Plan Review Details - Permit 21040761
Plan Review Stops For Permit 21040761
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-07-08 Cont ID  
Sent By mcdouga Date 2021-07-08 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2021-07-08 Time 14:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-07 Cont ID  
Sent By rmcdouga Date 2021-07-07 Time 13:58 Rev Time 0.00
Received By rmcdouga Date 2021-07-07 Time 13:58 Sent To  
Notes
2021-07-07 13:58:01PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING / PREVIOUS COMMENT NOT ADDRESSED.
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) I WAS NOT ABLE TO FIND THE GENERATOR PAD DRAWING.
 NOT COMPLIED. SUBMIT GENERATOR PAD DRAWING WITH
 GENERATOR TO PAD ANCHORING DETAILS. IF A PREFABRICATED
 GENERATOR PAD WILL BE USED SUBMIT SITE SPECIFIC
 ENGINEERING THAT IS SIGNED AND SEALED BY A FLORIDA
 LICENSED ENGINEER. FBC AMENDMENTS 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By rmcdouga Date 2021-05-07 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2021-05-07 Time 10:25 Sent To  
Notes
2021-05-07 10:33:25PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR PAD DRAWING WITH GENERATOR TO PAD
 ANCHORING DETAILS. IF A PREFABRICATED GENERATOR PAD
 WILL BE USED SUBMIT SITE SPECIFIC ENGINEERING THAT IS
 SIGNED AND SEALED BY A FLORIDA LICENSED ENGINEER. FBC
 AMENDMENTS 107.2.1
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-07 Cont ID  
Sent By equinone Date 2021-05-07 Time 13:01 Rev Time 0.00
Received By equinone Date 2021-05-07 Time 13:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-07-12 Cont ID  
Sent By lcrespo Date 2021-07-12 Time 13:11 Rev Time 0.00
Received By lcrespo Date 2021-07-12 Time 13:11 Sent To  
Notes
2021-07-12 13:12:27GAS PERMIT UNDER 21010535

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By ccole Date 2021-05-07 Time 08:24 Rev Time 0.00
Received By ccole Date 2021-05-07 Time 08:04 Sent To  
Notes
2021-05-07 08:39:481ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21040761
 5/7/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CONTRACT INDICATES "REMOVE EXISTING GENERATOR
 AND REPLACE WITH NEW" HOWEVER I WAS UNABLE TO LOCATE A
 PREVIOUS PERMIT ON FILE FOR INSTALLATION OF A
 GENERATOR. PROVIDE A COMPLETE GAS RISER DRAWING THAT
 INCLUDES ALL NEW AND EXISTING GAS PIPING AND APPLIANCES
 AT THE RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES.
 REFER TO FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL
 INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS MARKED UP OR HIGHLIGHTED TO SHOW THE
 SELECTED MODEL, INPUT AND OUT PRESSURES AND PIPE SIZES,
 AND ORIFICE SIZES- G2421.1 & G2421.2 FBC RES.
  
 3) SURVEY: PLEASE INDICATE THE REQUIRED 10 FT.
 CLEARANCE FOR THE GENERATOR EXHAUST TO WINDOW AND DOOR
 OPENINGS INTO THE BUILDING- SECTION R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-12 Cont ID  
Sent By lcrespo Date 2021-07-12 Time 13:12 Rev Time 0.00
Received By lcrespo Date 2021-07-01 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-21 Cont ID  
Sent By medwards Date 2021-05-21 Time 09:10 Rev Time 0.00
Received By medwards Date 2021-04-14 Time 15:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-07-12 Cont ID  
Sent By lcrespo Date 2021-07-12 Time 13:12 Rev Time 0.00
Received By lcrespo Date 2021-07-12 Time 13:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-05-07 Cont ID  
Sent By ccole Date 2021-05-07 Time 08:03 Rev Time 0.00
Received By ccole Date 2021-05-07 Time 08:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-08 Cont ID  
Sent By mcdouga Date 2021-07-08 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2021-07-08 Time 14:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-07-07 Cont ID  
Sent By rmcdouga Date 2021-07-07 Time 13:58 Rev Time 0.00
Received By rmcdouga Date 2021-07-07 Time 13:58 Sent To  
Notes
2021-07-07 13:58:43ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 487 & 61G1 OR FS 471 &
 61G15
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By rmcdouga Date 2021-05-07 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2021-05-07 Time 10:25 Sent To  
Notes
2021-05-07 10:34:10ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 487 & 61G1 OR FS 471 &
 61G15
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-20 Cont ID  
Sent By rthermid Date 2021-05-20 Time   Rev Time  
Received By rthermid Date 2021-05-20 Time   Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy