Plan Review Details - Permit 21031501
Plan Review Stops For Permit 21031501
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-14 Cont ID  
Sent By rmcphers Date 2021-06-14 Time 10:50 Rev Time 0.00
Received By rmcphers Date 2021-06-14 Time 10:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-24 Cont ID  
Sent By rmcphers Date 2021-05-24 Time 15:47 Rev Time 0.00
Received By rmcphers Date 2021-05-24 Time 15:34 Sent To  
Notes
2021-05-24 15:47:05COMMERCIAL ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING A0.0 IN "PROJECT DATA" THE COMMON CORRIDOR
 IS SHOWN AS NON RATED - AFTER REVIEWING PAST PERMITS
 FOR THE BUILDING IT HAS BEEN DETERMINED THAT THE
 EXISTING COMMON CORRIDOR HAS A 1 HOUR FIRE RATING.
 PLEASE SHOW THE HOURLY FIRE RATING FOR THE COMMON
 CORRIDOR. (IF THE ELEVATOR HOISTWAY IS PRESSURIZED
 PLEASE SHOW IN WRITING ON THE DRAWINGS)
 2) PLEASE SHOW THE HOURLY FIRE RATING FOR THE ADDED
 DOOR PER FBC 716.5
 3) PLEASE SHOW DOOR TO BE SELF CLOSING AND LATCHING PER
 FBC 716.5.9
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-09 Cont ID  
Sent By rmcphers Date 2021-04-09 Time 15:45 Rev Time 0.00
Received By rmcphers Date 2021-04-09 Time 15:16 Sent To  
Notes
2021-04-09 15:29:43COMMERCIAL ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE DOOR SWING ENCROACHMENT INTO THE
 EGRESS CORRIDOR TO COMPLY WITH FBC 1005.7 ENCROACHMENT.
 ENCROACHMENTS INTO THE REQUIRED MEANS OF EGRESS WIDTH
 SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THIS
 SECTION. FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
 2) A NEW OPENING IS BEING ADDED TO THE ELEVATOR LOBBY -
 PLEASE SHOW THE ELEVATOR HOISTWAY PROTECTION PER FBC
 3006.3
 3) PLEASE SHOW EXIT SIGNS WHERE REQUIRED PER FBC 1013.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-18 Cont ID  
Sent By jleahy Date 2021-05-18 Time 13:23 Rev Time 0.00
Received By jleahy Date 2021-05-18 Time 13:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-12 Cont ID  
Sent By jleahy Date 2021-04-12 Time 10:28 Rev Time 0.00
Received By jleahy Date 2021-04-12 Time 10:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-06-08 Cont ID  
Sent By pleduc Date 2021-06-08 Time   Rev Time 0.00
Received By pleduc Date 2021-06-08 Time 12:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-05-11 Cont ID  
Sent By pleduc Date 2021-05-11 Time   Rev Time 0.00
Received By pleduc Date 2021-05-11 Time 11:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-04-12 Cont ID  
Sent By pleduc Date 2021-04-12 Time   Rev Time 0.00
Received By pleduc Date 2021-04-12 Time 13:14 Sent To  
Notes
2021-04-12 13:29:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.1 - THE PROPOSED DOUBLE DOOR INDICATES
 THAT THEY OPEN UP INTO THE EGRESS CORRIDOR.
  
 THERE ARE NO DIMENSIONS SHOWING COMPLIANCE FOR DOOR
 LEAF ENCROACHMENT
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 PLEASE REVIEW AND PROVIDE DIMENSIONS OR CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-14 Cont ID  
Sent By rmcphers Date 2021-06-14 Time 10:50 Rev Time 0.00
Received By rmcphers Date 2021-06-07 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-24 Cont ID  
Sent By rmcphers Date 2021-05-24 Time 15:47 Rev Time 0.00
Received By rmcphers Date 2021-05-07 Time 15:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-16 Cont ID  
Sent By lmarchan Date 2021-04-16 Time 08:19 Rev Time 0.00
Received By lmarchan Date 2021-03-31 Time 06:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-04-12 Cont ID  
Sent By medwards Date 2021-04-12 Time 14:28 Rev Time 0.00
Received By medwards Date 2021-04-12 Time 14:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-14 Cont ID  
Sent By rmcphers Date 2021-06-14 Time 10:50 Rev Time 0.00
Received By rmcphers Date 2021-06-14 Time 10:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-09 Cont ID  
Sent By rmcphers Date 2021-04-09 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2021-04-09 Time 15:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-04-15 Cont ID  
Sent By aaponte Date 2021-04-15 Time 18:41 Rev Time 0.00
Received By aaponte Date 2021-04-15 Time 18:41 Sent To  
Notes
***NONE***