Plan Review Details - Permit 21031651
Plan Review Stops For Permit 21031651
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 13:17 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 13:17 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-08-19 Cont ID  
Sent By rmcphers Date 2021-08-19 Time 07:50 Rev Time 0.00
Received By rmcphers Date 2021-08-19 Time 07:50 Sent To  
Notes
2021-08-19 07:52:10PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-07-12 Cont ID  
Sent By rmcphers Date 2021-07-12 Time 15:41 Rev Time 0.00
Received By rmcphers Date 2021-07-12 Time 15:41 Sent To  
Notes
2021-07-12 15:42:27PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By rmcphers Date 2021-05-12 Time 16:48 Rev Time 0.00
Received By rmcphers Date 2021-05-12 Time 16:48 Sent To  
Notes
2021-05-12 16:49:02PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 13:14 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 13:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-08-19 Cont ID  
Sent By rmcphers Date 2021-08-19 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2021-08-19 Time 07:52 Sent To  
Notes
2021-08-19 07:55:10CHANGE OF OCCUPANCY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE WINDOW SCHEDULE DOESN'T SEEM TO MATCH THE FLOOR
 PLAN - PLEASE CORRECT.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-12 Cont ID  
Sent By rmcphers Date 2021-07-12 Time 15:42 Rev Time 0.00
Received By rmcphers Date 2021-07-12 Time 15:42 Sent To  
Notes
2021-07-12 15:51:05CHANGE OF OCCUPANCY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A WINDOW SCHEDULE SHOWING THE SIZES
 OF THE EXTERIOR WINDOWS TO BE REPLACED.
 2) PLEASE SHOW ACCESSIBLE REST ROOM MIRROR MAX. HEIGHT
 TO THE REFLECTIVE SURFACE FBC A603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By rmcphers Date 2021-05-12 Time 16:48 Rev Time 0.00
Received By rmcphers Date 2021-05-12 Time 14:26 Sent To  
Notes
2021-05-12 16:30:58CHANGE OF OCCUPANCY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING 1 OF 9 FLOOR PLAN SHOWS "PROPOSED OCCUPANCY"
 AS "B" - PLEASE REMOVE OR CORRECT TO A-2.
 2) PLEASE SHOW CEILING HEIGHTS AND BOTTOM OF FALSE BEAM
 HEIGHTS - FBC 1208.2
 3) PLEASE PROVIDE A WINDOW SCHEDULE SHOWING THE SIZES
 OF THE EXTERIOR WINDOWS TO BE REPLACED.
 4) PLEASE SHOW THE TOILET PAPER DISPENSER LOCATION (7-9
 INCHES TO THE CENTER OF THE DISPENSER) FROM THE FACE OF
 THE TOILET TO COMPLY WITH FBC A604.7
 5) ACCESSIBLE REST ROOM DOOR CANNOT SWING INTO THE
 FIXTURE CLEAR FLOOR SPACE - SEE EXCEPTION AND SHOW THE
 REQUIRED FLOOR SPACE FBC A603.2.3
 6) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND
 DOORS. ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 MARKED APPROVED BY THE DESIGNER OF RECORD. FBC 107.3.4

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-04 Cont ID  
Sent By jleahy Date 2021-05-04 Time 13:33 Rev Time 0.00
Received By jleahy Date 2021-05-04 Time 13:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-07-06 Cont ID  
Sent By cwalker Date 2021-07-06 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-29 Cont ID  
Sent By cwalker Date 2021-04-29 Time   Rev Time 0.00
Received By cwalker Date 2021-04-29 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 13:18 Rev Time 0.00
Received By rmcphers Date 2021-12-10 Time 06:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-23 Cont ID  
Sent By medwards Date 2021-11-23 Time 15:11 Rev Time 0.00
Received By medwards Date 2021-11-23 Time 15:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-20 Cont ID  
Sent By medwards Date 2021-08-20 Time 14:28 Rev Time 0.00
Received By medwards Date 2021-07-30 Time 10:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-20 Cont ID  
Sent By jesmith Date 2021-07-20 Time 16:51 Rev Time 0.00
Received By jesmith Date 2021-07-20 Time 16:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-24 Cont ID  
Sent By ccole Date 2021-05-24 Time 13:38 Rev Time 0.00
Received By ccole Date 2021-04-07 Time 10:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-12-22 Cont ID  
Sent By lmarchan Date 2021-12-22 Time 15:55 Rev Time 0.00
Received By lmarchan Date 2021-12-17 Time 08:49 Sent To  
Notes
2021-12-22 15:56:08NO FEES DUE FOR IMPACT. LEM
2021-12-17 08:40:4112/17/2021 EMAILED IMPACT FOR REVIEW AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By rmcphers Date 2021-05-12 Time 16:49 Rev Time 0.00
Received By rmcphers Date 2021-05-12 Time 16:49 Sent To  
Notes
2021-05-12 16:50:07CHANGE OF OCCUPANCY -
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-11-23 Cont ID  
Sent By medwards Date 2021-11-23 Time 15:10 Rev Time 0.00
Received By medwards Date 2021-11-23 Time 15:10 Sent To  
Notes
2021-11-23 15:13:35APPROVED WITH PRIVISO:
 PER CONVERSATION WITH PETE RUSSO BOTH MECHANICAL UNITS
 WILL BE 4-TONS.
 WINE COOLER WILL BE A SEPARATE PERMIT AND REVIEW. ME

