Plan Review Details - Permit 21031429
Plan Review Stops For Permit 21031429
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-04-05 Cont ID  
Sent By cpuell Date 2021-04-05 Time 17:22 Rev Time 0.00
Received By cpuell Date 2021-04-05 Time 17:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-15 Cont ID  
Sent By rmcphers Date 2021-06-15 Time 07:51 Rev Time 0.00
Received By rmcphers Date 2021-06-15 Time 07:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-07 Cont ID  
Sent By rmcphers Date 2021-05-07 Time 13:24 Rev Time 0.00
Received By rmcphers Date 2021-05-07 Time 13:16 Sent To  
Notes
2021-05-07 13:24:07NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ROOF SHEATHING ATTACHMENT. FBC
 R803.2.3.1
 2) PLEASE PROVIDE A SITE PLAN FBC 107.2.5 SITE PLAN.
 THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE
 APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE
 PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)
 3) PLEASE PROVIDE A SIGNED AND SEALED SURVEY SHOWING
 THE FLOOD ZONE BASED ON THE LATEST FIRM.
 4) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE
 LISTED ON THE DRAWINGS BY THE PRODUCT APPROVAL NUMBERS.
 5) STRUCTURAL DRAWINGS NEED TO BE SIGNED BY THE
 ENGINEER.
 FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN MAIL IN OR
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DEPT. AT THE CITY HALL

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By rmcphers Date 2021-04-21 Time 09:09 Rev Time 0.00
Received By rmcphers Date 2021-04-20 Time 16:16 Sent To  
Notes
2021-04-21 09:09:24NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CANNOT COMPLETE THE PLAN REVIEW - THE STRUCTURAL
 DRAWINGS ARE MISSING.
 2) PLEASE PROVIDE A SITE PLAN FBC 107.2.5 SITE PLAN.
 THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE
 APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE
 PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)
 3) PLEASE PROVIDE A SIGNED AND SEALED SURVEY SHOWING
 THE FLOOD ZONE BASED ON THE LATEST FIRM.
 4) PLEASE PROVIDE A ROOFING SHINGLES PRODUCT APPROVAL.
 (MIAMI DADE OR FLORIDA STATE)
 5) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE
 LISTED ON THE DRAWINGS BY THE PRODUCT APPROVAL NUMBERS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-05-24 Cont ID  
Sent By fgiaquin Date 2021-05-24 Time 21:27 Rev Time 0.00
Received By fgiaquin Date 2021-05-24 Time 21:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-05-12 Cont ID  
Sent By fgiaquin Date 2021-05-12 Time 22:45 Rev Time 0.00
Received By fgiaquin Date 2021-05-12 Time 21:53 Sent To  
Notes
2021-05-12 22:45:50NO RESPONSE LETTER WAS UPLOADED OR NEW PLANS. ZERO OF
 THE PREVIOUS PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By fgiaquin Date 2021-04-08 Time 22:26 Rev Time 0.00
Received By fgiaquin Date 2021-04-08 Time 21:22 Sent To  
Notes
2021-04-08 22:25:59ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SERVICE ENTRANCE CONDUCTORS ARE OF INSUFFICENT SIZE.
 LOAD FOR SERVICE IS SHOWN AS 271AMPS, AT 83% SERVICE
 ENTRANCE CONDUCTORS MUST CARRY A LOAD OF 225AMPS. 4/0
 CU REQUIRED. NEC 110.3B NEC 230.23
  
 2. EQUIPMENT GROUND SHOWN FROM METER-CAN TO MDP,
 EQUIPMENT GROUND ORIGINATES AT FIRST MEANS OF
 DISCONNECT, WHICH WOULD BE THE MDP, REMOVE EQUIPMENT
 GROUND FROM CONDUIT.
  
