Plan Review Details - Permit 21031619
Plan Review Stops For Permit 21031619
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-03 Cont ID  
Sent By rmcdouga Date 2021-05-03 Time 08:53 Rev Time 0.00
Received By rmcdouga Date 2021-04-30 Time 10:25 Sent To  
Notes
2021-05-03 07:54:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A3, THERE IS A WALL ID TAG (6) ON THE FLOOR
 PLAN, HOWEVER, THERE IS NO WALL TYPE (6) LISTED IN THE
 LEGEND. PLEASE CLARIFY. FBC AMENDMENTS 107.2.1
 2) ON SHEET A5 THE GUARDRAIL IS SPECIFIED AS 42" HIGH
 ON THE PLAN AND 36" IN THE DETAIL. PLEASE CLARIFY. FBC
 AMENDMENTS 107.2.1
 3) SUBMIT THE PRODUCT APPROVAL FOR THE AH160 ROOF TILE
 ADHESIVE. FAC RULE 61G20
 4) SUBMIT PRODUCT APPROVALS THAT HAVE BEEN VALIDATED OR
 CERTIFIED AS COMPLYING WITH THE 2020 FBC SEVENTH
 EDITION. THE PRODUCT APPROVAL FOR THE UNCLIPPED
 MULLIONS IS THE ONLY ONE THAT IS CERTIFIED TO COPY WITH
 THE 2020 FBC. FBC AMENDMENTS 107.2.1 & FAC RULE 61G20
 5) HI-LIGHT OR CIRCLE THE SPECIFIC ITEMS, SIZES, DESIGN
 PRESSURES, DETAILS, ETC. IN THE PRODUCT APPROVALS THAT
 WILL BE INSTALLED. FBC AMENDMENTS 107.2.1
 6) THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE THE PRODUCT APPROVALS IN WRITING. FBC
 AMENDMENTS 107.3.4
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-22 Cont ID  
Sent By equinone Date 2021-04-22 Time 08:35 Rev Time 0.00
Received By equinone Date 2021-04-22 Time 08:35 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By aborngra Date 2021-04-27 Time 09:07 Rev Time 0.00
Received By aborngra Date 2021-04-21 Time 16:21 Sent To  
Notes
2021-04-27 09:07:29THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. THE PERMIT VALUE EXCEEDS 50% OF THE IMPROVEMENT
 VALUE OF THE PROPERTY. THE PROPERTY IS REQUIRED TO
 COMPLY WITH CURRENT LANDSCAPING PERMITS PER SECTION
 94-442(C)(2) A. SINGLE FAMILY DWELLING UNITS. PLEASE
 SPEAK WITH RAY CARANCI, SENIOR LANDSCAPING PLANNER -
 [email protected] OR ANDREW BURNETT, LANDSCAPE PLANNER
 - [email protected] TO SHOW COMPLIANCE WITH CURRENT
 LANDSCAPING REQUIREMENTS OR SUBMIT A LANDSCAPING
 PERMIT. ZONING REVIEW WILL NOT PASS UNTIL A LANDSCAPING
 PERMIT NUMBER HAS BEEN ASSIGNED AND PAID FOR OR THE
 LANDSCAPE PLANNERS GIVE THE OKAY THAT IT COMPLIES.
 2. REVISE W9 TO HAVE OPTIONAL TEXTURED GLASS SUCH AS
 RAIN DROP TEXTURED GLASS. FROSTED GLASS IS NOT AN
 OPTION.
 3. ALL CGI WINDOWS AND DOORS SHALL USE AN EXTERNAL
 DIMENSIONAL MUNTIN PROFILE. FOR CGI PRODUCTS THIS IS
 THE SEMI-CONTOURED PROFILE.
 4. INDICATE COLOR OF S-TILE. TILE SHALL HAVE AN EARTH
 TONE COLOR.
 5. PROVIDE A MUNTIN DETAIL FOR THE FRONT DOOR AND FIXED
 WINDOW. THIS NEEDS TO MATCH THE CGI MUNTIN PROFILE.
 6. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS,
 GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION,
 LANDSCAPING. PLEASE ACKNOWLEDGE THIS.
  
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE. CONFIRM THAT
 THE PROPOSED PRODUCT(S) WILL COMPLY WITH THESE
 CONDITIONS.
 1. ALL REPLACEMENT WINDOWS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS) AND
 MATCH THE LOCATION/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS UNLESS AS OTHERWISE INDICATED BY A MODIFICATION
 OF THE WINDOW FRAME. WINDOW CASING SHALL NOT EXCEED
 BEYOND THE EXTERIOR WOOD FRAMING.
 2. ALL STREET OR SIDEWALK FACING GLASS SHALL BE CLEAR.
 ALL NON-STREET FACING GLASS SHALL BE CLEAR OR CLEAR
 WITH LOW-E COATING. NO TINT. OBSCURED TEXTURED GLASS
 MAY BE USED ON NON-STREET FACING BATHROOMS ONLY.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-03 Cont ID  
Sent By rmcdouga Date 2021-05-03 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2021-04-14 Time 15:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-20 Cont ID  
Sent By medwards Date 2021-04-20 Time 15:24 Rev Time 0.00
Received By medwards Date 2021-04-20 Time 15:10 Sent To  
Notes
2021-04-20 15:24:491ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21031619
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A MECHANICAL SUB-PERMIT IS REQUIRED.
  