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-08-20 Cont ID  
Sent By medwards Date 2021-08-20 Time 14:21 Rev Time 0.00
Received By medwards Date 2021-08-20 Time 14:12 Sent To  
Notes
2021-08-20 14:20:453RD REVIEW FBC-2020 MECHANICAL
 PERMIT-21031651
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 9 OF ( THE MECHANICAL DRAWING CLEARLY
 INDICATES A NEW 5-TON UNIT AND THE REPLACEMENT OF THE
 4-TON UNIT. PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 2) THIS APPEARS TO BE A CHANGE OF USE FROM BUSINESS TO
 A-2. THE CHANGE OF USE FROM AN OFFICE TO A
 RESTAURANT/LOUNGE WOULD REQUIRE A MECHANICAL LOAD
 CALCULATION AND WOULD REQUIRE AN OUTDOOR AIR
 CALCULATION FOR THIS NEW USE OF SPACE. I DO NOT SEE A
 MUA FOR THE HOOD ( NOT REQUIRED ON THIS PERMIT BUT AN
 OBSERVATION) SO ARE THE AHU?S MAKING UP FOR THE HOOD?
 FBC 107.2.1 AND FBC M 508
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-07-09 Cont ID  
Sent By medwards Date 2021-07-09 Time 09:08 Rev Time 0.00
Received By medwards Date 2021-07-09 Time 09:08 Sent To  
Notes
2021-07-09 09:08:332ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21031651
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL DESIGNER MUST DIGITALLY SIGN THE
 MECHANICAL SIZING CALCULATIONS OR THE MECHANICAL
 CONTRACTOR THAT HOLDS THE PERMIT TO DO THE WORK ON THIS
 PROJECT CAN PRINT AND SIGN THEIR NAME ON THE DOCUMENT.
 FS 471.003(H)
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE
 USE OF SPACE IN EACH AREA OF THIS BUILDING IE KITCHEN,
 EXCEPT FOR THE WINE CELLAR REVIEWER CONSIDERS THIS AREA
 AS A WALK IN COOLER WHICH WILL HAVE SEPARATE PERMITS
 AND REVIEWS. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 3) IS THERE GONG TO BE A SMOKING LOUNGE? IF SO PLEASE
 REFLECT THIS IN THE OUTDOOR AIR CALCULATIONS. FBC M
 TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 13:22 Rev Time 0.00
Received By medwards Date 2021-05-04 Time 12:36 Sent To  
Notes
2021-05-04 13:23:071ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21031651
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE INCLUDE A NOTE ON THE DRAWINGS THAT THE
 KITCHEN HOOD AND REFRIGERATION WILL REQUIRE SEPARATE
 PERMITS AND PLAN REVIEWS. FBC 107.2.1
  
 3) ACCORDING TO GIS THERE ARE 2 STRUCTURES ON THIS
 PARCEL, PLEASE PROVIDE ADDRESS AND IDENTIFICATION AS TO
 WHICH BUILDING IS PERMITTED ON THIS PROJECT. FBC
 107.2.1
  
 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS CHANGE OF USE. FBC M 312 AND FBC
 EC C403.2.1
  
 5) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON
 EACH USE OF SPACE I.E. KITCHEN, SINCE THIS IS A SOCIAL
 CLUB WITH ALCOHOL PLEASE FIGURE THE LARGE SITTING AREA
 AS A BAR, STORAGE. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 6) MECHANICAL SHEET: PLEASE LABEL EACH AHU CLEARLY, THE
 ONE ON THE LEFT APPEARS TO BE NAMED BOTH AHU-1 AND
 AHU-2. FBC 107.2.1
  
 7) PLEASE REMOVE THE RETURN IN THE KITCHEN AREAS AS YOU
 CANNOT TAKE RETURN AIR FROM A KITCHEN. FBC M 601.5 (7)
  
 8) PLEASE SHOW OUTDOOR AIR DUCT FOR AHU-2 RETURN. FBC
 107.2.1
  
 9) PLEASE SHOW CONDENSATE LINE FOR AHU-2 AND
 TERMINATION LOCATION. FBC M 307
  
 10) PLEASE EXPLAIN, IS THE ?WINE CELLAR? A PIECE OF
 REFRIGERATION EQUIPMENT? IF SO PLEASE PROVIDE THE
 SPECIFICATIONS FOR THIS PIECE OF EQUIPMENT. FBC 107.2.1
  
 11) PROVIDE EQUIPMENT SIZING CALCULATIONS FOR WINE AHU.
 FBC M 312 AND FBC EC C403.2.1
  
 12) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THE
 WINE ROOM. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 13) PLEASE SHOW THE BATH EXHAUST FAN AND THE CFM?S. FBC
 M TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-08-10 Cont ID  
Sent By pvalenti Date 2021-08-10 Time 12:43 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 15:15 Sent To  
Notes
2021-08-10 12:44:20PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21031651 1254 OKEECHOBEE RD

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-07-20 Cont ID  
Sent By jesmith Date 2021-07-20 Time 16:08 Rev Time 0.00
Received By jesmith Date 2021-07-15 Time 11:58 Sent To  
Notes
2021-07-20 16:06:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 PROVISO: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1,
 PROVIDE AS A DEFERRED SUBMITTAL MANUFACTURER?S
 SPECIFICATION AND INSTALLATION GUIDE FOR THE
 MANUFACTURER'S SPEC/INSTALLATION MANUALS FOR WATER
 HEATERS. DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON
 SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN
 RISK.
  
 1.SECOND REQUEST: THE CENTERLINE OF THE WATER CLOSET
 SHALL BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM
 THE SIDE WALL OR PARTITION PER FBC ACC 604.2
  
 2.SECOND REQUEST: PER FBC 606.5 EXPOSED PIPES AND
 SURFACES. EXPOSED WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
  
 3.SECOND REQUEST: MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND
  
 4. THERE IS A KITCHEN WHICH INCLUDES A RANGE WITH A
 GREASE HOOD, AN APPARENT KITCHEN SINK WITH DISHWASHER.
 APPARENTLY, THERE WILL BE FOOD PREP. PER WPB FBC
 107.2.1, PROVIDE A GREASE INTERCEPTOR TO COMPLY WITH
 THE REQUIREMENTS OF FBC PL 1003.3.1. PER WPB FBC
 107.2.1, PROVIDE A SPECIFICATION, SCHEDULE, DETAIL AND
 CALCULATIONS FOR THE SAME. PLEASE NOTE, PER FBC PL
 1003.3.2, A FOOD WASTE DISPOSER SHALL NOT DISCHARGE TO
 A GREASE INTERCEPTOR.
 -GREASE INTERCEPTOR IS PROVIDED
 -SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 CALCULATIONS FOR GREASE INTERCEPTOR.
 -NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE DETAIL FOR
 UNDER GROUND GREASE INTERCEPTOR; CONCRETE PIT W/FOOT
 TRAFFIC LID FOR ACCESS? PROVIDE REBAR REINFORCEMENT
 DETAILS.
  
 5. SECOND REQUEST; PER WPB FBC 107.2.1, SUBMIT FOR
 REVIEW MANUFACTURER'S SPEC/INSTALLATION MANUAL FOR
 DISHWASHER. APPROVED MANUFACTURER'S SPEC/INSTALLATION
 MANUALS SHALL BE ON SITE PRIOR TO INSPECTION. PROVIDE
 SCHEDULE FOR THE SAME; ITEM SHALL COMPLY WITH FBC PL
 409.1; INDICATE APPROPRIATE STANDARDS FOR MACHINE.
 PROVIDE DETAIL FOR PLUMBING CONNECTIONS; COMPLY WITH
 REQUIREMENTS OF FBC PL 409.2, 409.3 AND 409.4 AS IS
 APPLICABLE.
 -RESPONSE INDICATES SUBMITTAL FOR DISHWASHER WAS
 INCLUDED FOR REVIEW. I CANNOT FIND.
  
