OF TESTING
 REPORT FOR SUPER SAM 125 THE COMPONENTS OF THE ASSEMBLY
 ARE, 6 INCH CONCRETE SLAB FLOOR CEILING ASSEMBLY
 OVERLAID WITH QUARRY TILE ON NAC ? INCH MEDIUM- BED
 MORTAR AND SUPER SAM MEMBRANE ON HOMASOTE ? INCH
 COMFORTBASE TESTED TO ASTM E 492/ ASTM 989-89 AND
 ACHIEVED A IIC OF 52. OUT OF THE 11 TEST SUBMITTED FOR
 THIS PRODUCT THIS IS THE ONLY ONE THAT ACHIEVES A IIC
 RATING OF 50 OR MORE.
  
 PLEASE BE AWARE THAT BOTH TEST STRUCTURE BORNE SOUND
 AND AIR BORNE SOUND DEAL WITH THE FLOOR/ CEILING
 ASSEMBLY AS STATED IN THE FIRST REVIEW, COMMENTS 2A &
 2B.
  
 1ST ROUND OF COMMENTS. THE PROPOSED FLOOR PLAN, FLOOR
 PLAN KEY NOTES, NOTE # 3 INDICATES THE USE OF ? INCH
 SUPER SAM 90 & 125 UNDERLAYMENT WITH PORCELAIN TILE.
 THE CONTRACTOR UPLOADED A SALES BROCHURE FOR PROFLEX
 MSC, MEGA SOUND CONTROL MEMBRANE WITH A FLAME SPREAD
 REPORT. THE CITY HAS NOT RECEIVED ANY APPROVED TESTING
 REPORTS FOR THIS PRODUCT ON A 6-INCH SLAB. DISCREPANCY
 IN PRODUCTS. PLEASE NOTE THE CITY IS IN RECEIPT OF
 TESTING REPORTS FOR SUPER SAM-125 UNDERLAYMENTS ON A
 6-INCH CONCRETE SLAB THE FLOOR TOPPING BEING TRAVERTINE
 TILE, THE IIC OF 51 AND STC OF 54. AND FLAME SPREAD
 REPORT. NO REPORTS FOR SUPER SIM 90.
 1B) IF THE PRODUCT VARIES FROM WHAT THE DESIGNER OF
 RECORD REQUEST A SHOP DRAWING STAMP OF APPROVAL MUST
 ACCOMPANY THE FLOORING UNDERLAYMENT REPORTS. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
 2) FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD
 THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR
 ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By jwitmer Date 2021-04-27 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2021-04-27 Time 14:30 Sent To  
Notes
2021-04-27 15:14:51WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21040866
 ADD: 3901 S. FLAGLER DR. # 804 BUILDING BUILT IN 1986
 CONT: COUNHAN CONSTRUCTION LLC
 TEL: 561-585-0084
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 27TH/ 2021
 ACTION: DENIED
 1A) THE PROPOSED FLOOR PLAN, FLOOR PLAN KEY NOTES, NOTE
 # 3 INDICATES THE USE OF ? INCH SUPER SAM 90
 UNDERLAYMENT WITH PORCELAIN TILE. THE CONTRACTOR
 UPLOADED A SALES BROCHURE FOR PROFLEX MSC, MEGA SOUND
 CONTROL MEMBRANE WITH A FLAME SPREAD REPORT. THE CITY
 HAS NOT RECEIVED ANY APPROVED TESTING REPORTS FOR THIS
 PRODUCT ON A 6-INCH SLAB. DISCREPANCY IN PRODUCTS.
 PLEASE NOTE THE CITY IS IN RECEIPT OF TESTING REPORTS
 FOR SUPER SAM-125 UNDERLAYMENTS ON A 6-INCH CONCRETE
 SLAB THE FLOOR TOPPING BEING TRAVERTINE TILE, THE IIC
 OF 51 AND STC OF 54. AND FLAME SPREAD REPORT. NO
 REPORTS FOR SUPER SIM 90.
 1B) IF THE PRODUCT VARIES FROM WHAT THE DESIGNER OF
 RECORD REQUEST A SHOP DRAWING STAMP OF APPROVAL MUST
 ACCOMPANY THE FLOORING UNDERLAYMENT REPORTS. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
 2) FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE,
 MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD
 THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR
 ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-27 Cont ID  
Sent By fgiaquin Date 2021-05-27 Time 21:23 Rev Time 0.00
Received By fgiaquin Date 2021-05-27 Time 20:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-27 Cont ID  
Sent By fgiaquin Date 2021-04-27 Time 22:54 Rev Time 0.00
Received By fgiaquin Date 2021-04-27 Time 22:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-06-18 Cont ID  
Sent By cwalker Date 2021-06-18 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-05-21 Cont ID  
Sent By cwalker Date 2021-05-21 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By cwalker Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-06-21 Time 17:07 Rev Time 0.00
Received By aoliver Date 2021-06-17 Time 12:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-01 Cont ID  
Sent By rmcphers Date 2021-06-01 Time 12:01 Rev Time 0.00
Received By rmcphers Date 2021-05-18 Time 13:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-29 Cont ID  
Sent By medwards Date 2021-04-29 Time 15:35 Rev Time 0.00
Received By medwards Date 2021-04-16 Time 08:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-04-27 Cont ID  
Sent By jwitmer Date 2021-04-27 Time 15:15 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2021-05-28 Cont ID  
Sent By medwards Date 2021-05-28 Time 09:56 Rev Time 0.00
Received By medwards Date 2021-05-28 Time 09:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-29 Cont ID  
Sent By medwards Date 2021-04-29 Time 15:34 Rev Time 0.00
Received By medwards Date 2021-04-29 Time 14:50 Sent To  
Notes
2021-04-29 15:34:591ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21040866
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1 GENERAL NOTE HVAC REQUIRES EXISTING UNIT TO
 STAY BUT ALL NEW DUCT WORK PLEASE SUBMIT A MECHANICAL
 DRAWING SHOWING THE NEW MECHANICAL DUCT WORK. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-05-26 Cont ID  
Sent By ccole Date 2021-05-26 Time 12:04 Rev Time 0.00
Received By ccole Date 2021-05-26 Time 11:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By ccole Date 2021-04-27 Time 08:09 Rev Time 0.00
Received By ccole Date 2021-04-26 Time 16:46 Sent To  
Notes
2021-04-27 08:09:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21040866
 4/27/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DEMOLITION AND ELECTRICAL PLANS INDICATE NEW
 LOCATIONS FOR THE KITCHEN SINK AND WASHING MACHINE, AND
 REPLACED FIXTURES ETC. PLEASE PROVIDE PLUMBING PLANS
 INCLUDING A SCOPE OF WORK OUTLINE, SANITARY AND WATER
 RISER DRAWINGS, AND NEW FIXTURE SPECIFICATIONS-
 SECTIONS 107.2.1 & 107.3.5.3 WPB.
  