 2) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
 THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-22 Cont ID  
Sent By ccole Date 2021-04-22 Time 13:21 Rev Time 0.00
Received By ccole Date 2021-04-22 Time 11:39 Sent To  
Notes
2021-04-22 13:21:301ST REVIEW FBC-2020 RES.
 PERMIT- 21031619
 4/21/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A7: PROVIDE A SHOWER PAN DETAIL- SECTIONS
 P2709.1 & P2709.2 FBC RES.
  
 2) A7: PROVIDE A CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND SEWER- P3005.2.3 FBC RES.
  
 3) A7: SHOW THE LOCATION OF THE SHUTOFF VALVES FOR THE
 WASHING MACHINE. THE VALVES SHALL BE IN A LOCATION THAT
 CAN BE ACCESSED- SEE SECTION P2903.9.3 FBC RES. AND
 DEFINITION OF ACCESS- SECTION 202 FBC P. THE VALVES
 CANNOT BE LOCATED BEHIND THE STACKABLE WASHER/DRYER
 UNIT.
  
 4) A7: THE WATER RISER SHOWS A POTABLE WATER BACKFLOW
 PREVENTER. PLEASE PLACE A NOTE TO INDICATE A SEPARATE
 PERMIT IS REQUIRED- SECTION 105.1 WPB. A FL. LICENSED
 PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT. AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-05-03 Cont ID  
Sent By rmcdouga Date 2021-05-03 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2021-05-03 Time 08:53 Sent To  
Notes
2021-05-03 08:57:18CONCERETE ROOF TILE - NOA NO. 19-0715.02
 UNDERLAYMENT- NOA NO. 20-0723.36
 NO PRODUCT APPROVAL SUBMITTED FOR ROOF TILE ADHESIVE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-03 Cont ID  
Sent By rmcdouga Date 2021-05-03 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2021-05-03 Time 08:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By aborngra Date 2021-04-27 Time 09:07 Rev Time 0.00
Received By aborngra Date 2021-04-27 Time 09:06 Sent To  
Notes
2021-04-27 09:07:14THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. THE PERMIT VALUE EXCEEDS 50% OF THE IMPROVEMENT
 VALUE OF THE PROPERTY. THE PROPERTY IS REQUIRED TO
 COMPLY WITH CURRENT LANDSCAPING PERMITS PER SECTION
 94-442(C)(2) A. SINGLE FAMILY DWELLING UNITS. PLEASE
 SPEAK WITH RAY CARANCI, SENIOR LANDSCAPING PLANNER -
 [email protected] OR ANDREW BURNETT, LANDSCAPE PLANNER
 - [email protected] TO SHOW COMPLIANCE WITH CURRENT
 LANDSCAPING REQUIREMENTS OR SUBMIT A LANDSCAPING
 PERMIT. ZONING REVIEW WILL NOT PASS UNTIL A LANDSCAPING
 PERMIT NUMBER HAS BEEN ASSIGNED AND PAID FOR OR THE
 LANDSCAPE PLANNERS GIVE THE OKAY THAT IT COMPLIES.
 2. REVISE W9 TO HAVE OPTIONAL TEXTURED GLASS SUCH AS
 RAIN DROP TEXTURED GLASS. FROSTED GLASS IS NOT AN
 OPTION.
 3. ALL CGI WINDOWS AND DOORS SHALL USE AN EXTERNAL
 DIMENSIONAL MUNTIN PROFILE. FOR CGI PRODUCTS THIS IS
 THE SEMI-CONTOURED PROFILE.
 4. INDICATE COLOR OF S-TILE. TILE SHALL HAVE AN EARTH
 TONE COLOR.
 5. PROVIDE A MUNTIN DETAIL FOR THE FRONT DOOR AND FIXED
 WINDOW. THIS NEEDS TO MATCH THE CGI MUNTIN PROFILE.
 6. SEPARATE PERMIT REQUIRED FOR FENCE/WALL, AWNINGS,
 GENERATOR, MECHANICAL/AC/POOL EQUIPMENT, IRRIGATION,
 LANDSCAPING. PLEASE ACKNOWLEDGE THIS.
  
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE. CONFIRM THAT
 THE PROPOSED PRODUCT(S) WILL COMPLY WITH THESE
 CONDITIONS.
 1. ALL REPLACEMENT WINDOWS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS) AND
 MATCH THE LOCATION/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS UNLESS AS OTHERWISE INDICATED BY A MODIFICATION
 OF THE WINDOW FRAME. WINDOW CASING SHALL NOT EXCEED
 BEYOND THE EXTERIOR WOOD FRAMING.
 2. ALL STREET OR SIDEWALK FACING GLASS SHALL BE CLEAR.
 ALL NON-STREET FACING GLASS SHALL BE CLEAR OR CLEAR
 WITH LOW-E COATING. NO TINT. OBSCURED TEXTURED GLASS
 MAY BE USED ON NON-STREET FACING BATHROOMS ONLY.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  
  