Plan Review Details - Permit 21040564
Plan Review Stops For Permit 21040564
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2021-06-21 Cont ID  
Sent By rmcphers Date 2021-06-21 Time 10:24 Rev Time 0.00
Received By rmcphers Date 2021-06-21 Time 10:24 Sent To  
Notes
2021-06-21 10:25:16POLES ARE EXISTING

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-25 Cont ID  
Sent By rmcphers Date 2021-05-25 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2021-05-25 Time 15:25 Sent To  
Notes
2021-05-25 15:28:56LIGHT POST
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FOUNDATION PLAN SHOWS WIND DESIGN PER ASCE 7-10 -
 2020 FBC CHAPTER 35 SHOWS ASCE 7-16 TO BE USED FOR
 DESIGN.
  
2021-05-17 16:01:42ADDING LED FIXTURE TO POLE AFTER REMOVING GAS LANTERNS
 JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-17 Cont ID  
Sent By jleahy Date 2021-05-17 Time 16:13 Rev Time 0.00
Received By jleahy Date 2021-05-17 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-23 Cont ID  
Sent By jleahy Date 2021-04-23 Time 13:04 Rev Time 0.00
Received By jleahy Date 2021-04-23 Time 13:04 Sent To  
Notes
2021-04-23 13:07:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SIGN ELECTRICAL DRAWING.
  
 2) ARE YOU INSTALLING ALL NEW POLE? IF SO VALUE OF WORK
 IS LOW.
  
 3) WHAT KIND IF HEAD IS GOING ON PLOE?
  
 4) PLEASE INDICATE WIRE SIZES FOR POLES.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-06-23 Cont ID  
Sent By ccole Date 2021-06-23 Time 07:09 Rev Time 0.00
Received By jgomez Date 2021-06-22 Time 09:06 Sent To I
Notes
2021-06-23 17:22:55ENTERED THIS REVIEW FIELD BY MISTAKE. GAS REVIEW
 APPROVED BY CHRIS COLE ON 06/22/21. SEE STAMPED SITE
 PLAN UPLOADED TO PROJECTDOX ON 05/28/21. JG.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-05-14 Cont ID  
Sent By ccole Date 2021-05-14 Time 16:48 Rev Time 0.00
Received By ccole Date 2021-05-14 Time 16:36 Sent To  
Notes
2021-05-14 16:48:472ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21040564
 5/14/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW PRINTED BELOW STILL EXIST. NO NARRATIVE
 RESPONSES TO COMMENTS WERE SUBMITTED AS REQUESTED. THE
 REVIEW COMMENTS ARE BASED ON THE PERMIT APPLICATION
 WORK DESCRIPTION WHICH INDICATES CONVERSION OF THE GAS
 LIGHTS TO ELECTRIC.
  
 1) PROVIDE GAS PIPING AND EQUIPMENT DEMOLITION PLANS
 AND SUBMIT A GAS SUB-PERMIT APPLICATION- SECTIONS 105.1
 & 107.2.1 FBC FG.
  
 2) THE SCOPE OF WORK ON THE PLAN SHALL INDICATE
 COMPLIANCE WITH SECTION 404.15 FOR GAS PIPE CAPPING,
 AND SECTIONS 406.7.1.1 & 406.7.1.3 FOR GAS PIPING
 REMOVED FROM SERVICE REQUIREMENTS.
  
 406.7.1.1 REMOVAL FROM SERVICE.
 WHERE EXISTING GAS PIPING IS OPENED, THE SECTION THAT
 IS OPENED SHALL BE ISOLATED FROM THE GAS SUPPLY AND THE
 LINE PRESSURE VENTED IN ACCORDANCE WITH SECTION
 406.7.1.3. WHERE GAS PIPING MEETING THE CRITERIA OF
 TABLE 406.7.1.1 IS REMOVED FROM SERVICE, THE RESIDUAL
 FUEL GAS IN THE PIPING SHALL BE DISPLACED WITH AN INERT
 GAS.
 406.7.1.3 OUTDOOR DISCHARGE OF PURGED GASES.
 THE OPEN END OF A PIPING SYSTEM BEING PRESSURE VENTED
 OR PURGED SHALL DISCHARGE DIRECTLY TO AN OUTDOOR
 LOCATION. PURGING OPERATIONS SHALL COMPLY WITH ALL OF
 THE FOLLOWING REQUIREMENTS:
 1. 1. THE POINT OF DISCHARGE SHALL BE CONTROLLED WITH A
 SHUTOFF VALVE.
 2. 2. THE POINT OF DISCHARGE SHALL BE LOCATED NOT LESS
 THAN 10 FEET FROM SOURCES OF IGNITION, NOT LESS THAN 10
 FEET FROM BUILDING OPENINGS AND NOT LESS THAN 25 FEET
 FROM MECHANICAL AIR INTAKE OPENINGS.
 3. 3. DURING DISCHARGE, THE OPEN POINT OF DISCHARGE
 SHALL BE CONTINUOUSLY ATTENDED AND MONITORED WITH A
 COMBUSTIBLE GAS INDICATOR THAT COMPLIES WITH SECTION
 406.7.1.4.
 4. 4. PURGING OPERATIONS INTRODUCING FUEL GAS SHALL BE
 STOPPED WHEN 90 PERCENT FUEL GAS BY VOLUME IS DETECTED
 WITHIN THE PIPE.
 5. 5. PERSONS NOT INVOLVED IN THE PURGING OPERATIONS
 SHALL BE EVACUATED FROM ALL AREAS WITHIN 10 FEET (3048
 MM) OF THE POINT OF DISCHARGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-29 Cont ID  
Sent By ccole Date 2021-04-29 Time 08:31 Rev Time 0.00
Received By ccole Date 2021-04-29 Time 07:31 Sent To  
Notes
2021-04-29 08:32:031ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21040564
 4/29/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE GAS PIPING AND EQUIPMENT DEMOLITION PLANS
 AND SUBMIT A GAS SUB-PERMIT APPLICATION- SECTIONS 105.1
 & 107.2.1 FBC FG.
  