 3. NO MAINS SHOWN IN MDP, WHAT ARE THE SIZE OF THE
 MAINS?? FBC 107.2.1
  
 4. SEVERAL DISCREPANCIES ARE SHOWN ON RISER DIAGRAM,
 ONE NOTE SAYS " PARALLEL 3-350MCM RUNS" ANOTHER SAYS
 "PARALLEL 3-3/0 RUNS". PROVIDE ACCURATE AND CODE
 COMPLIANT RISER DIAGRAM. FBC 107.2.1
  
 5. SMOKE/CARBON ALARMS REQUIRED OUTSIDE OF BEDROOMS
 WITHIN 10' PER FBC-R 314 AND 315, PROVIDE CORRECTIONS.
  
 6. SMOKE ALARMS AND SMOKE/CARBON ALARMS MUST BE WITHIN
 12'' OF HIGHEST POINT OF CEILINGS. A NOTE ON PLAN
 STATING THIS WILL SUFFICE. FBC 107.2.1 NFPA 72
  
 7. GENERATOR ON PLANS REQUIRES A SEPARATE PERMIT WITH
 SEPARATE DRAWINGS. ATS CAN STAY ON PLAN BUT REMOVE
 GENERATOR FROM PLAN. FBC 107.2.1 FBC 105.1
  
 8. NO SPECS SUBMITTED OR SIZE OF ATS IS SHOWN ON PLAN.
 PROVIDE CORRECTIONS. FBC 107.2.1
  
 9. GARAGE DOOR OPENER RECEPTACLES REQUIRED GFCI
 PROTECTION PER NEC 210.8. PROVIDE CORRECTIONS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2021-07-08 Cont ID  
Sent By lmarchan Date 2021-07-08 Time 14:09 Rev Time 0.00
Received By lmarchan Date 2021-07-08 Time 07:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-06-25 Cont ID  
Sent By medwards Date 2021-06-25 Time 11:40 Rev Time 0.00
Received By medwards Date 2021-06-25 Time 11:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-06-15 Cont ID  
Sent By rmcphers Date 2021-06-15 Time 07:51 Rev Time 0.00
Received By rmcphers Date 2021-05-24 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-14 Cont ID  
Sent By lmarchan Date 2021-05-14 Time 09:51 Rev Time 0.00
Received By lmarchan Date 2021-05-13 Time 12:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-12 Cont ID  
Sent By fgiaquin Date 2021-05-12 Time 22:46 Rev Time 0.00
Received By fgiaquin Date 2021-04-28 Time 10:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-27 Cont ID  
Sent By lmarchan Date 2021-04-27 Time 14:44 Rev Time 0.00
Received By lmarchan Date 2021-04-26 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-22 Cont ID  
Sent By rmcphers Date 2021-04-22 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2021-03-30 Time 15:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-07-29 Cont ID  
Sent By lmarchan Date 2021-07-29 Time 12:48 Rev Time 0.00
Received By lmarchan Date 2021-07-15 Time 12:11 Sent To  
Notes
2021-07-28 16:21:47RECEIPT MU-2021-035914 - $12071.20 PAID
2021-07-15 12:11:487/15/21 EMAILED IMPACT FOR REVIEW AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By rmcphers Date 2021-04-21 Time 09:09 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 09:09 Sent To  
Notes
2021-04-21 09:11:39PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-07-08 Cont ID  
Sent By medwards Date 2021-07-08 Time 14:04 Rev Time 0.00
Received By medwards Date 2021-07-08 Time 14:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-07-01 Cont ID  
Sent By medwards Date 2021-07-01 Time 15:09 Rev Time 0.00
Received By medwards Date 2021-07-01 Time 15:05 Sent To  
Notes
2021-07-01 15:09:50PLEASE SEE THE SIGNATURE REVIEW COMMENTS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-06-03 Cont ID  
Sent By medwards Date 2021-06-03 Time 08:27 Rev Time 0.00
Received By medwards Date 2021-06-03 Time 08:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 15:00 Rev Time 0.00
Received By medwards Date 2021-05-04 Time 14:55 Sent To  
Notes
2021-05-04 15:19:48PLEASE UNDERSTAND THAT ONLY A FLORIDA LICENSED ENGINEER
 OR FLORIDA LICENSED MECHANICAL CONTRACTOR MUST BE
 RESPONSIBLE FOR THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS AND THE MECHANICAL DESIGN.
  
 1) A MECHANICAL SUB-PERMIT IS REQUIRED.
  
 2) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
 THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-09 Cont ID  
Sent By medwards Date 2021-04-09 Time 12:45 Rev Time 0.00
Received By medwards Date 2021-04-09 Time 12:23 Sent To  
Notes
2021-04-09 12:45:421ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21031429
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A MECHANICAL SUB-PERMIT IS REQUIRED.
  
