Plan Review Details - Permit 21040041
Plan Review Stops For Permit 21040041
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-30 Cont ID  
Sent By cwalker Date 2021-04-30 Time   Rev Time 0.00
Received By cwalker Date 2021-04-30 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-15 Cont ID  
Sent By medwards Date 2021-06-15 Time 11:22 Rev Time 0.00
Received By medwards Date 2021-06-07 Time 08:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-12 Cont ID  
Sent By medwards Date 2021-05-12 Time 13:25 Rev Time 0.00
Received By medwards Date 2021-04-29 Time 10:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-15 Cont ID  
Sent By medwards Date 2021-06-15 Time 11:22 Rev Time 0.00
Received By medwards Date 2021-06-15 Time 11:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By medwards Date 2021-05-12 Time 13:21 Rev Time 0.00
Received By medwards Date 2021-05-12 Time 11:05 Sent To  
Notes
2021-05-12 13:21:541ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21040041
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: SF-1 MUST MEET FBC M 508.1.1
 508.1.1 MAKEUP AIR TEMPERATURE. THE TEMPERATURE
 DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE
 CONDITIONED SPACE SHALL NOT EXCEED 10?F (6?C) EXCEPT
 WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP
 AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM.
  
 2) SHEET M-6: PLEASE SHOW ON THE DRAWINGS THAT THE
 SUPPLY AIR FOR THE MAKE UP AIR IS A MINIMUM OF 10 FT.
 FROM ANY EXHAUST OR PLUMBING VENTS. FBC M 401.4
  
 3) SHEET M-7: IT APPEARS THAT THE DESIGNER IS CALLING
 OUT BOTH 1 INCH THICK 22 GA. GALVANIZED STEEL MINERAL
 WOOL PANEL TO PROTECT COMBUSTIBLES FROM DUCT AND UL
 APPROVED FIRE BARRIER WRAP. ARE BOTH REQUIRED FOR THIS
 DESIGN? IF NOT PLEASE REMOVE THE DESIGN NOT USED. FBC
 107.2.1
  
 4) PLEASE PROVIDE VENTING SPECIFICATIONS FOR THE FBM
 BAKING MACHINE AND THE SINGLE RACK OVEN. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-12 Cont ID  
Sent By medwards Date 2021-05-12 Time 13:25 Rev Time 0.00
Received By medwards Date 2021-05-12 Time 13:25 Sent To  
Notes
***NONE***