 2) THE SCOPE OF WORK ON THE PLAN SHALL INDICATE
 COMPLIANCE WITH SECTION 404.15 FOR GAS PIPE CAPPING,
 AND SECTIONS 406.7.1.1 & 406.7.1.3 FOR GAS PIPING
 REMOVED FROM SERVICE REQUIREMENTS.
 406.7.1.1 REMOVAL FROM SERVICE.
 WHERE EXISTING GAS PIPING IS OPENED, THE SECTION THAT
 IS OPENED SHALL BE ISOLATED FROM THE GAS SUPPLY AND THE
 LINE PRESSURE VENTED IN ACCORDANCE WITH SECTION
 406.7.1.3. WHERE GAS PIPING MEETING THE CRITERIA OF
 TABLE 406.7.1.1 IS REMOVED FROM SERVICE, THE RESIDUAL
 FUEL GAS IN THE PIPING SHALL BE DISPLACED WITH AN INERT
 GAS.
  
 406.7.1.3 OUTDOOR DISCHARGE OF PURGED GASES.
 THE OPEN END OF A PIPING SYSTEM BEING PRESSURE VENTED
 OR PURGED SHALL DISCHARGE DIRECTLY TO AN OUTDOOR
 LOCATION. PURGING OPERATIONS SHALL COMPLY WITH ALL OF
 THE FOLLOWING REQUIREMENTS:
 1. 1. THE POINT OF DISCHARGE SHALL BE CONTROLLED WITH A
 SHUTOFF VALVE.
 2. 2. THE POINT OF DISCHARGE SHALL BE LOCATED NOT LESS
 THAN 10 FEET FROM SOURCES OF IGNITION, NOT LESS THAN 10
 FEET FROM BUILDING OPENINGS AND NOT LESS THAN 25 FEET
 FROM MECHANICAL AIR INTAKE OPENINGS.
 3. 3. DURING DISCHARGE, THE OPEN POINT OF DISCHARGE
 SHALL BE CONTINUOUSLY ATTENDED AND MONITORED WITH A
 COMBUSTIBLE GAS INDICATOR THAT COMPLIES WITH SECTION
 406.7.1.4.
 4. 4. PURGING OPERATIONS INTRODUCING FUEL GAS SHALL BE
 STOPPED WHEN 90 PERCENT FUEL GAS BY VOLUME IS DETECTED
 WITHIN THE PIPE.
 5. 5. PERSONS NOT INVOLVED IN THE PURGING OPERATIONS
 SHALL BE EVACUATED FROM ALL AREAS WITHIN 10 FEET (3048
 MM) OF THE POINT OF DISCHARGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
2021-04-23 13:09:45DO THEY NEED A GAS PERMIT TO DISCONNECT ALL THE OLD
 LIGHT POLES (GAS).

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-23 Cont ID  
Sent By jgomez Date 2021-06-23 Time 17:22 Rev Time 0.00
Received By jleahy Date 2021-05-28 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-25 Cont ID  
Sent By rmcphers Date 2021-05-25 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2021-05-05 Time 08:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-04-29 Time   Rev Time 0.00
Received By cdecoeur Date 2021-04-09 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-06-22 Cont ID  
Sent By ccole Date 2021-06-22 Time 09:37 Rev Time 0.00
Received By ccole Date 2021-06-22 Time 09:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-05-14 Cont ID  
Sent By ccole Date 2021-05-14 Time 16:36 Rev Time 0.00
Received By ccole Date 2021-05-14 Time 16:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-29 Cont ID  
Sent By ccole Date 2021-04-29 Time 08:31 Rev Time 0.00
Received By ccole Date 2021-04-29 Time 07:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-06-21 Cont ID  
Sent By rmcphers Date 2021-06-21 Time 10:27 Rev Time 0.00
Received By rmcphers Date 2021-06-21 Time 10:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-25 Cont ID  
Sent By rmcphers Date 2021-05-25 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2021-05-25 Time 15:29 Sent To  
Notes
2021-05-25 15:29:50SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-23 Cont ID  
Sent By jleahy Date 2021-04-23 Time 13:08 Rev Time 0.00
Received By jleahy Date 2021-04-23 Time 13:08 Sent To  
Notes
2021-04-23 13:08:51NO SIGNATURE ON ELECTRICAL PLAN.