 6. THE PLUMBING PLAN INDICATES THAT THE APPARENT
 KITCHEN SINK IN THE KITCHEN IS A SERVICE SINK. THE
 INTENT OF THE REQUIRED SERVICE SINK AS REQUIRED IN FBC
 PL TABLE 403.1, IS TO PROVIDE A SUITABLE FIXTURE FOR
 CUSTODIAL DUTIES/SERVICES. PER WPB FBC 107.2.1. PROVIDE
 A DESIGNATED SERVICE SINK THAT WILL MEET THE CRITERIA.
 PROVIDE A DETAIL FOR THE SAME. COMPLIED
 -NEW COMMENT: THE THREE-COMPARTMENT SINK DISCHARGING TO
 THE GREASE INTERCEPTOR THROUGH A FLOOR SINK NEEDS TO BE
 DESIGNATED A POT SINK; WPB FBC 107.2.1. THE FLOOR SINK
 SHALL BE VENTED WITH AN INDIVIDUAL VENT CONNECTING TO
 EXISTING VENT SYSTEM; FBC PL 909.1, 904.1. PROVIDE
 INDIRECT WASTE TO FLOOR SINK W/AIR GAP; FBC PL 802.1.7.
 -THE DISHWASHER SHALL ALSO DISCHARGE TO THE FLOOR SINK.
 PROVIDE INDIRECT WASTE TO FLOOR SINK W/AIR GAP; FBC PL
 802.1.7.
 -PER WPB FBC 107.2.1, PROVIDE A DETAIL SHOWING
 DISCHARGE OF BOTH TO FLOOR SINK.
 -NEW COMMENT: HAND SINK AND NEW MOP SINK SHALL NOT
 DISCHARGE TO THE GREASE INTERCEPTOR; FBC PL 1003.2.
 -NEW COMMENT: THE MOP SINK SHALL NOT BE WET VENTED BY
 THE HAND SINK; FBC PL 912.1. PROVIDE INDIVIDUAL VENT
 FOR MOP SINK; FBC 909.1 OR PROVIDE COMMON VENT; FBC PL
 911. SEE RED LINED DRAWING 10-P PLUMBING RISERS.
  
 7. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE FINISH
 WALL SCHEDULES FOR TOILET ROOMS AND SERVICE SINK.
 COMPLY WITH FBC PL 310.3 AND FBC 1210.2.2. WALLS AND
 PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 STIPULATES THAT
 THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION IS
 THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE
 THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL COULD
 BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
 -RESPONSE: FINISHES ON THE PLAN. I CAN NOT FIND. PER
 WPB FBC 107.2.1, PLEASE INDICATE WHICH PLAN SHEET AND
 CLOUD THE NOTE(S)/SCHEDULE. PLEASE NOTE, THE ADDED MOP
 SINK SHALL ALSO COMPLY WITH FBC PL 310.3 AND FBC
 1210.2.2.
  
 8. COMPLIED
  
 9. COMPLIED
  
 10.SECOND REQUEST; PER WPB FBC 107.2.1, PROVIDE
 EQUIPMENT SCHEDULE FOR ACCUMIX TANKLESS WATER HEATER
 INDICATING MANUFACTURER, MODEL NUMBER, GPM AND
 ELECTRICAL CHARACTERISTICS; PROVIDE DETAIL. IF IT IS
 ALSO A WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS
 TO ASSE 1070, PROVIDE NOTE.
 -NEW COMMENT: DELETE MULTIPLE FIXTURES WATER TEMPERING
 DEVICE DETAIL; WPB FBC 107.2.1
  
 11. SEE PROVISO REGARDING DEFERRED SUBMITTALS: PER WPB
 FBC 107.2.1, PROVIDE EQUIPMENT SCHEDULE FOR TANK TYPE
 WATER HEATER INDICATING MANUFACTURER, MODEL NUMBER,
 STORAGE CAPACITY AND ELECTRICAL CHARACTERISTICS. ALL
 DRAWINGS/SCHEDULE OF TANK TYPE WATER HEATER STORAGE
 CAPACITY SHALL BE CONSISTENT WITH EACH OTHER.
  
 12. COMPLIED
  
 13.REGARDING NEW WATER HEATER DETAIL
 -PER WPB FBC 107.2.1, SPECIFY AND SIZE THE EXPANSION
 TANK.
 -RELIEF LINE SHALL DISCHARGE FULL SIZE TO PAN THROUGH
 AIR GAP OR TO THE EXTERIOR; FBC PL 504.6
 -REMOVE ALL REFERENCES TO RECIRCULATING PUMP
 -PROVIDE PAN W/3/4 INCH DRAIN TO EXTERIOR; 504.7
  
