Plan Review Details - Permit 21031428
Plan Review Stops For Permit 21031428
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-22 Cont ID  
Sent By rmcdouga Date 2021-06-22 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2021-06-22 Time 15:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-24 Cont ID  
Sent By rmcdouga Date 2021-05-24 Time 14:14 Rev Time 0.00
Received By rmcdouga Date 2021-05-24 Time 14:04 Sent To  
Notes
2021-05-24 14:14:10PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [NOT COMPLIED. THE NEW WINDLOAD CALCULATIONS FROM
 THE ENGINEER ARE FOR EXPOSURE CATEGORY C. THIS
 STRUCTURE IS LOCATED IN EXPOSURE CATEGORY D.] THE
 WINDLOAD CHART IS FOR EXPOSURE CATEGORY C AND THIS
 PROJECT IS LOCATED IN EXPOSURE CATEGORY D WITH A 170
 MPH WINDSPEED. PLEASE CORRECT. FBC 1609
  
 2) [NOT COMPLIED. THE LOCATIONS OF THE OPENINGS FROM
 THE BUILDING'S CORNERS WERE NOT PROVIDED.] THE
 PRESSURES THAT ARE MARKED IN THE WINDLOAD TABLE ARE FOR
 INTERIOR WALL ZONE 4. THE WINDLOAD PRESSURES FOR THE
 ZONE 5 CORNER AREAS ARE SIGNIFICANTLY MORE. SPECIFY THE
 LOCATION OF THE OPENINGS FROM THE CORNER OF THE
 BUILDING. USE THE BUILDINGS HEIGHT AND THE SMALLER OF
 THE WALL LENGTHS TO DETERMINE THE WIDTH OF ZONE 5 FROM
 THE CORNER OF THE BUILDING IN THE CHART BELOW THE
 WINDLOAD CHART. FBC AMENDMENTS 107.2.1 AND FBC 1609

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-09 Cont ID  
Sent By rmcdouga Date 2021-04-09 Time 10:58 Rev Time 0.00
Received By rmcdouga Date 2021-04-09 Time 09:59 Sent To  
Notes
2021-04-09 10:25:58PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WINDLOAD CHART IS FOR EXPOSURE CATEGORY C AND
 THIS PROJECT IS LOCATED IN EXPOSURE CATEGORY D WITH A
 170 MPH WINDSPEED. PLEASE CORRECT. FBC 1609
  
 2) THE PRESSURES THAT ARE MARKED IN THE WINDLOAD TABLE
 ARE FOR INTERIOR WALL ZONE 4. THE WINDLOAD PRESSURES
 FOR THE ZONE 5 CORNER AREAS ARE SIGNIFICANTLY MORE.
 SPECIFY THE LOCATION OF THE OPENINGS FROM THE CORNER OF
 THE BUILDING. USE THE BUILDINGS HEIGHT AND THE SMALLER
 OF THE WALL LENGTHS TO DETERMINE THE WIDTH OF ZONE 5
 FROM THE CORNER OF THE BUILDING IN THE CHART BELOW THE
 WINDLOAD CHART. FBC AMENDMENTS 107.2.1 AND FBC 1609

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-22 Cont ID  
Sent By rmcdouga Date 2021-06-22 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2021-06-02 Time 15:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-24 Cont ID  
Sent By rmcdouga Date 2021-05-24 Time 14:14 Rev Time 0.00
Received By rmcdouga Date 2021-05-14 Time 13:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-09 Cont ID  
Sent By rmcdouga Date 2021-04-09 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2021-03-29 Time 14:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-24 Cont ID  
Sent By rmcdouga Date 2021-05-24 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2021-05-24 Time 14:04 Sent To  
Notes
2021-05-24 14:21:23THE SIGNATURES ON ANY NEW DOCUMENTS WILL HAVE TO BE
 VALIDATED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-09 Cont ID  
Sent By rmcdouga Date 2021-04-09 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2021-04-09 Time 09:59 Sent To  
Notes
2021-04-09 10:00:52THE WINDLOAD CHART DOES NOT HAVE THE ENGINEER'S DIGITAL
 SIGNATURE. ELECTRONICALLY SUBMITTED DRAWINGS AND
 DOCUMENTS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15