Plan Review Details - Permit 21031555
Plan Review Stops For Permit 21031555
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 16:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-09 Cont ID  
Sent By rmcdouga Date 2021-06-09 Time 11:56 Rev Time 0.00
Received By rmcdouga Date 2021-06-09 Time 11:56 Sent To  
Notes
2021-05-28 10:54:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A GENERATOR PAD DRAWING THAT SPECIFIES HOW
 THE GENERATOR IS ANCHORED TO RESIST WIND LOADS. IF YOU
 ARE USING A PREFABRICATED GENERATOR PAD SUBMIT THE
 SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR IT.
 SPECIFY THE WIND LOAD DATA ON THE DRAWING. FBC 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 3) SEE SIGNATURE REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-18 Cont ID  
Sent By equinone Date 2021-05-18 Time 14:48 Rev Time 0.00
Received By equinone Date 2021-05-18 Time 14:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-05-13 Cont ID  
Sent By lcrespo Date 2021-05-13 Time 10:46 Rev Time 0.00
Received By lcrespo Date 2021-05-13 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-23 Cont ID  
Sent By rmcphers Date 2021-07-23 Time 13:38 Rev Time 0.00
Received By rmcphers Date 2021-06-15 Time 16:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-09 Cont ID  
Sent By rmcdouga Date 2021-06-09 Time 12:00 Rev Time 0.00
Received By rmcdouga Date 2021-05-04 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-05-13 Cont ID  
Sent By lcrespo Date 2021-05-13 Time 10:47 Rev Time 0.00
Received By lcrespo Date 2021-05-13 Time 10:47 Sent To  
Notes
2021-05-13 10:47:44GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 16:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-09 Cont ID  
Sent By rmcdouga Date 2021-06-09 Time 11:56 Rev Time 0.00
Received By rmcdouga Date 2021-05-28 Time 10:36 Sent To  
Notes
2021-06-09 12:00:45THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 PREFABRICATED GENERATOR SLAB DRAWINGS. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & 61G1 OR FS 471 & 61G15
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-07-22 Cont ID  
Sent By kalexand Date 2021-07-22 Time 18:50 Rev Time 0.00
Received By kalexand Date 2021-07-22 Time 18:50 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-09 Cont ID  
Sent By kalexand Date 2021-06-09 Time 09:33 Rev Time 0.00
Received By kalexand Date 2021-06-09 Time 09:33 Sent To  
Notes
***NONE***