 14. COMPLIED
  
 15. ORIGINAL REQUEST: PER WPB FBC 107.2.1, PROVIDE
 PLUMBING/EQUIPMENT/ FIXTURE SCHEDULE TO INCLUDE NEW AND
 REMAINING EXISTING FIXTURES, EQUIPMENT INCLUDING
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 AS REQUIRED BY FBC PL 419.5,
 607.1.2 AND WATER-HAMMER ARRESTORS THAT CONFORM TO ASSE
 1010 AS REQUIRED FOR QUICK-CLOSING VALVES INCLUDING
 DISHWASHERS BY FBC PL 604.9. ADDITIONALLY, SHOW
 LOCATIONS ON RISER DIAGRAM AND IDENTIFY THE SAME.
 -NEW COMMENT: ICE MAKER IS NOTED IN RESPONSE BUT IS NOT
 INDICATED ON THE PLANS. PER WPB FBC 107.2.1, PROVIDE
 PLUMBING/EQUIPMENT/ FIXTURE SCHEDULE TO INCLUDE NEW AND
 REMAINING EXISTING FIXTURES.
 -PER WPB FBC 107.2.1, IDENTIFY ICE MAKER ON THE PLANS;
 PROVIDE DRAIN AND WATER. PROVIDE BACKFLOW PROTECTION IN
 THE COLD WATER SUPPLY PER FBC PL 608.1 AND INDIRECT
 WASTE TO A TRAPPED AND VENTED WASTE RECEPTACLE (HUB
 DRAIN IS ACCEPTABLE) PER FBC PL 802 (WASTE RECEPTACLE
 SHALL BE READILY ACCESSIBLE). ICE MACHINE SHALL NOT
 DISCHARGE TO THE GREASE INTERCEPTOR; FBC PL 1003.2.
 -WATER HAMMER ARRESTORS FOR DISHWASHER AND ICE MACHINE
 ARE NOT NOTED
  
 16.PER WPB FBC 107.2.1, PROVIDE SIZE OF EXISTING
 INCOMING WATER SERVICE AND SHOW LOCATION, TYPE AND SIZE
 OF EXISTING BACKFLOW PREVENTOR FOR WATER SERVICE.
 -NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE A DETAIL AND
 SPEC FOR NEW BFP. NEW BFP REQUIRES A SEPARATE PERMIT.
  
 17.SECOND REQUEST: PER WPB FBC 107.2.1, REVISE NOTE 11
 BY REPLACING THE DESIGNATED M COPPER WITH L AS PER
 COPPER & COPPER ALLOY TUBE AND PIPE STANDARDS PUBLISHED
 BY THE COPPER DEVELOPMENT ASSOCIATION STATES "SEAMLESS
 COPPER WATER TUBE IS MANUFACTURED IN SIZES 1/4 INCH
 THROUGH 12 INCH NOMINAL. TYPES K AND L ARE MANUFACTURED
 IN DRAWN TEMPER (HARD) 1/4 INCH THROUGH 12 INCH AND
 ANNEALED TEMPER (SOFT) COILS 1/4 INCH THROUGH 2 INCH
 WHILE TYPE M IS ONLY MANUFACTURED IN DRAWN (HARD)
 TEMPER 1/4 INCH THROUGH 12 INCH."
  
 18. COMPLIED
  
 19. COMPLIED
  
 20. COMPLIED
  
 21. COMPLIED
  
 22. COMPLIED.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21031651 1254 OKEECHOBEE RD
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-05-04 Cont ID  
Sent By jesmith Date 2021-05-04 Time 14:55 Rev Time 0.00
Received By jesmith Date 2021-04-29 Time 16:09 Sent To  
Notes
2021-05-04 14:20:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW'PLUMBING COMMENTS:
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 CHANGE OCCUPANCY FROM BUSINESS TO A2 ASSEMBLY. ALL
 INFRASTRUCTURE SHALL COMPLY WITH 2020 FLORIDA BUILDING
 CODES.
  
 1. PER WPB FBC 107.2.1, PROVIDE DEMO PLAN SHOWING
 EXISTING CONDITIONS.
  
 2. PER FBC PL TABLE 403.1, SEPARATE TOILET FACILITIES
 ARE BE REQUIRED FOR MEN AND WOMEN. FBC ACC 213 REQUIRES
 EACH TO BE FULLY ACCESSIBLE. IT APPEARS THERE IS ONLY
 ONE (1) FRONT OF THE HOUSE TOILET ROOM. THE SECOND
 TOILET ROOM APPEARS TO BE ACCESSIBLE THROUGH A STORAGE
 ROOM. PER WPB FBC 107.2.1, CLARIFY. PER FBC PL 403.3.1,
 THE ROUTE TO THE PUBLIC TOILET FACILITIES SHALL NOT
 PASS THROUGH KITCHENS, STORAGE ROOMS OR CLOSETS. THE
 PUBLIC SHALL HAVE ACCESS TO THE REQUIRED TOILET
 FACILITIES AT ALL TIMES THAT THE BUILDING IS OCCUPIED.
 ADDITIONALLY, IDENTIFY MEN'S AND WOMEN'S TOILET ROOMS.
 PROVIDE SIGNAGE AS REQUIRED BY FBC PL 403.4.
  