 2) SHEET 2- SHOWER PAN: LINERS SHALL BE PITCHED
 ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS- SECTION 421.5.2 FBC P.
  
 3) RELOCATING DRAIN OUTLETS WILL REQUIRE THE FLOOR TO
 BE X-RAYED TO IN ORDER TO LOCATE REINFORCING STEEL OR
 POST STRESSED FLOOR TENDONS. PLEASE PLACE A NOTE ON THE
 PLANS TO VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1
 WPB.
  
 4) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-17 Cont ID  
Sent By medwards Date 2021-06-17 Time 16:41 Rev Time 0.00
Received By medwards Date 2021-06-17 Time 16:40 Sent To  
Notes
2021-06-17 16:42:28ORIGINAL SIGNED AND SEALED PAPER DRAWING ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-18 Cont ID  
Sent By medwards Date 2021-05-18 Time 17:29 Rev Time 0.00
Received By medwards Date 2021-05-18 Time 17:27 Sent To  
Notes
2021-05-18 17:29:37ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-16 Cont ID  
Sent By equinone Date 2021-04-16 Time 13:04 Rev Time 0.00
Received By equinone Date 2021-04-16 Time 13:04 Sent To  
Notes
2021-04-16 13:05:34SEALED AND SIGNED PAPER ORIGINALS. ROUTED TO INCOMING.