Plan Review Details - Permit 21031672
Plan Review Stops For Permit 21031672
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-09-14 Cont ID  
Sent By rmcphers Date 2021-09-14 Time 15:49 Rev Time 0.00
Received By rmcphers Date 2021-09-14 Time 15:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-30 Cont ID  
Sent By rmcphers Date 2021-04-30 Time 08:52 Rev Time 0.00
Received By rmcphers Date 2021-04-30 Time 08:10 Sent To  
Notes
2021-04-30 08:52:24ROOF TOP GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE DETAILS FOR THE REQUIRED GUARD RAIL
 OR SHOW DETAILS ON THE DRAWINGS THAT A GUARD RAIL IS
 NOT REQUIRED. FBC 1015.6 MECHANICAL EQUIPMENT, SYSTEMS
 AND DEVICES.
 GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND
 EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-26 Cont ID  
Sent By jleahy Date 2021-04-26 Time 17:26 Rev Time 0.00
Received By jleahy Date 2021-04-26 Time 17:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-24 Cont ID  
Sent By pleduc Date 2021-08-24 Time   Rev Time 0.00
Received By pleduc Date 2021-08-24 Time 11:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-28 Cont ID  
Sent By pleduc Date 2021-04-28 Time   Rev Time 0.00
Received By pleduc Date 2021-04-28 Time 10:21 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-09-13 Cont ID  
Sent By ccole Date 2021-09-13 Time 12:25 Rev Time 0.00
Received By ccole Date 2021-09-13 Time 12:00 Sent To  
Notes
2021-09-13 12:25:162ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21031672
 9/13/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW- PLEASE COMPLY.
  
 2) P2: PROVIDE SUPPORT AND HANGING DETAILS FOR THE GAS
 PIPING- SECTIONS 404.9, 4107.2, & 415.1 FBC FG.
  
 A) PROVIDE A DETAIL SHOWING THE TYPE, SIZE, AND SPACING
 OF HANGERS TO ATTACH THE PIPE ALONG THE FACE OF THE
 BUILDING.
  
 B) PROVIDE A DETAIL SHOWING THE TYPE, SIZE, SPACING OF
 SUPPORTS TO ANCHOR THE PIPE ALONG THE ROOF SURFACE.
  
 3) PROVIDE A COPY OF A SURVEY DRAWING MARKED UP TO SHOW
 THE LOCATION OF THE NEW METER- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-26 Cont ID  
Sent By ccole Date 2021-04-26 Time 08:25 Rev Time 0.00
Received By ccole Date 2021-04-26 Time 07:06 Sent To  
Notes
2021-04-26 08:25:471ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21031672
 4/26/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1 GAS RISER:
 A) SHOW THE UTILITY REGULATOR AT METER- SECTION 402.2
 FBC FG.
 B) LIST THE MAKE AND MODEL OF THE REGULATOR AT THE
 GENERATOR AND SUBMIT MANUFACTURER'S SPECIFICATIONS.
 PLEASE MARK OR HIGHLIGHT THE SPECS TO SHOW THE SELECTED
 MODEL, INLET AND OUTLET PIPE SIZES AND PRESSURES-
 SECTION 410.2.
 C) INDICATE A TEST TEE FITTING WITH ONE OPENING CAPPED
 OR PLUGGED WILL BE INSTALLED BETWEEN THE REGULATOR AND
 THE UPSTREAM SHUTOFF VALVE- SECTION 410.2 (5 & 6).
 D) INDICATE PIPE UNIONS WILL BE INSTALLED WITHIN 1 FT.
 OF EITHER SIDE OF THE REGULATOR- SECTION 410.2 (7).
  
 2) P2: PROVIDE SUPPORT AND HANGING DETAILS FOR THE GAS
 PIPING- SECTIONS 404.9, 4107.2, & 415.1 FBC FG.
 A) PROVIDE A DETAIL SHOWING THE TYPE, SIZE, AND SPACING
 OF HANGERS TO ATTACH THE PIPE ALONG THE FACE OF THE
 BUILDING.
 B) PROVIDE A DETAIL SHOWING THE TYPE, SIZE, SPACING OF
 SUPPORTS TO ANCHOR THE PIPE ALONG THE ROOF SURFACE.
  
 3) PROVIDE A COPY OF A SURVEY DRAWING MARKED UP TO SHOW
 THE LOCATION OF THE NEW METER- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-14 Cont ID  
Sent By rmcphers Date 2021-09-14 Time 15:53 Rev Time 0.00
Received By rmcphers Date 2021-08-23 Time 07:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-20 Cont ID  
Sent By cthroop Date 2021-05-20 Time 11:30 Rev Time 0.00
Received By cthroop Date 2021-04-14 Time 08:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-09-13 Cont ID  
Sent By ccole Date 2021-09-13 Time 12:01 Rev Time 0.00
Received By ccole Date 2021-09-13 Time 12:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-26 Cont ID  
Sent By ccole Date 2021-04-26 Time 08:25 Rev Time 0.00
Received By ccole Date 2021-04-26 Time 07:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-14 Cont ID  
Sent By rmcphers Date 2021-09-14 Time 15:52 Rev Time 0.00
Received By rmcphers Date 2021-09-14 Time 15:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-30 Cont ID  
Sent By rmcphers Date 2021-04-30 Time 08:52 Rev Time 0.00
Received By rmcphers Date 2021-04-30 Time 08:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-09-01 Cont ID  
Sent By ckimmerl Date 2021-09-01 Time 09:14 Rev Time 0.00
Received By ckimmerl Date 2021-09-01 Time 09:14 Sent To  
Notes
2021-09-01 09:12:39SEC. 94-109. - DEFINITIONS AND MINIMUM REQUIREMENTS. >
 PROJECTION, VERTICAL - 1. MECHANICAL EQUIPMENT AND
 APPURTENANCES NECESSARY TO THE OPERATION OR MAINTENANCE
 OF THE BUILDING OR STRUCTURE ITSELF SUCH AS, BUT NOT
 LIMITED TO, COOLING TOWERS, ELEVATORS, STAIRS AND
 MECHANICAL PENTHOUSES, VENT STACKS AND ANTENNAS SHALL
 BE ENCLOSED AND SCREENED IN SUCH A MANNER THAT THE
 ENCLOSURE IS DESIGNED AS AN INTEGRAL PART OF THE
 OVERALL BUILDING DESIGN.
  
 - SCREEN IS REQUIRED FOR THE PROPOSED GAS GENERATOR,
 THE SCREEN SHALL BE AT A MINIMUM EQUAL IN HEIGHT TO THE
 GAS GENERATOR ITSELF.

Review Stop Z ZONING
Rev No 1 Status F Date 2021-05-19 Cont ID  
Sent By aaponte Date 2021-05-19 Time 11:37 Rev Time 0.00
Received By aaponte Date 2021-05-19 Time 11:37 Sent To  
Notes
2021-05-19 11:38:20NEW GAS GENERATOR SHALL BE SCREENED FROM VIEW WITH A
 SCREEN AS TALL AS THE PROPOSED EQUIPMENT.
 FOR ADDITONAL INFORMATIION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.