 3.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 REVIEW THE FOLLOWING AND
 PROVIDE/REVISE PLAN AND ELEVATION DETAILS AS REQUIRED
 FOR TOILET ROOMS AND OTHER ACCESSIBLE FIXTURES:
 . A. PROVIDE DIMENSIONS OF EACH TOILET ROOM.
 . B. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL
 OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
 . C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 . D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 . E. FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 . F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 . G. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 . H. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE.
 . I. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 . J. PER FBC 606.5 EXPOSED PIPES AND SURFACES. EXPOSED
 WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT.
 . K. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 . L. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 . M. SHOW ALL CLEAR FLOOR OR GROUND SPACES FOR
 LAVATORIES AND SINKS COMPLYING WITH 305 POSITIONED FOR
 A FORWARD APPROACH AND CENTERED ON THE UNIT. KNEE AND
 TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED PER
 FBC ACC 602.2.
 . N. REGARDING FRONT OF THE HOUSE TOILET ROOM WITH DOOR
 SWING-IN PROVIDE CLEAR FLOOR SPACE FOR LAVATORY WHEN
 DOOR IS OPENED.
 . O. SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1
 OR 304.3.2.
 . P. DOORS SHALL BE PERMITTED TO SWING INTO TURNING
 SPACES PER FBC ACC 304.4.
 . Q. REGARDING THE KITCHEN SINK, PLEASE NOTE WHERE
 SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER
 THAN ONE, OF EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM
 OR SPACE SHALL COMPLY WITH 606 PER FBC ACC 212.3.
  
 4. THERE IS A KITCHEN WHICH INCLUDES A RANGE WITH A
 GREASE HOOD, AN APPARENT KITCHEN SINK WITH DISHWASHER.
 APPARENTLY, THERE WILL BE FOOD PREP. PER WPB FBC
 107.2.1, PROVIDE A GREASE INTERCEPTOR TO COMPLY WITH
 THE REQUIREMENTS OF FBC PL 1003.3.1. PER WPB FBC
 107.2.1, PROVIDE A SPECIFICATION, SCHEDULE, DETAIL AND
 CALCULATIONS FOR THE SAME. PLEASE NOTE, PER FBC PL
 1003.3.2, A FOOD WASTE DISPOSER SHALL NOT DISCHARGE TO
 A GREASE INTERCEPTOR.
  
 5. PER WPB FBC 107.2.1, SUBMIT FOR REVIEW
 MANUFACTURER'S SPEC/INSTALLATION MANUAL FOR DISHWASHER.
 APPROVED MANUFACTURER'S SPEC/INSTALLATION MANUALS SHALL
 BE ON SITE PRIOR TO INSPECTION. PROVIDE SCHEDULE FOR
 THE SAME; ITEM SHALL COMPLY WITH FBC PL 409.1; INDICATE
 APPROPRIATE STANDARDS FOR MACHINE. PROVIDE DETAIL FOR
 PLUMBING CONNECTIONS; COMPLY WITH REQUIREMENTS OF FBC
 PL 409.2, 409.3 AND 409.4 AS IS APPLICABLE.
  
 6. THE PLUMBING PLAN INDICATES THAT THE APPARENT
 KITCHEN SINK IN THE KITCHEN IS A SERVICE SINK. THE
 INTENT OF THE REQUIRED SERVICE SINK AS REQUIRED IN FBC
 PL TABLE 403.1, IS TO PROVIDE A SUITABLE FIXTURE FOR
 CUSTODIAL DUTIES/SERVICES. PER WPB FBC 107.2.1. PROVIDE
 A DESIGNATED SERVICE SINK THAT WILL MEET THE CRITERIA.
 PROVIDE A DETAIL FOR THE SAME.
  
 7. PER WPB FBC 107.2.1, PROVIDE FINISH WALL SCHEDULES
 FOR TOILET ROOMS AND SERVICE SINK. COMPLY WITH FBC PL
 310.3 AND FBC 1210.2.2. WALLS AND PARTITIONS WITHIN 2
 FEET (610 MM) OF SERVICE SINKS, URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. PLEASE NOTE
 THAT FBC 1210.2.2 STIPULATES THAT THE MATERIAL BE
 "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 8. IF SLABS ARE TO BE CUT AND REMOVED FOR UNDERSLAB
 WORK, THEN PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR
 DETAIL. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS OF THE CONCRETE TO BE REPLACED, AND THE PSI
 OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF THE
 DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE EXISTING
 SLAB, THE ANCHORING MATERIAL FOR THE DOWELS AND THE
 SPACING OF THE DOWELS ON CENTER. THE REPAIR SHALL ALSO
 INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED
 VAPOR BARRIER OVER WELL-COMPACTED SOIL. A COPY OF THE
 TERMITE CERTIFICATE SHALL BE ONSITE FOR A FINAL
 INSPECTION.
  
 9. PER WPB FBC 107.2.1, SUBMIT FOR REVIEW
 MANUFACTURER'S SPEC/INSTALLATION MANUAL FOR WATER
 HEATERS AND RECIRCULATING PUMP. APPROVED MANUFACTURER'S
 SPEC/INSTALLATION MANUALS SHALL BE ON SITE PRIOR TO
 INSPECTION.
  
 10.PER WPB FBC 107.2.1, PROVIDE EQUIPMENT SCHEDULE FOR
 ACCUMIX TANKLESS WATER HEATER INDICATING MANUFACTURER,
 MODEL NUMBER, GPM AND ELECTRICAL CHARACTERISTICS;
 PROVIDE DETAIL. IF IT IS ALSO A WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070, PROVIDE
 NOTE.
  
 11.PER WPB FBC 107.2.1, PROVIDE EQUIPMENT SCHEDULE FOR
 TANK TYPE WATER HEATER INDICATING MANUFACTURER, MODEL
 NUMBER, STORAGE CAPACITY AND ELECTRICAL
 CHARACTERISTICS. ALL DRAWINGS/SCHEDULE OF TANK TYPE
 WATER HEATER STORAGE CAPACITY SHALL BE CONSISTENT WITH
 EACH OTHER.
  
 12.PROVIDE EQUIPMENT SCHEDULE FOR RECIRCULATING PUMP
 INDICATING MANUFACTURER, MODEL NUMBER, GPM, HEAD, TYPE
 OF CONTROLS (COMPLY WITH FBC EC R403.5.2) AND
 ELECTRICAL CHARACTERISTICS
  
 13.PER WPB FBC 107.2.1, PROVIDED DETAIL OF TANK TYPE
 WATER HEATER INSTALLATION SHALL INCLUDE BUT NOT BE
 LIMITED TO THE FOLLOWING:
 . A.THE INCORPORATION OF RECIRCULATION PUMP
 . B.PIPING ARRANGEMENT, SIZES, SHUT OFF VALVES, CHECK
 VALVES, BALANCING VALVES, PUMP CONTROL DEVICE (COMPLY
 WITH FBC EC R403.5.2), INTER-CONNECTIONS, ETC. A
 SCHEMATIC AS OPPOSED TO ISOMETRIC IS ACCEPTABLE AND
 SOMETIMES PRESENTS A MORE LEGIBLE PRESENTATION.
 . C.T&P RELIEF DISCHARGING TO THE EXTERIOR SHALL BE
 FULL SIZE AND TERMINATE IN A SPACE THAT IS READILY
 OBSERVABLE BY THE BUILDING OCCUPANTS PER FBC PL
 504.6(3) AND 504.6(7). NOTE THAT PER FBC PL 504.6(14),
 IF THE RELIEF VALVE DISCHARGE PIPING IS INSTALLED WITH
 INSERT FITTINGS, THE PIPE SIZE SHALL BE ONE NOMINAL
 SIZE LARGER THAN THE SIZE OF THE RELIEF VALVE OUTLET
 AND THE OUTLET END OF SUCH TUBING SHALL BE FASTENED IN
 PLACE.
 . D.PER WPB FBC 107.2.1, EXPANSION TANK SHALL BE
 CONNECTED TO THE WATER HEATER COLD WATER SUPPLY PIPE AT
 A POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES,
 PRESSURE REDUCING VALVES AND BACKFLOW PREVENTERS.
 . E.PER FBC PL 504.2, IF THE WATER HEATER IS BOTTOM FED
 IT SHALL HAVE A VACUUM RELIEF COMPLYING WITH ANSI
 Z21.22 INSTALLED IN THE COLD-WATER SUPPLY.
 . F.PAN SHALL BE CONSTRUCTED OF MATERIALS COMPLYING
 WITH FBC PL 504.7.
 . G.PAN SHALL BE A MINIMUM OF 11/2 INCHES (38 MM) IN
 DEPTH AND SHALL BE OF SUFFICIENT SIZE AND SHAPE TO
 RECEIVE ALL DRIPPING OR CONDENSATE FROM THE TANK OR
 WATER HEATER. THE PAN SHALL BE DRAINED BY AN INDIRECT
 WASTE PIPE HAVING A DIAMETER OF NOT LESS THAN 3/4 INCH
 (19 MM). PIPING FOR SAFETY PAN DRAINS SHALL BE OF THOSE
 MATERIALS LISTED IN TABLE 605.4 PER FBC PL 504.7.1.
 . H.THE PAN DRAIN SHALL EXTEND FULL SIZE AND TERMINATE
 OVER A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR
 FLOOR DRAIN OR EXTEND TO THE EXTERIOR OF THE BUILDING
 AND TERMINATE NOT LESS THAN 6 INCHES (152 MM) AND NOT
 MORE THAN 24 INCHES (610 MM) ABOVE THE ADJACENT GROUND
 SURFACE PER FBC PL 504.7.2.
  
 14.PER FBC E607.5 AND FBC EC C404.4 WPB FBC 107.2.1,
 PROVIDE INSULATION FOR THE HOT WATER SUPPLY AND RETURN.
 PER WPB FBC 107.2.1, PROVIDE INSULATION SPECIFICATION
 FOR THE SAME COMPLYING WITH FBC EC TABLE C403.2.10.
  
 15.PER WPB FBC 107.2.1, PROVIDE PLUMBING/EQUIPMENT/
 FIXTURE SCHEDULE TO INCLUDE NEW AND REMAINING EXISTING
 FIXTURES, EQUIPMENT INCLUDING APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 AS REQUIRED BY FBC PL 419.5, 607.1.2 AND
 WATER-HAMMER ARRESTORS THAT CONFORM TO ASSE 1010 AS
 REQUIRED FOR QUICK-CLOSING VALVES INCLUDING DISHWASHERS
 BY FBC PL 604.9. ADDITIONALLY, SHOW LOCATIONS ON RISER
 DIAGRAM AND IDENTIFY THE SAME.
  
 16.PER WPB FBC 107.2.1, PROVIDE SIZE OF EXISTING
 INCOMING WATER SERVICE AND SHOW LOCATION, TYPE AND SIZE
 OF EXISTING BACKFLOW PREVENTOR FOR WATER SERVICE.
  
 17.PER WPB FBC 107.2.1, REVISE NOTE 11 BY REPLACING THE
 DESIGNATED M COPPER WITH L AS PER COPPER & COPPER ALLOY
 TUBE AND PIPE STANDARDS PUBLISHED BY THE COPPER
 DEVELOPMENT ASSOCIATION STATES "SEAMLESS COPPER WATER
 TUBE IS MANUFACTURED IN SIZES 1/4 INCH THROUGH 12 INCH
 NOMINAL. TYPES K AND L ARE MANUFACTURED IN DRAWN TEMPER
 (HARD) 1/4 INCH THROUGH 12 INCH AND ANNEALED TEMPER
 (SOFT) COILS 1/4 INCH THROUGH 2 INCH WHILE TYPE M IS
 ONLY MANUFACTURED IN DRAWN (HARD) TEMPER 1/4 INCH
 THROUGH 12 INCH."
  
 18.PER WPB FBC 107.2.1, PROVIDE NOTE "ALL COMPONENTS IN
 THE DOMESTIC WATER SYSTEM SHALL BE LEAD FREE."
  
 19.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR
 PLUMBING VALVES.
  
 20.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION AND
 DETAIL FOR PIPE HANGERS. SPECIFY SPACING TO COMPLY WITH
 FBC PL TABLE 308.5.
  
 21.PER WPB FBC 107.2.1, DELETE NOTE 17 ON PLUMBING PLAN
 REFERENCING GAS PIPE.
  
 22.RE: WATER RISER DIAGRAM; SUSPENDED COLD WATER IS 3/4
 INCH, HOWEVER AT THE HEATER IS 1"C(32FU). PER WPB FBC
 107.2.1, CLARIFY.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21031651 1254 OKEECHOBEE RD
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-20 Cont ID  
Sent By medwards Date 2021-08-20 Time 14:28 Rev Time 0.00
Received By medwards Date 2021-08-20 Time 14:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-07-09 Cont ID  
Sent By medwards Date 2021-07-09 Time 09:10 Rev Time 0.00
Received By medwards Date 2021-07-09 Time 09:10 Sent To  
Notes
2021-07-09 09:12:24A LICENSED ENGINEER MUST DIGITALLY SIGN THE EQUIPMENT
 SIZING CALCULATIONS, OR THE MECHANICAL CONTRACTOR THAT
 HOLDS THE PERMIT TO DO THE WORK ON THIS PROJECT CAN
 PRINT AND SIGN THEIR NAME. FS 471.003(H)
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 13:28 Rev Time 0.00
Received By medwards Date 2021-05-04 Time 13:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-08-13 Cont ID  
Sent By awooten Date 2021-08-13 Time   Rev Time 0.00
Received By awooten Date 2021-08-13 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-07-15 Cont ID  
Sent By awooten Date 2021-07-15 Time   Rev Time 0.00
Received By awooten Date 2021-07-15 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-21 Cont ID  
Sent By awooten Date 2021-05-21 Time   Rev Time  
Received By awooten Date 2021-05-21 Time   Sent To  
Notes
***NONE***