 2) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
 THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB.
  
 A REVIEW OF THE DRAWINGS WILL BE COMPLETED ONCE THE
 LICENSED ENGINEER HAS SUBMITTED THE REQUIRED DOCUMENTS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-04-19 Cont ID  
Sent By abelisle Date 2021-04-19 Time 17:22 Rev Time 0.00
Received By abelisle Date 2021-04-19 Time 17:21 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2021-06-15 Cont ID  
Sent By rmcphers Date 2021-06-15 Time 07:51 Rev Time 0.00
Received By rmcphers Date 2021-06-15 Time 07:51 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-05-07 Cont ID  
Sent By rmcphers Date 2021-05-07 Time 13:25 Rev Time 0.00
Received By rmcphers Date 2021-05-07 Time 13:25 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By rmcphers Date 2021-04-21 Time 09:11 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 09:11 Sent To  
Notes
2021-04-21 09:12:04SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status N Date 2021-07-08 Cont ID  
Sent By medwards Date 2021-07-08 Time 14:04 Rev Time 0.00
Received By medwards Date 2021-07-08 Time 14:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2021-07-01 Cont ID  
Sent By medwards Date 2021-07-01 Time 15:04 Rev Time 0.00
Received By medwards Date 2021-07-01 Time 15:03 Sent To  
Notes
2021-07-01 15:08:56PLEASE PROVIDE THE DOCUMENTS REQUESTED IN THE LAST 3
 REVIEWS. I DID NOT ASK FOR THE MECHNAICAL CONTRACTOR TO
 SIGN THE DRAWINGS. I DID ASK THAT HE SIGN THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS OR AN
 ENGINEER.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-06-25 Cont ID  
Sent By medwards Date 2021-06-25 Time 11:39 Rev Time 0.00
Received By medwards Date 2021-06-25 Time 11:36 Sent To  
Notes
2021-06-25 11:38:12PLEASE PROVIDE THE DOCUMENTATION REQUESTED. THIS LAST
 SUBMITTAL WAS A SIGNED ENERGY PERFORMANCE LEVEL DISPLAY
 CARD. THIS IS NOT WHAT WAS REQUESTED. SEE BELOW:
  
 A LICENSED ENGINEER OR THE MECHANICAL CONTRACTOR THAT
 HOLDS THE PERMIT TO INSTALL THE MECHANICAL EQUIPMENT
 FOR THIS PROJECT MUST DIGITALLY SIGN AND SEAL THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-06-03 Cont ID  
Sent By medwards Date 2021-06-03 Time 08:27 Rev Time 0.00
Received By medwards Date 2021-06-03 Time 08:27 Sent To  
Notes
2021-06-03 08:42:29A LICENSED ENGINEER OR THE MECHANICAL CONTRACTOR THAT
 HOLDS THE PERMIT TO INSTALL THE MECHANICAL EQUIPMENT
 FOR THIS PROJECT MUST DIGITALLY SIGN AND SEAL THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-18 Cont ID  
Sent By medwards Date 2021-05-18 Time 17:03 Rev Time 0.00
Received By medwards Date 2021-05-18 Time 16:56 Sent To  
Notes
2021-05-18 17:03:54ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS ROUTED TO
 STORAGE. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 15:20 Rev Time 0.00
Received By medwards Date 2021-05-04 Time 15:20 Sent To  
Notes
2021-05-04 15:20:37PLEASE UNDERSTAND THAT ONLY A FLORIDA LICENSED ENGINEER
 OR FLORIDA LICENSED MECHANICAL CONTRACTOR MUST BE
 RESPONSIBLE FOR THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS AND THE MECHANICAL DESIGN.
  
 1) A MECHANICAL SUB-PERMIT IS REQUIRED.
  
 2) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
 THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By rmcphers Date 2021-04-21 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 09:13 Sent To  
Notes
2021-04-21 09:14:19SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 1 Status P Date 2021-04-21 Cont ID  
Sent By rthermid Date 2021-04-21 Time   Rev Time  
Received By rthermid Date 2021-04-21 Time   Sent To I
Notes
***NONE***