Plan Review Details - Permit 21031451
Plan Review Stops For Permit 21031451
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-29 Cont ID  
Sent By mcphers Date 2021-04-29 Time 13:44 Rev Time 0.00
Received By rmcphers Date 2021-04-29 Time 13:36 Sent To  
Notes
2021-04-29 13:43:58REVISIONS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT BOTH ENDS OF
 THE RAMPS TO COMPLY WITH FBC 505.10.1 RAMP HANDRAILS
 SHALL EXTEND HORIZONTALLY ABOVE THE LANDING FOR 12
 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. EXTENSIONS SHALL RETURN TO A WALL, GUARD, OR
 THE LANDING SURFACE, OR SHALL BE CONTINUOUS TO THE
 HANDRAIL OF AN ADJACENT RAMP RUN.
 2) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT TOP OF ALL
 STAIR TO COMPLY WITH FBC 505.10.2 AT THE TOP OF A STAIR
 FLIGHT, HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE
 LANDING FOR 12 INCHES (305 MM) MINIMUM BEGINNING
 DIRECTLY ABOVE THE FIRST RISER NOSING. EXTENSIONS SHALL
 RETURN TO A WALL, GUARD, OR THE LANDING SURFACE, OR
 SHALL BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT
 STAIR FLIGHT.
 3) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT BOTTOM OF ALL
 STAIR TO COMPLY WITH FBC 505.10.3 AT THE BOTTOM OF A
 STAIR FLIGHT, HANDRAILS SHALL EXTEND AT THE SLOPE OF
 THE STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT LEAST
 EQUAL TO ONE TREAD DEPTH BEYOND THE LAST RISER NOSING.
 EXTENSION SHALL RETURN TO A WALL, GUARD, OR THE LANDING
 SURFACE, OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT.
 4) HANDRAILS SHALL BE SHOWN ON BOTH SIDES OF RAMPS AND
 STAIR PER FBC 1011.11 AND FBC 1012.8
 5) DRAWING A2.0 - DOORS BETWEEN UNITS IN THE CORRIDOR
 WERE TO SWING IN PER APPROVED DRAWINGS AS TO NOT
 ENCROACH IN THE EGRESS PATH FBC 1005.7.1 - DOOR SWING
 ON ALL OTHER PLANS SHOULD MATCH.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-05-05 Cont ID  
Sent By fmittner Date 2021-05-05 Time 09:24 Rev Time 0.00
Received By fmittner Date 2021-05-05 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-05 Cont ID  
Sent By lmarchan Date 2021-05-05 Time 14:19 Rev Time 0.00
Received By lmarchan Date 2021-04-12 Time 09:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-29 Cont ID  
Sent By rmcphers Date 2021-04-29 Time 13:46 Rev Time 0.00
Received By rmcphers Date 2021-04-29 Time 13:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-05 Cont ID  
Sent By aaponte Date 2021-05-05 Time 09:24 Rev Time 0.00
Received By fmittner Date 2021-05-05 Time 09:24 Sent To  
Notes
2021-05-19 11:14:40PROVISO: FPL TRANSFORMER SHALL BE SCREENED WITH A
 HEDGE.