Plan Review Details - Permit 21040007
Plan Review Stops For Permit 21040007
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-05-27 Cont ID  
Sent By rmcphers Date 2021-05-27 Time 09:24 Rev Time 0.00
Received By rmcphers Date 2021-05-27 Time 09:24 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-25 Cont ID  
Sent By rmcphers Date 2021-05-25 Time 16:41 Rev Time 0.00
Received By rmcphers Date 2021-05-25 Time 16:41 Sent To  
Notes
2021-05-25 16:42:20PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 20:54 Rev Time 0.00
Received By shill Date 2021-06-11 Time 20:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-25 Cont ID  
Sent By rmcphers Date 2021-05-25 Time 16:38 Rev Time 0.00
Received By rmcphers Date 2021-05-25 Time 16:38 Sent To  
Notes
2021-05-25 16:41:47CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW SHOWER WALL FINISHES TO COMPLY WITH FBC
 1210.2.3 SHOWERS.
 SHOWER COMPARTMENTS AND WALLS ABOVE BATHTUBS WITH
 INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH,
 NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72
 INCHES (1829 MM) ABOVE THE DRAIN INLET.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-09 Cont ID  
Sent By jleahy Date 2021-06-09 Time 09:05 Rev Time 0.00
Received By jleahy Date 2021-06-09 Time 08:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-17 Cont ID  
Sent By jleahy Date 2021-05-17 Time 07:13 Rev Time 0.00
Received By jleahy Date 2021-05-17 Time 07:08 Sent To  
Notes
2021-05-17 07:23:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 KITCHEN PENINSULAR NEXT TO RANGE NEEDS AN OUTLET TO
 SERVE COUNTER TOP. SPACE NEXT TO RANGE IS MORE THAN 12"
 AN OUTLET IS REQUIRED THERE ALSO.
  
 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH PENINSULAR
 COUNTERTOP LONG DIMENSION SPACE WITH A LONG DIMENSION
 OF 600 MM (24 IN.) OR GREATER AND A SHORT DIMENSION OF
 300 MM (12 IN.) OR GREATER. A PENINSULAR COUNTERTOP IS
 MEASURED FROM THE CONNECTED PERPENDICULAR WALL.
 (4) SEPARATE SPACES. COUNTERTOP SPACES SEPARATED BY
 RANGETOPS, REFRIGERATORS, OR SINKS SHALL BE CONSIDERED
 AS SEPARATE COUNTERTOP SPACES IN APPLYING THE
 REQUIREMENTS OF 210.52(C)(1). IF A RANGE,
 COUNTER-MOUNTED COOKING UNIT, OR SINK IS INSTALLED IN
 AN ISLAND OR PENINSULAR COUNTERTOP AND THE DEPTH OF THE
 COUNTERTOP BEHIND THE RANGE, COUNTER-MOUNTED COOKING
 UNIT, OR SINK IS LESS THAN 300 MM (12 IN.), THE RANGE,
 COUNTER-MOUNTED COOKING UNIT, OR SINK SHALL BE
 CONSIDERED TO DIVIDE THE COUNTERTOP SPACE INTO TWO
 SEPARATE COUNTERTOP SPACES. EACH SEPARATE COUNTERTOP
 SPACE SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS IN
 210.52(C).

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-05-12 Cont ID  
Sent By cwalker Date 2021-05-12 Time   Rev Time 0.00
Received By cwalker Date 2021-05-12 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 20:55 Rev Time 0.00
Received By shill Date 2021-06-04 Time 13:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-25 Cont ID  
Sent By rmcphers Date 2021-05-25 Time 16:42 Rev Time 0.00
Received By rmcphers Date 2021-05-10 Time 10:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-05-17 Cont ID  
Sent By ccole Date 2021-05-17 Time 08:56 Rev Time 0.00
Received By ccole Date 2021-05-17 Time 07:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 20:55 Rev Time 0.00
Received By shill Date 2021-06-11 Time 20:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-25 Cont ID  
Sent By rmcphers Date 2021-05-25 Time 16:42 Rev Time 0.00
Received By rmcphers Date 2021-05-25 Time 16:42 Sent To  
Notes
2021-05-25 16:42:50SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL